Resetting Alarm Counter; Restoring Factory Settings - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

Engineering
9

Resetting alarm counter

9.6 Resetting alarm counter

9.7 Restoring factory settings

106 | 151
The 'Alarm counter reset' function is used to reset the alarm counter to '0'.
1. Press
on the keypad.
 The 'Main menu' window is open.
2. Select 'Engineering' and press
 The 'Engineering' window is open.
3. Select 'Alarm counter reset' and press
 A password entry window is open.
4. Enter the password (66666666) and press
 A confirmation dialog window is open.
5. Press
to confirm.
 The alarm counter is reset to '0'.
NOTICE
Restoring factory settings on the panel
The configuration of the panel is deleted!
Save the configuration data for the panel before restoring to factory settings.
The 'Factory reset' operation must be executed in one of the following situations:
Two loops are merged into one loop.
Current country or language selection is not desired.
The restoration process may take a few minutes, depending on the size of site.
1. Press
on the keypad.
 The 'Main menu' window is open.
2. Select 'Engineering' and press
 The 'Engineering' window is open.
3. Select 'Factory reset' and press
 A confirmation window is open.
4. Press
to confirm.
 A 'Factory set is ongoing...' message is displayed.
 The panel restarts.
5. Select country and language, and then decide whether auto configuration on
loops/stubs performs automatically during the startup process. See 'Starting up
the panel [➙ 110]'.
 The panel is reset to factory settings.
.
.
.
.
.