Safety information
1.3 Safety information
CAUTION
As part of routine tests, SINAMICS S120 Cabinet Modules undergo a voltage test in
accordance with EN 61800-5-1. Prior to performing the voltage test for electrical equipment
of industrial machines in accordance with EN 60204-1, Section 19.4, all connections of the
Cabinet Modules must be disconnected/removed to prevent the units from being damaged.
Motors must be connected according to the circuit diagrams provided.
Note
When operated in dry operating areas, SINAMICS S120 Cabinet Modules with three-phase
induction motors conform to Low Voltage Directive 2006/95/EC.
SINAMICS S120 Cabinet Modules with three-phase induction motors conform to EMC
Directive 2004/108/EC in the configurations specified in the associated EC Declaration of
Conformity, provided that the configuration guidelines and actions are consistently applied.
CAUTION
Operating the equipment in the immediate vicinity (< 1.5 m) of mobile telephones with a
transmitter power of > 1 W may lead to incorrect operation.
18
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A