1MRK506375-UEN Rev. N
Instantaneous samples
Peak value(SMAI o/p)
RMS value(SMAI o/p)
TRIGFLTUI
IL1MAXPK
IL1MAX
FLTIL1MAG
IL1
IL2MAXPK
IL2MAX
FLTIL2MAG
IL2
IEC21000241 V1 EN-US
Figure 171:
Maximum peak and RMS current calculation
15.13.4
Setting guidelines
The setting parameters for fault current and voltage reporting function FLTMMXU can be set via
Protection and Control Manager PCM600.
Operation: To disable/enable the operation of fault current and voltage reporting function, that is,
Off/On.
PreTrig: To set the number of power system cycles to be considered for fault event data window prior
to positive edge of the binary input TRIGFLTUI.
PostTrig: To set the number of power system cycles to be considered for fault event data window
after the positive edge of binary input TRIGFLTUI.
Railway application RER670
Application manual
PreTrig
Time duration for maximum peak and
© 2017 - 2023 Hitachi Energy. All rights reserved
PostTrig
RMS current calculation
Section 15
Monitoring
GUID-0A8DF112-1058-4B1C-BEB2-AAD055D99646 v2
349