Special features of POM 4220 Highend:
Error code
5104
5105
5107
Error code
5104
5105
5107
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
Connection type "2-pin switching"
Meaning
Channels 1 to 4
Both Triacs are fused
Channels 5 to 8
Exactly one Triac has fused
–
–
Channels 1 to 4
External fault
•
Fuse F1 ... F8 is defective
•
Triac 1 ... 8 has high re-
•
sistance
Channels 5 to 8
–
Connection type "economy circuit"
Meaning
Channels 1 to 4
Triac 1 ... 4 is fused
Channels 5 to 8
Triac 5 ... 8 is fused
Channels 1 to 4
Fuse F1 ... F4 tripped
•
Triac 1 ... 4 has high re-
•
sistance
Channels 5 to 8
Fuse F5 ... F8 tripped
•
Triac 5 ... 8 has high re-
•
sistance
Channels 1 to 4
External fault
Channels 5 to 8
External fault
10.3 Transfer of diagnostic alarms to the controller
Description
The error message is generated
via channels 1 to 4.
The error message is generated
via channels 5 to 8.
–
The error message is generated
via channels 1 to 4.
No distinction is possible between
an external fault and a fuse fault.
Therefore, the error code 5107
includes the following errors:
Channel fault "Triac has high
•
resistance" / "outgoing fuse
blown"
Channel fault "external fault".
•
See also section Fault reporting
through diagnostics data
(Page 180).
–
Description
From the user's point of view, only
channels 1 through 4 are used.
However, error messages 5104
and 5105 are generated specifical-
ly via channels 1 through 8.
–
–
Communications
177