Commissioning
4.5 Establishing an online connection to the drive
Procedure via "Online access"
To search for a drive, proceed as follows:
1. Open the "Online access" entry in the project navigator.
2. Select the network interface of your computer.
3. Double click on "Update accessible devices".
The drive is displayed in the project navigator.
Figure 4-41
If the communication parameters are at their factory settings (IP address 0.0.0.0 and no
device name), then the default device names of the TIA Portal ("Node" in this case) and
the MAC address are displayed.
If you want to go online on the device, you must assign an IP address and a device
name.
4. Select the drive, and if necessary assign an IP address and device name, see also the
Chapters "Assigning an IP address (Page 135)" and "Assigning PROFINET device
names (Page 136)".
Figure 4-42
The drive is displayed with the device name (in this case, drive_1) and the IP address.
If you cannot assign an IP address and device name, you may have to check the IP
address of your PG/PC. This must also lie in the same address range as the address of
the drive, see also Chapter "Setting the PG/ PC interface (Page 138)".
Result
You have found the device in the PROFINET subnet and assigned an IP address and a
device name.
Now establish an online connection.
134
PROFINET online access
PROFINET with IP address
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0