Advanced Settings Guide
1.5.10.7 Balance Point
This feature allows the user to set the outdoor temperature for which the dual fuel
system changes between Heat Pump heating and Furnace heating
Options: 5°F to 60°F
Default: 40°F
1.
Main Menu
2.
System Settings
3.
Unit Confi guration
4.
Heat Type (Select Dual Fuel)
5.
Heat Pump
6.
Select the Balance Point box
Use the Up and Down keys to select Balance Point Temperature
Figure 44
1.5.10.8 Changeover Delay
This feature allows the user to adjust the time delay implemented when switching
from one heating source to the other during dual fuel operation.
Options: 45 sec to 300 sec
Default: 45 sec
1.
Main Menu
2.
System Settings
3.
Unit Confi guration
4.
Heat Type (Select Dual Fuel)
5.
Heat Pump
6.
Select the Changeover Delay box
Figure 45
1 6 |
1.6 Advanced Settings
The Advanced Settings are for the specifi c settings about how the system operates.
Here is also where the installer/contractor can access settings not available to
the homeowner. The Advanced Settings are accessed by clicking on Menu, then
Advanced Settings.
1.6.1 Fan On Delay in Heating
This feature allows the ability to delay the fan motor from energizing for a specifi ed
amount of time while in the heating mode.
This option is skipped for A/C equipment.
Options: 0 Seconds to 120 Seconds.
Default: 0 Seconds
1.
Main Menu
2.
Advanced Settings
3.
Heating & Cooling
4.
Enter Professional Access code "1886"
5.
Fan Delay
6.
Select On
Use the Up and Down keys to select Fan Delay.
Figure 46
Bosch Connected Control BCC100 Thermostat (01.2022)