Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
9.11.11
REX640
Technical Manual

Monitored data

Table 1436:
PASANCR Monitored data
Name
Type
COIL_MV_SPD
FLOAT32
I_AFTER_RUN
FLOAT32
I_MCH_PLAY
FLOAT32
I_COIL_TOT
FLOAT32
OHM_COIL
FLOAT32
I_DAMPING
FLOAT32
I_C_NETWORK
FLOAT32
I_EF
FLOAT32
I_RESONANCE
FLOAT32
DAMPING
FLOAT32
I_DETUNING
FLOAT32
DETUNING_REL
FLOAT32
UREF_AMPL
FLOAT32
UREF_ANG
FLOAT32
URESO_AMPL
FLOAT32
URESO_REL
FLOAT32
URESO_AMPL_R
FLOAT32
URESO_REL_R
FLOAT32
Table continues on next page
Values (Range)
Unit
0.00...100.00
A/s
0.00...100.00
A
0.00...100.00
A
0.00...10000.00
A
0...3000
ohm
0.00...10000.00
A
0.00...10000.00
A
0.00...10000.00
A
0.00...10000.00
A
0.00...100.00
-100.00...100.00
A
-100.00...100.00
%
0.00...100.00
xUn
-180.00...180.00
deg
0...100000
V
0.0...100.0
%
0...100000
V
0.0...100.0
%
Section 9
Control functions
Description
Coil movement speed
detected during
calibration
Coil after-running current
Mechanical play of the
coil
Total inductive current of
adjustable and fixed arc
suppression coil
Coil position indicating
potentiometer value
Wattmetric part of the
residual current at the
fault location
Uncompensated earth-
fault current of the
network
Earth-fault current at
present operate point
Current at the resonance
point
Damping of the network
Petersen coil detuning in
amperes
Petersen coil detuning in
percents
Reference voltage
amplitude
Reference voltage angle
Resonance point voltage
amplitude without the
parallel resistor
Resonance point voltage
in percent without the
parallel resistor
Resonance point voltage
amplitude with the
parallel resistor
connected
Resonance point voltage
in percent with the
parallel resistor
connected
1595

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents