Other Information

Object setting when there is communication error
If any communication error occurs between the air conditioner devices, the property
will be set as below.
1. Reliability property will be set as COMMUNICATION_FAILURE.
2. Fault / Alarm flag of Status_Flags property will be set as TRUE.
3. Present_Value property is readable but the value is not guaranteed.
Object setting when there is general error
If any air conditioner related error occurs, the property will be set as below.
1. The Reliability property value of each object will be set as UNRELIABLE_OTHER.
2. FAULT / Alarm flag of Status Flags property will be set as TRUE.
Main service
Time setting
Time synchronization Service is a service that allows the time of BACnet Gateway to
be synchronized with the time of PC.
COV (Change Of Value)
COV service is supported and you can set confirmed or unconfirmed COV.
You can set lifetime value.
COV registration information will disapper when a BACnet gateway is switched
off. The reserved value caused by the power supply problem is not guaranteed
according to the BACnet regulation.