Installation
6
Spare parts

6.12.2 Door incl. PMI FHD3601-Z1

58 | 151
The door incl. PMI FHD3601-Z1 is already mounted in the fire control panel in the
factory and only has to be replaced in the event of a repair.
Fig. 25: Installation of door incl. PMI
Fig. 26: Details view of installation
1
Bolt
2
Bolt pin
3
Hinge
 The power supplies (mains and battery) are disconnected.
 Connector to mainboard is disconnected.
 The old door incl. PMI is removed. Refer to document A6V10450591, see
chapter 'Applicable documents [➙ 9]'.
1. From the right side insert the bolt pin on the door into the hinge (3) on the rear
panel, aligning the hole on the bolt pin (2) with the hole on the hinge (3).
2. Secure the door with two bolts (1).
3. Insert the connector to the mainboard into the PCB board on the door.
The panel recovers the previous status after the new door incl. PMI is installed.
A6V10421795_en--_k