Samsung DVM PLUS III Technical Data Book
Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

cover
1/8/08 3:06 PM
Page 1
SAMSUNG DVM Air Conditioner
2008
DVM
Technical
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM
DVM
Data
Book

Advertisement

Table of Contents
loading

Summary of Contents for Samsung DVM PLUS III

  • Page 1 1/8/08 3:06 PM Page 1 SAMSUNG DVM Air Conditioner 2008 Technical Data Book DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM DVM...
  • Page 2 1. products(01~41) 3/14/08 22:01 Page 2 ✛ ✛ ✛ ✛ ✛ ontents Products Introduction New technology of DVM PLUS , DVM PLUS Main features of DVM PLUS , DVM PLUS Line-up DVM design process Indoor Units Slim 1 way cassette 2 way cassette Mini 4 way cassette 4 way cassette...
  • Page 3 Panels & Drain pumps Branch joints MCU kits EEV kits Control Systems Individual control system Centralized control system Integrated management system Power distribution system External contact control system Building management system Installation DVM PLUS III / DVM PLUS III HR...
  • Page 4 1. products(01~41) 3/14/08 22:01 Page 4 DVM PLUS III...
  • Page 5 1-1. DVM PLUS III, DVM PLUS III HR -------------------------------------- 1-2. DVM PLUS III HR -------------------------------------------------------- 1-3. Mini DVM -------------------------------------------------------------------- New technology of DVM PLUS III, DVM PLUS III HR 2-1. Digital hybrid system ------------------------------------------------------ 2-2. High efficiency Ø8 heat exchanger -------------------------------------- 2-3.
  • Page 6 1-1. DVM PLUS III, DVM PLUS III HR DVM PLUS III, DVM PLUS III HR is a module multi-system air conditioner that has the world's largest capacity(8~64HP) with the application of a DVI (Digital Vapor Injection) compressor, and can connect up to a maximum of 64 indoor units.
  • Page 7 • For seasonal air-conditioning which may need a simultaneous cooling and heating operation. • In case of medium or large office, DVM PLUS III HR satisfies cooling and heating operation simultaneously for the requirements of interior and perimeter zone.
  • Page 8 4) New MCU MCU subcooling heat exchanger The MCU for DVM PLUS III HR has a double-tube heat exchanger for securing high subcooling effect by the MCU itself, thus improving the reliability of the long piping and cooling and heating performance.
  • Page 9 ❈ 3Ø, 380~415V, 50Hz (5, 6HP) 1) High energy efficiency Mini DVM is equipped with the Digital Scroll Compressor which ensures a high level of cooling and heating COP. Cooling 3.33 3.04 3.05 Samsung Heating 3.91 3.87 3.73 Average 3.62 3.46 3.39...
  • Page 10 Mini DVM is highly reliable to be adopted digital scroll compressor which can be controlled easily. Because digital scroll compressor needs just one control PCB, it achieves simple structure and high reliability. Only 1-PCB board (197 x 98mm) Large size 3-PCB board Samsung Company A EMC filter Control PCB...
  • Page 11 3/14/08 22:01 Page 11 New technology of DVM PLUS III, DVM PLUS III HR 2-1. Digital hybrid system DHS (Digital Hybrid System) is a brand new concept system composed of DVI (Digital Vapor Injection) compressor, vapor injection technology and turbo intercooler. These 3 factors together provide highly efficient performance.
  • Page 12 Page 12 Products New technology of DVM PLUS III, DVM PLUS III HR 2-2. High efficiency Ø8 heat exchanger Efficient Ø8 grooved tube reduced pressure loss while increasing heat exchange rates to improve COP. Grooved shape is designed to be high and slim to increase heat transfer performance inside the tube.
  • Page 13 Fan guard has been optimized to improve air volume and reduce noise and vibration. • BLDC motor, which is 2.7% more efficient than the competitors has been applied. • High static pressure propeller fan and the optimum Bell mouth figuration for high external static pressure. (8mmAq) DVM PLUS III Company A 900 1000...
  • Page 14 3/14/08 22:01 Page 14 Products New technology of DVM PLUS III, DVM PLUS III HR 2-5. Upgraded control systems 1) Easy management system A wide range of control system is provided to support various needs and applications such as individual or central control and automated building management.
  • Page 15 1. products(01~41) 3/14/08 22:01 Page 15 3) Simple contact control Contact interface makes it possible to connect mechanical contacts to indoor units directly, allowing individual and group control as well as malfunction monitoring of the indoor units. Direct ON/OFF indoor unit control Window Emergent control synchronization...
  • Page 16 High performance and efficiency 3-1. High COP High efficiency DVM PLUS III has improved average cooling and heating COP compared to conventional products and achieved the world’s top class energy efficiency. • DHS(Digital Hybrid System) technology increased refrigerant flow rate and evaporation enthalpy difference.
  • Page 17 • Improve COP using multiple heat exchangers of outdoor units at part loads. Scroll Scroll Scroll Scroll A unit B unit 3-4. Free installation DVM PLUS III provides the degree of freedom from priority of capacity when installing outdoor units in module. Conventional model Company A 14HP 10HP 10HP 14HP 14HP...
  • Page 18 3-6. Small size and light weight To facilitate the convenience and mobility of module installation, DVM PLUS III is the best compact air conditioner in the world with its small size and weight. It reduces the burden of weight and minimizes the required installation space (it can be installed in the rooftop), ensuring a more spacious place for relaxation, parking lots, or additional offices, for instance.
