Panasonic AFPE224300 User Manual page 83

Fp-e series panel mounted controller
Hide thumbs Also See for AFPE224300:
Table of Contents

Advertisement

9.1.2 Performance specifications
Item
Programming method/
Control method
Control unit
Number of
controllable
Front switch
I/O points
input
Program
Built-in
memory
memory
Program capacity
Number of
Basic
instruction
High-level
Operation speed
I/O update and Base time
Internal relay (R)
Special internal
relay (R)
Timer/Counter
(T/C)
Data register (DT)
Special data
register (DT)
Index registers
(IX. IY)
Differential points
Master control relay points
(MCR)
Number of labels (JP and
LOOP)
Number of step ladders
Number of subroutines
Number of interrupt programs
Self-diagnostic function
Clock/calendar function
Battery life
Pulse catch input
Interrupt input
Note 5)
COM. port
Periodical interrupt
Constant scan
Password
Note 1) High-level instructions are available for Ver1.2 or higher.
Note 2) The time takes longer every 250 ms.
Note 3) The proportion of timer points to counter points can be changed using a system register.
Note 4) Precision of calendar timer:
- At 0 ºC/32 ºF, less than 200 seconds error per month
- At 25 ºC/77 ºF, less than 70 seconds error per month
- At 55 ºC/131 ºF, less than 240 seconds error per month
Note 5) When using the COM. port to communication with other devices, retransmission is recom-
mended as it may be affected by excessive noise depending on the environments installed. The
driver IC for the RS232C port conforms to EIA/TIA-232E and CCITT V. 28 standards.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
AFPE224300
(Standard
Model
type)
RS232C
Relay symbol/Cyclic operation
14 points
[Input: 8, Output: 6 (Tr. NPN: 5/Ry 1)]
8 points For mode switching
For screen switching
For data setting or external input
Built-in EEP-ROM
2,720 steps
83
Note1)
168
0.9μs/step (Basic instruction)
2 ms
1,008 points (R0 to R62F)
64 points (R9000 to R903F)
144 points (Initial setting: 100 timer points, T0 toT99/44 counter points, C100 to
Note 3 )
C143
Timer range (1 ms, 10ms, 100ms, 1 s): selected by instruction
1,660 words (DT0 to DT1659)
112 words (DT9000 to DT9111)
2 points
Unlimited number of points
32 points
64 labels
128 stages
16 subroutines
7 programs (external: 6, internal 1)
Watchdog timer, program syntax check, etc.
Note 4)
Not available
No battery
6 points in total (X0 and X1: 50 µs, X2 to X5: 100 µs)
RS232C
0.5 ms to 30 s
Available
Available
AFPE224302
AFPE224305
(Standard
(Calendar
type)
timer
RS485
type)
RS232C
Available (year, month, day,
hour, minute, second and day
of week) However, this can
only be used when a battery
has been installed.
220 days or more (actual
usage value: approx. 870
days (25 ºC) (Periodic re-
placement interval: 1 year)
(Value applies when no pow-
er is supplied at all.)
RS485
RS232C
AFPE214325
AFPE224322
(Thermo-
(Thermo-
couple input
couple input
type)
type)
RS232C
RS485
12 points
[Input: 6, Output: 6]
1 point
1 point
6 points
Typical 2 to 3 ms Max. 15 ms
Note2)
Not available
No battery
RS232C
RS485
9-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afpe224305Afpe224322Afpe224302Afpe214325