Options
8.15 L10, dv/dt filter plus Voltage Peak Limiter
Table 8- 20
Table 8- 21
Commissioning
During commissioning, the dv/dt filter must be logged on using STARTER or via the AOP30
operator panel (p0230 = 2).
Note
Parameter p0230 is reset when the factory setting is established. The parameter has to be
reset when recommissioning.
370
Maximum permissible motor cable lengths for the DC link voltage 510 - 720 V DC
1 reactor
Shielded cable max. 300 m or
unshielded cable max. 450 m
6SL3720-1TE32-1AA0
6SL3720-1TE32-6AA0
6SL3720-1TE33-1AA0
6SL3720-1TE33-8AA0
6SL3720-1TE35-0AA0
6SL3720-1TE36-1AA0
6SL3720-1TE37-5AA0
6SL3720-1TE38-4AA0
Maximum permissible motor cable lengths for the DC link voltage 675 - 1035 V DC
1 reactor
Shielded cable max. 300 m or
unshielded cable max. 450 m
6SL3720-1TG28-5AA0
6SL3720-1TG31-0AA0
6SL3720-1TG31-2AA0
6SL3720-1TG31-5AA0
6SL3720-1TG31-8AA0
6SL3720-1TG32-2AA0
6SL3720-1TG32-6AA0
6SL3720-1TG33-3AA0
6SL3720-1TG34-1AA0
6SL3720-1TG34-7AA0
6SL3720-1TG35-8AA0
2 reactors
Shielded cable max. 150 m or
unshielded cable max. 225 m
6SL3720-1TE41-0AA0
6SL3720-1TE41-2AA0
6SL3720-1TE41-4AA0
-
-
-
-
-
2 reactors
Shielded cable max. 150 m or
unshielded cable max. 225 m
6SL3720-1TG37-4AA0
6SL3720-1TG38-1AA0
6SL3720-1TG38-8AA0
6SL3720-1TG41-0AA0
6SL3720-1TG41-3AA0
-
-
-
-
-
-
S120 Cabinet Modules Equipment Manual