3.1.4 Unpacking and Checking

Figure 3-6
Figure 3-6 Transportation safety requirements
Issue 18 (2021-07-16)
Number
Rated
of
Voltage
Phases
-
± 240 V DC
1
220 V
AC/230 V
AC/240 V
AC
3
380 V
AC/400 V
AC/415 V
3
AC
-
± 240 V DC
3
380 V
AC/400 V
AC/415 V
AC
NO TE
● If customers purchase input and output power cables by themselves, use the cables that
comply with standards proposed by Underwriters Laboratories (UL) or International
Electrotechnical Commission (IEC).
● Two-mains-input scenarios are not supported on the UPS2000-G-15 kVA/20 kVA (single-
phase input single-phase output).
shows the transportation safety requirements.
Copyright © Huawei Technologies Co., Ltd.
Externa
Cable
l Circuit
Cross-
Breaker
Sectional
Area
63 A
2
16 mm
125 A
2
25 mm
(feature
D)
63 A
2
10 mm
(feature
D)
63 A
2
16 mm
63 A
2
10 mm
(feature
D)
3 Installation
Terminal
Torque
Type
for
Tighteni
ng Bolts
4.8 N·m
2
16 mm
M6 90°
OT
terminal
4.8 N·m
2
25 mm
M6 OT
terminal
2.8 N m
2
10 mm
M6 OT
terminal
2
4.8 N·m
16 mm
M6 90°
OT
terminal
2.8 N m
2
10 mm
M6 OT
terminal
34