inst_h3.fm
Installing HiPath 3000
Installing HiPath 3750, HiPath 3700
Structure of the Patch Panel S30807-K6143-X
All incoming cables must be attached to the patch panel using cable ties.
>
MW8 jack assignment:
4 = a-wire
5 = b-wire
8
1
Necessary height units for 19-inch cabinet assembly: 1
(one height unit corresponds to approx. 1.7''=43 mm)
Figure 4-80
Patch Panel S30807-K6143-X
Information on MW8 jack assignment on the front of the patch panel is provided in the board
descriptions (in the "Cable and Connector Assignment" table) in Chapter 3.
Surge protector
To divert surges caused by lightning, insert surge protectors on
lines that leave the system buildings (outside stations)
lines > 500 m long.
Connect the polarized surge protectors to slots F1 – F8 provided on the patch panel
(seeFigure 4-81).
4-144
SIVAPAC edge connector: port for
CABLU connection to the backplane
Eight surge protector plug loca-
tions
Front panel with 3 x 16 MW8 jacks
P31003-H3550-S403-4-7620, 02/05
HiPath 3000 V5.0, HiPath 5000 V5.0, Service Manual