Intefaces at the Y-Repeater

7.2.1

View on the Connector Panels

Fig.7-11:
PROFIBUS DP interface XDPSLAVE
The bus cable is specified as cable type A according to EN 50170, part 8-2. It
must comply with the following cable parameters:
Surge impedance at a frequency within a range
from 3 to 20 MHz
Operating capacity
Loop resistance
Outer diameter
Core cross-section
Fig.7-12:
Parameters for PROFIBUS DP cable
The above mentioned cable parameters of a standard cable of cable type A
result in the following length extensions of a bus segment for the particular
transmission rates:
19,2
45,45
93,75
1200
1200
1200
Fig.7-13:
Maximum segment length with regard to the transmission rate
The corresponding PROFIBUS Slave address is set via the rotary
switch, see
corresponding GSD file is "Rx010135.gsd".
The connections are located at the two shorter sides of the Y-Repeater:
Fig.7-14:
Interface to control cabinet PC (IPC)
DOK-SUPPL*-VDP16/40/60-PR03-EN-P
Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display
135 to 156 ohms
≤ 30 pF/m
≤ 110 Ohm/km
> 0.64 mm
> 0.34 mm
187,5
500
1500
1000
400
200
chapter 7.1.4 "S3/S4 Rotary Switch" on page
2
3000
6000
12000
100
100
100
46. The