Section 9
Control functions
Table 1377:
ASNSCSYN Non group settings (Basic)
Parameter
Operation
Synchrocheck mode
Dead bus voltage
Live bus voltage
Max energizing V
Auto Syn mode
Table 1378:
ASNSCSYN Non group settings (Advanced)
Parameter
Phase shift
Minimum Syn time
Maximum Syn time
Energizing time
Closing time of CB
9.7.9
1446
Values (Range)
Unit
1=on
5=off
1=Off
2=Synchronous
3=Asynchronous
4=Command
0.1...0.8
xUn
0.2...1.0
xUn
0.50...1.30
xUn
-1=Semi-automatic
synchronising
mode
1=Automatic
synchronising
mode
3=Manual mode
Values (Range)
Unit
-180...180
deg
0...60000
ms
100...6000000
ms
100...60000
ms
40...250
ms

Monitored data

Table 1379:
ASNSCSYN Monitored data
Name
ENERG_STATE
U_DIFF_MEAS
PH_DIFF_MEAS
U_BUSA_MEAS
U_BUSB_MEAS
Table continues on next page
Step
Default
1=on
3=Asynchronous
0.1
0.2
0.1
0.5
0.01
1.05
3=Manual mode
Step
Default
1
0
10
0
10
60000
10
100
1
60
Type
Values (Range)
Enum
0=Unknown
1=Both Live
2=Live Bus B,
Dead Bus A
3=Dead Bus B,
Live Bus A
4=Both Dead
FLOAT32
-3.00...3.00
FLOAT32
-180.00...180.00
FLOAT32
0.00...5.00
FLOAT32
0.00...5.00
1MRS759142 C
Description
Operation Off / On
Synchrocheck operation mode
Voltage low limit for energizing check
Voltage high limit for energizing check
Maximum voltage above which no
paralleling takes place
Autosynchronization operation mode
Description
Phase difference correction between bus
A and bus B voltages
Minimum time to accept synchronizing
Maximum time to accept synchronizing
Time delay for energizing check
Closing time of the breaker
Unit
Description
Energization state of bus
A and bus B
xUn
Calculated voltage
amplitude difference
deg
Calculated voltage phase
angle difference
xUn
Calculated bus A voltage
amplitude
xUn
Calculated bus B voltage
amplitude
Technical Manual
REX640