4.3.13

Operation as cold store door (as of V1.13)

Function description
To use the ATD4xxW control unit to control a cold store door, further settings have to be made
in addition to the FBLOCK configuration of the input signals (see section "5.4.1 Digital input
signals (Page 132)")
Note: The increased force in the first 10 cm to open the cold store door is only available when the
opening signal is issued via the digital inputs.
This means that it is possible that the door cannot be opened when commands are given via the
service buttons on the control unit, the service menu or via the SIDOOR user software.
The procedure for the configuration of the ATD4xxW control unit as a cold store door is described
below:
1. Start a learn run with a new motor, service menu: "General setup -> Start learn run with new
motor"
2. If no output transmission has been previously parameterized, the input prompt: "Output
transmission" is now displayed.
3. After entering the output transmission, start the learn run again via the service menu:
"General setup -> Start learn run with new motor".
4. If the learn run has been performed successfully, the 7 segment display shows "u"
5. Set the FBLOCK logic for the circuiting of the input signals as a cold store door, service menu:
"General setup > Special parameters > Default command mode > FBLOCK configuration >
FBLOCK config. cold storage mode"
6. Set the command priority (for ATD401W this should already have been preset at the factory),
service menu: "General setup > Special parameters -> Default command mode -> FBLOCK +
relay".
7. If required, the hold-open time for the opening button can be modified, service menu:
"General setup > Special parameters > Hold-open time standard"
If the FBLOCK logic is set to cold storage door 6 seconds is preset as the default value for the
hold-open time. The value 0 means pulsed operation. This means Press button once = OPEN,
press button again = CLOSED.
8. If required, the behavior of the cord-operated switch can be modified, service menu: "General
setup -> Special parameters -> Hold-open time cord-operated switch".
The default value is 0. The value 0 means pulsed operation. This means Actuate cord-
operated switch once = OPEN, actuate button again = CLOSE.
110
The value 176 mm/rev has to be set here for the SIDOOR default motors M3, M4 or M5.
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA