Input And Output Specifications; Input Specifications - Panasonic AFPE224300 User Manual

Fp-e series panel mounted controller
Hide thumbs Also See for AFPE224300:
Table of Contents

Advertisement

2.3 Input and Output Specifications

2.3.1 Input specifications

- DC input specifications (X0 toX7)
Number of input
Insulation method
Rated input voltage
Operating voltage range
Rated input current
Input points per common
ON voltage/ON current
OFF voltage/OFF current
Input impedance
Response time
Operation indicator
Note) X0 through X5 are inputs for the high-speed counter and have a fast response time. If used as
normal inputs, you are recommend to insert a timer in the ladder program as chattering and
noise may be interpreted as an input signal.
Also, the above specifications apply when the rated input voltage is 24V DC and the temperature
is 25 ºC.
Internal circuit diagram
R
1
X0 and X1
5.1 kΩ
X2 to X5
5.6 kΩ
X6 and X7
5.6 kΩ
2-6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Item
OFF to ON
ON to OFF
R
2
3 kΩ
2 kΩ
1 kΩ
Description
8 points
6 points (thermocouple input type)
Optical coupler
24 V DC
21.6 to 26.4 V DC
Approx. 4.3 mA
8 points/common,
6 points/common (thermocouple input type)
(Either the positive or negative of the input
power supply can be connected to
common terminal.)
19.2 V or less / 4 mA or less
2.4 V or more / 1 mA or more
Approx. 5.1 kΩ (X0, X1)
Approx. 5.6 kΩ (X2 to X7)
Note)
50 µs or less (X0, X1)
100 µs or less (X2 to X5)
2 ms or less (X6, X7)
Note)
50 µs or less (X0, X1)
100 µs or less (X2 to X5)
2 ms or less (X6, X7)
LCD display (I/O monitor mode)
Note)
Note)

Hide quick links: