Example: (p9909 = 1) replacing a defective component with an identical article number
Requirement:
● The replaced component has an identical article number
● The serial number of the new replacement component must not be contained in the
stored target topology of the Control Unit.
● Topology comparison component replacement active p9909 = 1.
Sequence:
During startup of the Control Unit, the serial number of the new component is automatically
transferred to the target topology and saved.
Example: (p9909 = 0) replacing a defective component with an identical article number
Requirement:
● The replaced component has an identical article number
● Topology comparison component replacement inactive p9909 = 0.
Table 13- 8
Action
The component has been successfully replaced.
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Example: Replacing a Motor Module
Switch off the power supply
Replace the defective com-
ponent and connect the new
one
Switch on the power supply
Set p9905 to "1"
Basic information about the drive system
Reaction
Alarm A01425
Alarm disappears
The serial number is copied
to the target topology
13.9 Component replacement
Remark
The serial number is stored in
the RAM of the Control Unit and
has to be copied to the non-
volatile memory with p0977 = 1
and p0971 = 1. As an alterna-
tive, STARTER can be used to
backup data with a RAM to
ROM operation.