1MRS759142 C
9.8.5
REX640
Technical Manual
G1
Bus1
CB2
Bus3
CB1
GUID-E39F2BFC-3124-4C9F-877F-6C45B478E80E V1 EN
Figure 784:
Example of an internally connected network
Externally connected
A network where both Bus3 and Bus4 are connected to the grid across CB1 is
considered an externally connected network.
Bus1
TX1
Bus3
GUID-F986E960-C6CF-4F8F-B5B0-03196BABBDA9 V1 EN
Figure 785:
Example of an externally connected network
The number of sources active in the voltage and frequency matching is shared to
sources via the corresponding output signal ASC_SRC1_DAT...ASC_SRC8_DAT.
The binary input BLOCK can be used to block the function. The activation of the
BLOCK input deactivates all binary outputs and resets the internal timers.

Application

A circuit breaker is used to connect two different power networks. It is essential to
ensure that these power networks are synchronized before closing the CB, otherwise
it may lead to disturbances in the power system, causing stress and damage to the
connected equipment.
The synchronization of any bus coupler or tie feeder is not feasible if the voltage and
frequency differences across the circuit breaker are not within the allowed limits. In
this case, the sources which are part of the power network connected across this bus
G2
Bus2
Bus4
Bus2
CB2
Bus4
CB1
Section 9
Control functions
TX2
1461