M80 To M87, Dc Busbar System; General Information - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options

8.37 M80 to M87, DC busbar system

8.37
M80 to M87, DC busbar system
8.37.1

General information

Availability of option
This option is available for the following S120 Cabinet Modules:
● Line Connection Module
● Basic Line Module
● Smart Line Module
● Active Line Module
● Motor Module in chassis format
● Booksize Base Cabinet
● Central Braking Module
● Auxiliary Power Supply Module
Description
The DC busbar connects the DC voltage across the drive line-up. The DC busbar comprises
an upper busbar (DC P) and a lower busbar (DC N).
The following optional DC busbars are available:
● Option M80 = busbar system 1 x 60 x 10
● Option M81 = busbar system 1 x 80 x 10
● Option M82 = busbar system 1 x 100 x 10
● Option M83 = busbar system 2 x 60 x 10
● Option M84 = busbar system 2 x 80 x 10
● Option M85 = busbar system 2 x 100 x 10
● Option M86 = busbar system 3 x 80 x 10
● Option M87 = busbar system 3 x 100 x 10
Note
The required current intensity of the DC busbar depends on the individual plant
configuration. For this reason, a fixed DC busbar thickness is not assigned to the
individual Cabinet Modules. The required thickness must be configured for each
individual case and specified as option M80 to M87 (mandatory option).
For transport units, integrated busbars are installed at the factory. Connection jumpers
are not required inside a transport unit.
For option M26 (side panel on the right), connection jumpers are not required, nor are
they permitted.