G Battery Shallow Discharge Test - Huawei UPS2000-G-6KRTS User Manual

Hide thumbs Also See for UPS2000-G-6KRTS:
Table of Contents

Advertisement

UPS2000-G- (6 kVA-20 kVA)
User Manual
G
Context
A shallow discharge test method that tests the battery loop reliability and short-
time backup capacity after batteries are charged for a long time (60 days by
default, 30 days to 90 days configurable).
Before a shallow discharge test, ensure that the load rate is 0%–100% and the
load fluctuation does not exceed 10%.
Procedure
Step 1 Check the battery status for test start conditions.
1.
2.
Issue 18 (2021-07-16)
Battery Shallow Discharge Test
NO TICE
On the Main Menu screen, choose Status and click
screen, locate Battery Status.
Figure G-1 Battery Status menu
NO TE
– Status: The battery status is N/A (battery not connected or reversely connected),
Equalized charging, Float charging, Hibernating, or Discharging.
– Capacity: indicates the remaining battery capacity.
– Backup time: indicates the estimated battery discharge time when batteries are
being charged or discharged.
Batteries in Hibernating state cannot start a shallow discharge test. Choose
Control and Maintain Batteries, and then click Manual Float Charging to
switch the batteries to the float charging state. If the batteries hibernate due
Copyright © Huawei Technologies Co., Ltd.

G Battery Shallow Discharge Test

. On the Status
177

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents