Huawei ECC500 User Manual page 60

Data center
Hide thumbs Also See for ECC500:
Table of Contents

Advertisement

ECC500 (Data Center)
User Manual
Category
Surge protection
Safety
Reliability
Mechanical
parameters
Issue 06 (2020-01-06)
Item
Conducted susceptibility
Radiated susceptibility
Digital parameter
Analog parameter
Communication signal
DC port
-
MTBF
Annual return repair rate
Life cycle
Water resistance and dustproof
level
Dimensions (H x W x D)
Weight
Copyright © Huawei Technologies Co., Ltd.
A Technical Specifications
Description
before the test
For the conductor in the signal
port: contact discharge: ± 2 kV
(criterion R); the conductor
has been powered on before
the test
3 V, 0.15-80 MHz (criterion A)
10 V/m, 80 MHz to 2 GHz
(criterion A)
Differential mode: 3 kA; common
mode: 5 kA
Differential mode: 3 kA; common
mode: 5 kA
Differential mode: 3 kA; common
mode: 5 kA
—48 V; differential mode: 2 kA;
common mode: 4 kA
ECC500 components and the PCB
comply with IEC60950-1,
EN60950-1, and GB4943.
≥ 100,000 hours
< 1%
> 10 years (at least three years
promised in actual application)
Cabinet: IP45 or IP55
≤ 44.5 mm x 220 mm x 440 mm
≤ 5 kg