Hitachi Relion 670 Series Applications Manual page 103

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506375-UEN Rev. N
X1FwZ4: To set the forward positive sequence reactance reach of zone 4 in Ohm/p. It may be set
identical to X1RvZ4.
X1RvZ4: To set the reverse positive sequence impedance reach of zone 4 in Ohm/p. It should be set
less than zone 1 reach of distance protection for the shortest line in the reverse direction.
REoverRLZ4: To set the earth return compensation factor for resistance of zone 4. It provides zero
sequence compensation for phase-to-earth faults.
XEoverXLZ4: To set the earth return compensation factor for reactance of zone 4. It provides zero
sequence compensation for phase-to-earth faults.
RFPEFwZ4: To set the forward fault resistive reach in Ohm/p for the phase-to-earth faults in zone 4.
This may be set identical to RFPERVZ4.
RFPERvZ4: To cover the zone 4 fault resistive reach in Ohm/p for phase-to-earth faults in reverse
direction. It should cover apparent phase-to-earth bus fault resistance allowing for multiple infeed
from other circuits. Therefore, it should be set identical to zone 3 resistive reach setting.
RFPPFwZ4: To set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 4.
This may be set identical to RFPPRVZ4.
RFPPRvZ4: To cover the zone 4 fault resistive reach in Ohm/p for phase-to-phase faults in reverse
direction. It should cover apparent phase-to-phase bus fault resistance allowing for multiple infeed
from other circuits. Therefore, it should be set identical to zone 3 resistive reach setting.
TimerSelZ4: To set the zone timer selection mode of zone 4. i.e. Timers separated, Timers linked,
General start, PhSel start, Internal start and External start. The default setting is Timers separated.
OpModetPEZ4: To set the Off/On operation of the phase-to-earth timer of zone 4. The default setting
is Off.
tPEZ4: To set the time delay to trip for phase-to-earth faults in zone 4. It should be set identical to
zone 2 timer setting.
OpModetPPZ4: To set the Off/On operation of the phase-to-phase timer of zone 4. The default
setting is Off.
tPPZ4: To set the time delay to trip for phase-to-phase faults in zone 4. It should be set identical to
zone 2 timer setting.
Zone 5
OpZ5: For the Off/On operation of zone 5 and it is set to Off by default. This Zone can be used for
the permissive overreach scheme along with a communication channel.
DirModeZ5: To set the zone 5 direction mode. It can be set to Non-directional, Forward and Reverse.
The default setting is Forward direction mode.
PhSelModeZ5: To enable the measuring loops of zone 5. It can be set to Phsel logic, Release L1E,
ReleaseL2E, Release PE, Release L1L2 and Release PE&PP modes. The default setting is Phsel
logic mode.
LCModeZ5: To enable/disable the adaptive load compensation mode of zone 5. It avoids
overreaching of the zone in to the next section in case of resistive fault due to remote end feed.
Generally, this setting is not needed for zone 5. The default setting is Off.
X1FwZ5: To set the forward positive sequence reactance reach of zone 5 in Ohm/p. It may be set
identical to either zone 2 or zone 3 reach settings.
X1RvZ5: To set the reverse positive sequence impedance reach of zone 5 in Ohm/p. It may be set
identical to X1FwZ5.
Railway application RER670
Application manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 7
Impedance protection
GUID-B9AD6153-0B91-4C1C-AAE1-E387AAC02A98 v4
97

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer670

Table of Contents