Bacnet Point List - Samsung BACnet Gateway MIM-B17N Installation Manual

Hide thumbs Also See for BACnet Gateway MIM-B17N:
Table of Contents

Advertisement

BACnet Point List

Indoor Unit
Single indoor unit has following point list.
Instance
Number
1
Indoor Temperature
2
Set temperature
3
Setting lower temperature limit
4
Setting upper temperature limit
The power value of an indoor
5
unit after the basic date
The number of hours usage of an
6
indoor unit after the basic date
7
Power value within period
The number of hours usage of
8
an indoor unit within period
9
Power On/Off
Applying lower temperature
10
limit setting
Applying upper temperature
11
limit setting
12
Filter sign status
13
Filter sign reset
14
Operation mode status
15
Fan speed status
16
Air flow direction status
17
Operation mode limit status
18
Remote controller limit status
Integrated error code of both
19
indoor unit and outdoor unit
* 20
SPI setting
* 21
HumanSensor setting
22
AC Indoor Notify
 Temperature setting range can be different depending on the model and the common
range is as follows:
Auto: 18˚C~30˚C
Cool: 18˚C~30˚C
Heat: 16˚C~30˚C
Fan: Temperature cannot be adjusted
Dry: 18˚C~30˚C
(*) Mark is optionally supported.
62
E-
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 62
Object
Object
Type
AI
AC_RoomTemp_xx_xxxxxx
AV AC_Temp_Set_xx_xxxxxx
AV AC_Cool_LimitTemp_xx_xxxxxx
AV AC_Heat_LimitTemp_xx_xxxxxx
AI
AC_Baseline_kWh_xx_xxxxxx
AC_Baseline_Minute_xx_
AI
xxxxxx
AI
AC_Period_kWh_xx_xxxxxx
AI
AC_Period_Minute_xx_xxxxxx Minute
BV
AC_Power_xx_xxxxxx
BV
AC_Cool_Limit_set_xx_xxxxxx
BV
AC_Heat_Limit_set_xx_xxxxxx
BI
AC_FilterSign_xx_xxxxxx
BO AC_FilterSign_Reset_xx_xxxxxx
AC_Operation_Mode_xx_
MV
xxxxxx
MV AC_FanSpeed_xx_xxxxxx
MV AC_FanFlow_xx_xxxxxx
MV AC_Mode_Limit_xx_xxxxxx
AC_Remocon_Limit_xx_
MV
xxxxxx
AI
AC_Error_Code_xx_xxxxxx
BV AC_SPI_xx_xxxxxx
BV AC_MDS_xx_xxxxxx
NC AC_Notify_xx_xxxxxx
Unit
Object Name
Inactive Active
Text-1
Text-2
°C
°C
°C
°C
kWh
Minute
kWh
Off
False
True
False
True
False
True
False
True
Auto
Cool
Auto
Low
None
Vertical
No Limit Cool Only Heat Only
Disable
Enable RC
Refer to list of error code
False
True
False
True
When the error occurred, send event to list of
destination in the recipient_list. (Max : 8)
Status value
Text-3
Text-4 Text-5
On
Heat
Fan
Dry
Mid
High
Horizon
All
Conditional
RC
RC
2013-04-25 오전 10:14:42

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bacnet mim-b17n

Table of Contents