10.1.2 Memory Clear Function
Initialize the FL654.
When FL654 used in AUTO / LOCK specification is changed in TOOL specification, please
switch specification after executing "memory clear" for deleting inside information. Even an
opposite usage is similar.
Moreover, in TOOL specification, please execute download again after executing "memory
clear" when it doesn't normally complete download.
The initializing procedure is as follows:
(1) Select the relevant I/O station in the system's station configuration of the V-Tool and
right click on it to display the menu. In this menu, select "System View."
(2) In the System View/Station Status screen, select "FL654" in the Main Module Type
column and click the Maintenance button. In the Maintenance Panel screen, click the
Memory Operation tab to display its panel. Then select "Memory Clear" in the
Command box and click the OK button to start memory initialization.