Operations Under Access Level 3; Deleting Test Logs - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Operation
8

Operations under access level 3

8.6 Operations under access level 3

8.6.1 Deleting test logs

86 | 151
This function is available with access level 3 password.
The 'Test log' function deletes all test logs on the panel. Before performing this
function, you can back up all the existing test logs to a PC. See 'Backing up test
reports to the PC [➙ 118]' for more information about test log backup.
1. Press
on the keypad. The 'Main menu' window is open.
Main menu
1 - System status
2 - Operation
3 - Event memory
5 - Lamp test
6 - Engineering
7 - Logout
2. Select 'Event memory' and press
Event memory
1 - Event log
2 - Test log
3 - Compensation Value
3. Select 'Test log' and press
Test log
1 - Delete log
4. Select 'Delete log' and press
Confirm delete?
Yes (OK) or No (C)
5. Press
to confirm. All test logs are deleted.
L3
. The 'Event memory' window is open.
L3
. The 'Test log' window is open.
L3
. A confirmation dialog window is open.