System Architecture

OnOff
controller
Outdoor
Unit
Connecting outdoor units and BACnet Gateway
- You can control up to 80 outdoor units and 256 indoor units using BACnet Gateway.
*Each communication channel of BACnet Gateway can be connected with 16 outdoor units.
- The more outdoor units are connected, the longer time takes for tracking.
For the devices which support new communication, set the communication channel
mode on '[System setting]-[Tracking]' menu as 'NEW' and for SIM/PIM which conventional
communication is applied, set the communication channel mode as 'IM'. You cannot
connect indoor & outdoor unit SET which conventional communication is applied to new
communication BACnet Gateway.
When setting communication channel mode as 'NEW', the address of virtual centralized
control will be assigned.
Channel 0: Virtual OnOff controller 11, Channel 1: Virtual OnOff controller 12,
Channel 2: Virtual OnOff controller 13, Channel 4: Virtual OnOff controller 14,
Channel 5: Virtual OnOff controller 15
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 9
BMS system
RS 485
Max 256 Indoor units
(DVM Series)
BMS Engineering
Internet
TRANE Engineering
BACnet Gateway
9