Humidifi Er Control; Dehumidifi Cation Control - Bosch BCC100 Settings Manual

Hide thumbs Also See for BCC100:
Table of Contents

Advertisement

Advanced Settings Guide
1.5.10.3 Humidifi er Control
This feature enables the use of a humidifi er. The setup technician must set
the humidity set point to establish the desired humidity level that should be
maintained. The humidifi er will only be activated during a heating call.
This option is skipped for A/C equipment.
 Options: Humidifier, Dehumidifier and None
 Default: Dehumidifer
1.
Main Menu
2.
System Settings
3.
Unit Confi guration
4.
Accessory
5.
Select Humidifi er
Figure 39
1 4 |
1.5.10.4 DeHumidifi cation Control
This feature allows the ability to enable cool-to-dehumidify functionality (if the
HVAC equipment includes this feature) or to disable the functionality and operate
hot gas reheat (if the HVAC equipment is equipped with this feature). When cool-to-
dehumidify functionality is enabled, the cooling equipment will remain on until the
humidity set point is met or the over cooling temperature has been reached. The
over cooling temperature is the permissible number of degrees below the set point
that the user will allow in an attempt to better dehumidify the space.
 Options: Enable and Disable
 Default: Disable
1.
Main Menu
2.
System Settings
3.
Unit Confi guration
4.
Accessory
5.
Dehumidifi er
6.
Setup
Figure 40
Figure 41
Bosch Connected Control BCC100 Thermostat (01.2022)