11.3 Function test

Function
↑ Detector line
Outputs
Inputs
Alarm organization
Panel
A6V10421795_en--_k
The following schedule is recommended for the function test. However, local
regulations have higher priorities.
Activity
Activate all automatic detectors and all manual call points.
Activate a detector or manual call point per line
Check all detectors and manual call points for dirt and check that
usage is in accordance with regulations.
Activate a fault, short circuit and open line, and check that usage
is in accordance with regulations.
Check sounder controls and all acoustic and optical alarm
devices.
Activate fire outputs and check the application.
Activate ↑ RT alarm and check the RT transmission.
Activate each input and check the application.
Mode ↑ Manned.
Activate a detector and manual call point and check the timer T1
and T2 and the RT transmission.
Mode ↑ unmanned.
Activate a detector and check the RT transmission.
Check the DAR functionality for each input and output.
Check date and time.
Check the display, button and LEDs.
Check earth connections.
Activate mains and battery fault condition and verify the
application.
Maintenance
11
Function test
Interval
(years)
1
2
5
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X