1.6.7 Second Stage Latching

This feature establishes how the HVAC Equipment will stage down. If the unit
possess multiple stages of heating or cooling, the ability of controlling the stage
down process can be benefi cial. With this feature disabled, once the set point is
met, the thermostat will stage down to the previous stage. After the stage delay, if
the set point is still satisfi ed, the thermostat will stage down once again. With this
feature enabled, once the set point has been satisfi ed, all stages will be turned off
and the thermostat will go into standby mode.
 Options: Enable and Disable
 Default: Disable
1.
Main Menu
2.
Advanced Settings
3.
Installer Access
4.
Enter Professional Access Code "1886"
5.
Enter Action code "ST"
6.
Latching
Figure 52
Bosch Connected Control BCC100 Thermostat (01.2022)

1.6.8 Stage Delay

After the thermostat has been continuously calling for a time equal to the selected
time period, the Stage Delay Timer automatically up stages the heating or cooling.
The timer will not upstage cooling if the indoor temperature is below the selected
temperature. Similarly, it will not upstage heating if the indoor temperature is above
the selected temperature. Neither upstaging for cooling or heating will occur if the
space temperature is within the Zero Energy Band.
 Options: 3 minutes to 90 minutes.
 Default: 10 min
1.
Main Menu
2.
Advanced Settings
3.
Installer Access
4.
Enter Professional Access Code "1886"
5.
Enter Action code "ST"
6.
Select Stage Delay
Use the Up and Down keys to select the Stage Delay.
Figure 53
Advanced Settings Guide
| 19