UPS2000-G1-(6 kVA–10 kVA) V100R001 User Manual Issue Date 2013-07-17 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
This document describes the UPS2000 in terms of its features, performance, appearance, structure, working principles, installation, operation and maintenance (O&M). NOTE Unless otherwise specified, the UPS2000 described in this document refers to the UPS2000-G1-6 kVA and UPS2000-G1-10 kVA. Intended Audience This document is intended for: ...
(for example, motors, air conditioners, and printers). Before using a UPS to support the following equipment, consult Huawei for special requirements on the application, configuration, management, and maintenance of the UPS: Life support equipment −...
UPS2000-G1-(6 kVA–10 kVA) User Manual 2 UPS Overview Figure 2-4 UPS2000-G1-6 kVA rear panel (1) RS232 port (2) EPO port (3) Parallel control port (4) Fan (5) Input breaker (6) Fuse (7) Surge protection and (8) Output grounding port socket...
User Manual 3 Installation NOTE The Schneider contactors LC1-D3210M5C and LC1-D5011M5C are recommended for the UPS2000-G1-6 kVA and UPS2000-G1-10 kVA respectively. The contactor specifications are as follows: Rated voltage: 220 V AC, 230 V AC, or 240 V AC ...
Page 29
UPS2000-G1-(6 kVA–10 kVA) User Manual 4 Operation Instructions Figure 2-4 and Figure 2-5 show the positions of the input breakers on the UPS2000-G1-6 kVA and UPS2000-G1-10 kVA respectively. Step 2 If the LCD lights up and displays correct information, press the button for 1 second.
After switching on the output breaker of the parallel system, check the output cross current of each UPS. If any output cross current exceeds 3 A, contact Huawei technical support for repair. Otherwise, the inverter will be damaged. ----End 4.3.2 Shutting Down Parallel-Running UPSs...