Pc Voltage Supply X10, X20 - Bosch Rexroth lndraControl VPB 40.1 Project Planning Manual

Control cabinet pc
Table of Contents

Advertisement

40/81
Bosch Rexroth AG
Connections
7.2.11

PC Voltage Supply X10, X20

X10 - DC 24 V voltage supply
This connection is used for device variants for DC 24 V. All internally required
voltages are generated with electrical isolation via a DC/DC converter. The
connection is designed as connector terminal MSTB 1.5, 4-pin. To this con‐
nector terminal, cables with a cross-section of maximum 1.5 mm
connected.
NOTICE
For terminal connectors use copper wire only. Tighten the screws of the screw
terminals with a torque of 5.5 lb in (0.6 Nm).
X10
_
+
1 2 3 4
Fig.7-19:
DC 24 V connection, X10, pin assignment
Parameter
Rated voltage U
N
Residual ripple at U
N
Emitted interference and surge immunity U
Current consumption for U
N
Input fuse
Reverse voltage protection
Fig.7-20:
DC 24 V connection, technical data
DANGER
The DC 24 V input voltage must comply with the requirements of the "Protective
separation"!
Plug and unplug the connector only if there is no voltage!
DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
Destruction of screw terminals, insufficient
contact and loss of UL/CSA certificiation if no
copper wire is used and/or wrong tightening
torque.
Pin
Assignment
1
24 V
2
24 V
3
0 V
4
0 V
Value
DC 24 V ; +20 %, -15 %
See
fig. 7-22 "Limit values of the DC 24 V
voltage" on page 41
= 35 V (for t < 100 ms)
max
4.8 A max.
M6, 3A (5x20) medium time-lag
Via decoupling diode
The line-side fuse is activated when polarity
reversal occurs.
Danger without protective separation!
2
can be

Advertisement

Table of Contents
loading