USB Checker
This will be used to detect the actual USB port where transmission adaptor is inserted.
Note that this will not be displayed if the driver for the U10 USB Network Interface is
not installed. This will not be displayed for re-scanning.
<Detection Mechanism>
• Insert the transmission adaptor (U10 Network Interface) into the USB port.
(This requires that software installation is already completed).
• When clicking the [USB Checker] in the scanning setting screen, following screen will
be displayed.
• In this screen, click the U10 USB Network Interface pull-down list box and select any
USB port, then push the [Light] button.
• If the selected USB port is the actual porting connecting the U10 USB Network In-
terface, [SVC] in this screen and LED (SVC) of the transmission adaptor will flicker 4
times. (If the port differs, there will be no flicker).
• When the USB port No. is confirmed, close the screen and set the USB No. port in
the above procedure
USB Network Interface was detected.
*1 When not checked, since scanning is not performed, the scanning objective
Note
refrigerant circuit address cannot be set.
*2
When Perform System Initialization checked
Normally, perform bus priority mode scanning. Full scanning which can
receive detail data is performed. However, since each unit performs scan
dedicated special operation, the units of the entire VRF System temporar-
ily stop. To start scanning, check if the VRF System can be completely
stopped, then execute scanning. Since the units remain stopped even
when scanning is finished, a restart command must be sent from the con-
trol unit.
When Perform System Initialization not checked (S/V series)
Use when scanning at sites at which the VRF System cannot be stopped.
In this mode, scanning can be performed without affecting the operat-
ing status of the VRF System. However, since R.C group data cannot be
received, it is not full scanning. Operation is not controlled in R.C. group
units.
• When Single-Split Adaptor (UTR-YRDA) is connected within the VRF sys-
tem, be sure to check the "Perform System Initialization" when performing
scanning in order to recognized the equipment and display correct infor-
mation.
20
(USB port selection field) the USB port number where U10