Technical data
Contents of this chapter
The chapter contains the technical specifications of the drive, for example ratings, sizes
and technical requirements as well as provisions for fulfilling the requirements for CE,
UL and other approval marks.
Ratings
■
IEC ratings
Drive
Nom-
Max.
Type
inal
cur-
ACS560
In
rent
I 1N
I max
A
A
3 phases U N = 400 V (380...415 V)
02A6-4
2.6
3.2
03A3-4
3.3
4.7
04A0-4
4
5.9
05A6-4
5.6
7.2
07A2-4
7.2
10.1
09A4-4
9.4
13
12A6-4
12.6
16.9
017A-4
17
22.7
025A-4
25
30.6
033A-4
33
44.3
039A-4
39
56.9
046A-4
46
67.9
062A-4
62
76
073A-4
73
104
088A-4
88
122
106A-4
106
148
145A-4
145
178
169A-4
169
247
Nominal use
Light overload
I N
P N
I Ld
(Con-
tinu-
ous)
A
kW
Hp
A
2.6
0.75
1
2.5
3.3
1.1
1.5
3.1
4
1.5
2
3.8
5.6
2.2
3
5.3
7.2
3
4
6.8
9.4
4
5
8.9
12.6
5.5
7.5
12
17
7.5
10
16.2
25
11
15
23.8
33
15
20
30.4
39
18.5
25
36.1
46
22
30
42.8
62
30
40
58
73
37
50
68.4
88
45
60
82.7
106
55
75
99.8
145
75
100
138
169
90
120
161
Output ratings
Heavy-duty use
use
P Ld
I Hd
(Con-
tinu-
ous)
kW
Hp
A
0.75
1
1.8
1.1
1.5
2.6
1.5
2
3.3
3
3
4
2.2
4
5.6
4
5
7.2
5.5
7.5
9.4
7.5
10
12.6
11
15
17
15
20
24.6
18.5
25
31.6
22
30
37.7
30
40
44.6
37
50
61
45
60
72
55
75
87
75
100
105
90
120
145
Technical data 117
Frame
size
P Hd
kW
Hp
0.55
0.75
R0
0.75
1
R0
1.1
1.5
R0
1.5
2
R0
2.2
3
R0
3
4
R0
4
5
R1
5.5
7.5
R2
7.5
10
R2
11
15
R3
15
20
R3
18.5
25
R3
22
30
R4
30
40
R4
37
50
R5
45
60
R5
55
75
R6
75
100
R7
EN
HI