Siemens SINAMICS S120 Equipment Manual page 362

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options
8.13 K90/K91, Control Unit with CompactFlash card with/without performance enhancement
Note
An open input is interpreted as "low".
The "fast inputs" can be used in conjunction with a measuring system for position sensing.
When externally generated 24 V DC signals are connected to a digital input, the ground
reference of the external signal must also be connected.
-X5: Digital inputs/outputs
Table 8- 17
Terminal block -X55 -X5
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
DI: digital input, DI/DO: bidirectional digital input/output, M: electronics ground, M2: ground reference,
Temp: motor temperature sensor,
max. connectable cross section: 2.5 mm²
362
Designation
DI 4
DI5
DI 6
DI 7
M2
M
DI/DO 12
DI/DO 13
M
DI/DO 14
DI/DO 15
M
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
Technical specifications
Voltage: -3 V to 30 V
Typical current consumption: 10 mA at 24 V DC
Electrical isolation: reference potential is M2 terminal
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to 5 V
Signal propagation times:
L → H: approx. 50 μs
H → L: approx. 100 μs
As input:
Voltage: -3 V to 30 V
Typical current consumption: 10 mA at 24 V DC
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to 5 V
Terminal numbers 8, 10, and 11 are "fast inputs"
Signal propagation times for inputs/"fast inputs":
L → H: approx. 50 μs/5 μs
H → L: approx. 100 μs/50 μs
As output:
Voltage: 24 V DC
Max. load current per output: 20 mA (sustained-short-circuit-proof)
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A