Huawei FusionModule1000A20 Commissioning Manual page 65

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 Prefabricated All-in-One
Data Center
Commissioning Guide
Issue 03 (2022-12-15)
NO TE
● A password is required to log in to the configurations page. Set the password by using
the Up, Down, and Enter buttons. The initial password is 0001.
● Language setting: Default screen > Main Menu > Device Configuration > Language.
On the default screen, hold down
On the main menu screen, select system configuration and press
The following table lists the system configuration attributes and values.
Table 9-1 System configuration attributes and values
Item
Rated operating
voltage
Rated frequency
Number of Phases
LN1
Number of Phases
LN2
Secondary load
Generator Usage
Power supply
priority
On the main menu screen, select device configuration and press
the device configuration screen, you can set thresholds for parameters.
Copyright © Huawei Digital Power Technologies Co., Ltd.
. The main menu screen is displayed.
Value
110 V/57 V; 115 V/66 V; 120
V/70 V; 208 V/120 V; 220
V/127 V; 230 V/132 V; 240
V/138 V; 227 V/160 V; 347
V/200 V; 380 V/220 V; 400
V/230 V; 415 V/240 V; 440
V/254 V; 480 V/277 V
50 Hz; 60 Hz
Single phase; three-phase
four-wire; three-phase
three-wire
Single phase; three-phase
four-wire; three-phase
three-wire
Not Used; Opening Only;
Opening And Closing
No Generator; Generator In
Use
Line 1-Switch I; Line 2-
Switch II; No Line Priority
9 Commissioning Core Components
Description
The default value is
380 V/220 V. Set the
parameter based on
site requirements.
The default value is 50
Hz. Set the parameter
based on site
requirements.
The default value is
three-phase four-wire.
The default value is
three-phase four-wire.
The default value is
Not Used.
The default value is No
generator. Set the
parameter based on
site requirements.
The default value is
Line 1-Switch I. Set the
parameter based on
site requirements.
.
. On
58