Panasonic AFPE224300 User Manual page 186

Fp-e series panel mounted controller
Hide thumbs Also See for AFPE224300:
Table of Contents

Advertisement

Num-
Name
ber
High speed counter/Pulse output instruction for FPΣ/FP-X
F0
High-speed
counter and
Pulse output
controls
F1
Change and
read of the
elapsed value
of high-speed
counter and
Pulse output
F166
Target value
much on
(with channel
specification)
F167
Target value
much off
(with channel
specification)
F171
Pulse output
(with channel
specification)
(Trapezoidal
control and
home return)
F172
Pulse output
(with channel
specification)
(JOG
operation)
F173
PWM output
(with channel
specification)
F174
Pulse output
(with channel
specification)
(Selectable
data table
control
operation )
F175
Pulse output
(Linear
interpolation)
F176
Pulse output
(Circular
interpolation)
11-88
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Boolean
Operand
MV
S, DT90052
DMV
FPΣ:
S, DT90044
FP-X:
S, DT90300
FPΣ:
DT90044, D
FP-X:
DT90300, D
HC1S
n, S, D
HC1R
n, S, D
SPDH
S, n
PLSH
S, n
PWMH
S, n
SP0H
S, n
SPSH
S, n
SPCH
S, n
Description
Performs high-speed counter and Pulse output
controls according to the control code specified by
"S". The control code is stored in DT90052.
Transfers (S+1, S) to high-speed counter and
Pulse output elapsed value area (DT90045,
DT90044).
Transfers value in high-speed counter and Pulse
output elapsed value area (DT90045, DT90044) to
(D+1, D).
Turns output Yn on when the elapsed value of the
built-in high-speed counter reaches the target value
of (S+1, S).
Turns output Yn off when the elapsed value of the
built-in high-speed counter reaches the target value
of (S+1, S).
Positioning pulses are output from the specified
channel, in accordance with the contents of the
data table that starts with S.
Pulse strings are output from the specified output,
in accordance with the contents of the data table
that starts with S.
PWM output is output from the specified output, in
accordance with the contents of the data table that
starts with S.
Outputs the pulses from the specified channel
according to the data table specified by S.
Pulses are output from channel, in accordance with
the designated data table, so that the path to the
target position forms a straight line.
Pulses are output from channel, in accordance with
the designated data table, so that the path to the
target position forms an arc.
Steps
5
7
7
11
11
5
5
5
5
5
5

Hide quick links: