Ambient Conditions; Used Standards - Bosch Rexroth lndraControl VPB 40.1 Project Planning Manual

Control cabinet pc
Table of Contents

Advertisement

DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
4.4

Ambient Conditions

Max. surrounding air temperature
Max. temperature gradient
Relative humidity
Air pressure
Mechanical strength
Degree of pollution
4.5

Used Standards

NOTICE
When maximum output currents are specified, please observe that the currents
are the maximum possible currents for the respective output voltage. However,
it is not possible to produce the maximum current from all output voltages at
the same time, as the maximum total output power (= max. 110 W) must not
be exceeded.
In operation
+5 ℃ ... +45 °C
Temporal temperature changes up to 3 ℃
per minute
Climatic class 3K3 according to EN
60721,
non-condensing.
Up to 2000 m above MSL according to
DIN 60204
Max. vibration:
Frequency range:
10 to 150 Hz
Excursion: 0.075 mm for 10 ... 57 Hz
Acceleration: 1 g for 57 to 150 Hz
acc. to EN 60068-2-6
2
Fig.4-4:
Ambient conditions
The system components of the VPB 40.1 correspond to the following standards:
Standard
EN 60 204-1
EN 50 081-2
EN 50 082-2
EN 60 742
EN 60 950
EN 61 131
EN 61 131-2
EN 418
Bosch Rexroth AG
The control cabinet PC VPB 40.1 can be dam‐
aged if the power supply unit is switched off if
the total output power exceeds 110 W.
Storage / Transport
-20 ℃ to +60 ℃
Not defined
Climatic class 3K3 according to EN
60721,
non-condensing.
Max. shock:
15 g acc. to DIN IEC 68-2-27,
No breakdown of the function
2
Meaning
Electrical equipment of machines
Generic standards - emission standard (industrial envi‐
ronments)
Generic standards - noise immunity (industrial environ‐
ments)
Transformer for 24 V power supply unit, protective sepa‐
ration
Overvoltage category II
24 V outputs requirements
24 V current supply requirements
Safety of machinery, emergency stop devices
21/81
Technical Data