Samsung BACnet Gateway MIM-B17N Installation Manual page 38

Hide thumbs Also See for BACnet Gateway MIM-B17N:
Table of Contents

Advertisement

Selecting the contact point control pattern
1
Click [System Settings].
2
Click [Edit] from the 'Select the contact point control pattern' section.
3
Select the pattern you want to check when checkboxes enables.
 Pattern 1[No external input]: No operation will be made when inputting contact
point control signal.
 Pattern 2[Level (Emergency stop)]: Commands to stop all operation of indoor unit
(except DDC) and disable remote control when inputting contact point control
signal.
In level emergency stop status, it will not be controllable even if the command is
from upper controller.
 Pattern 3[Level (Operation/Stop)]: Level signal input timing. It changes operation/
stop status of all indoor units.
 Pattern 4[Pulse (Operation/Stop, Disable/Enable)]: Pulse signal. It changes
operation/stop status of all indoor units.
4
When pattern is selected, click [Save].
NASAS_MIM-B17N_BACnet Gateway_IM_EN_03719A(1).indd 37
37