Assigning Profinet Device Names - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
4.5 Establishing an online connection to the drive
6. Click on "Assign IP address"
7. Update the display at "Online access". The IP address is now displayed.
The MAC address is read out automatically.
Result
The IP address has been assigned to the drive.
4.5.4.4

Assigning PROFINET device names

Assigning a name
You must assign a device name to the drive so that you can operate the drive in a
PROFINET subnet.
This name must comply with DNS name conventions. Review the TIA Portal online help for
more detailed information on this topic.
● When delivered, the drive does not have a device name.
● If the drive already has a name, perform "Restore factory settings". The name is deleted.
Precondition
An online connection has been established to the device.
"Online access" procedure
To assign a name, proceed as follows:
1. Select the network interface of your computer.
2. Double click on "Update accessible devices".
Accessible devices are indicated below the interface.
3. Double-click "Online & Diagnostics" under this node in the project navigator.
4. Click the "Functions" entry in the secondary navigation of the working area.
5. Click the "Assign PROFINET device name" entry in the secondary navigation.
Figure 4-44
136
Assigning names
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0