1.6.2 Fan On Delay in Cooling

This feature allows the ability to delay the fan motor from energizing for a specifi ed
amount of time while in the cooling mode.
 Options: 0 Seconds to 120 Seconds.
 Default: 0 Seconds
1.
Main Menu
2.
Advanced Settings
3.
Heating & Cooling
4.
Enter Professional Access code "1886"
5.
Fan Delay
6.
Select On
Use the Up and Down keys to select Fan Delay.
Figure 47
Bosch Connected Control BCC100 Thermostat (01.2022)

1.6.3 Minimum Run Time

This feature establishes the minimum allowable run time for the compressor. The
minimum run time prevents short run time and lengthens the life of the compressor.
The compressor will continue to run for the specifi ed number of minutes even if the
set point is reached.
Minimum run time is the number of seconds the thermostat will call for heating
or cooling to ensure a comfortable cycling rate. Setting the System to Off or the
opposite system call will override the timer and immediately terminate the heating
or cooling call.
The minimum run time (MRT) upper limit is tied to the Stage Delay Timer (SDT)
setting (600s or 10min by default). The upper limit for MRT may be set as high as
90 minutes, if the SDT is set accordingly.
 Options: 180 seconds to Stage Delay Timer Setting (600 seconds/10
minutes by default, but can be set up to 90 minutes)
 Default: 300 Seconds
1.
Main Menu
2.
Advanced Settings
3.
Heating & Cooling
4.
Enter Professional Access code "1886"
5.
Min. Run Time
Use the Up and Down keys to select the minimum run time.
Figure 48
Advanced Settings Guide