A.4 Technology alarms
Technology alarm 204
Alarm reaction: Remove enable
Restart: Not required
Alarm text
Commissioning error
Sign-of-life failure between controller and TIA Portal.
A.4.4

Technology alarms 304-342

Technology alarm 304
Alarm reaction: Stop with emergency stop ramp
Restart: Not required
Alarm text
Limit value for velocity is zero.
Technology alarm 305
Alarm reaction: Stop with emergency stop ramp
Restart: Not required
Alarm text
Limit value for acceleration/deceleration is zero.
Acceleration
Deceleration
Technology alarm 306
Alarm reaction: Stop with emergency stop ramp
Restart: Not required
Alarm text
Limit value for jerk is zero.
376
Solution
Check the connection properties.
Solution
Enter a non-zero value for the maximum speed
(DynamicLimits.MaxVelocity) in the dynamic limits.
Solution
Enter a non-zero value for the maximum acceleration
(DynamicLimits.MaxAcceleration) in the dynamic limits.
Enter a non-zero value for the maximum deceleration
(DynamicLimits.MaxDeceleration) in the dynamic limits.
Solution
Enter a non-zero value for the maximum jerk
(DynamicLimits.MaxJerk) in the dynamic limits.