  • Page 19 3-8. Free piping & wiring directions DVM PLUS III is easy to install as its piping can be connected from front, right, left and bottom side. Wiring hole (Conduits) adds convenience as it allows power and communication lines to be connected in various ways and directions.
  • Page 20 Data storing Time 3-13. Refrigerant pump-down and pump-out DVM PLUS III provides several functions to facilitate the replacements of product, additional installation and maintenance without much effort. Refrigerant pump-down function In case of moving outdoor units, maintenance of pipes between indoor units, between outdoor units and indoor units, it is possible that recover refrigerant into outdoor units.
  • Page 21 1) DVI scroll compressor As DVM PLUS III employs a DVI scroll compressor, it can adjust not only the compressor capacity linearly in accordance with indoor loads, but at minimum load. Therefore it is superior to Inverter system in creating a pleasant indoor environment and energy saving.
  • Page 22 Cooling operation Cooling operation cooling operation Oil recovery during Heating operation Cooling operation heating operation 3-17. Acceleration life cycle test All parts fitted to DVM PLUS III ensure reliability for life cycle through ALT (Acceleration Life cycle Test ). I-22...
  • Page 23 Robust design through CAE Sound quality 3-19. Sound quality DVM PLUS III improves the problem of noise not only at the low sound level, but also at the actual sound quality level by: • Developing a sound insulation material for compressor •...
  • Page 24 RoHS restriction only applies to small or large household appliances, IT equipment, lightings, power train, toys, leisure or sports equipment, and vending machines. Samsung expands the RoHS restriction into its entire range of products based on its own environmental policies.
  • Page 25 1/10 HP (3 Digits) ② ⑥ Type Rating voltage Mini DVM 1Ø, 220~240V, 50Hz DVM PLUS III 3Ø, 208~230V, 60Hz DVM PLUS III HR 3Ø, 380~415V, 50Hz 3Ø, 380V, 60Hz ③ Mode 3Ø, 460V, 60Hz Heat Pump Heat Recovery ⑦...
  • Page 26 1. products(01~41) 3/14/08 22:01 Page 26 Products Line-up 4-1. Outdoor units 3) DVM PLUS III and DVM PLUS III HR high efficiency combination table RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP...
  • Page 27 1. products(01~41) 3/14/08 22:01 Page 27 4) DVM PLUS III, DVM PLUS III HR compact combination table RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVHT160GE RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE RVXVRT160GE 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP 42HP...
  • Page 28 1. products(01~41) 3/14/08 22:01 Page 28 Products Line-up 4-2. Indoor units 1) Nomenclature ODEL NAME ① ② ③ ④ ⑤ ⑥ ⑦ ① ⑤ Classification Capacity Indoor unit (R410A) x 1/10 kW (3 digits) Notation Cooling Heating ② Classification by product group Cassette type Duct type Wall mounted type...
  • Page 29 1. products(01~41) 3/14/08 22:01 Page 29 2) Indoor units Capacity 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 6.0kW 7.1kW 9.0kW 11.2kW 12.8kW 14.0kW Type Slim 1way cassette 2way cassette Mini 4way cassette 4way cassette Slim Duct M.S.P Duct Ceiling Console Neo- Forte Vivace I-29...
  • Page 30 DVM PLUS III, DVM PLUS III HR (Non RAC or Console) Power distribution Power distribution unit MCM-B102 DVM Series, FJM ❇ DVM Series : Mini DVM, DVM, DVM HR, DVM PLUS II, DVM PLUS II HR, DVM PLUS III, DVM PLUS III HR I-30...
  • Page 31 Over 139.2 kW Outdoor joint MXJ-T3819K Below 48 HP DVM PLUS II , DVM PLUS II HR, Requisite (Outdoor Connection) DVM PLUS III,DVM PLUS III HR (Modul e ) MXJ-T4422K Over 50 HP Outdoor joint MXJ-T3100K Below 48 HP DVM PLUS II HR...
  • Page 32 1. products(01~41) 3/14/08 22:01 Page 32 Products DVM design process 5-1. DVM design process DVM is a multi-system air conditioner that changes its performance by different conditions such as design temperature, indoor and outdoor unit combination rates, heating operation rates, piping length, and level difference. It is important to select the appropriate design condition to the load specification of each room.
  • Page 33 1. products(01~41) 3/14/08 22:01 Page 33 5-2. DVM design process example (Cooling) (As for both cooling and heating units, it is necessary to review its design for heating) 1) Determine design conditions Design temperature Cooling Cooling Outdoor Outdoor Indoor Indoor ❈...
  • Page 34 1. products(01~41) 3/14/08 22:01 Page 34 Products DVM design process 5-2. DVM design process example (Cooling) 2) Select preliminary indoor unit for each zone Indoor unit selection example ( Zone A) - Cooling load : 3.3kW - Sensible heat load : 2.4kW - Indoor unit type : Vivace ❈...
  • Page 35 1. products(01~41) 3/14/08 22:01 Page 35 3) Select preliminary outdoor units Before selecting outdoor units, decide the permissible combination rates for indoor and outdoor unit. ➊ Determining permissible combination rates for indoor and outdoor units: Below 110% ❷ Calculate the sum of total capacity of the selected indoor units: 52.9kW (Refer to the table below) 52.9kW = [3.6kW + 7.1kW + 5.6kW + 7.1kW + 11.2kW + 7.1kW + 11.2kW] Zone Total cooling load (kW)
  • Page 36 1. products(01~41) 3/14/08 22:01 Page 36 Products DVM design process 5-2. DVM design process example (Cooling) 4) Calculate the actual capacity of outdoor units The actual capacity of outdoor unit can be calculated as follows: ➊ Using capacity tables, get the capacity values according to indoor and outdoor design temperature and actual combination ratio. ❷...
  • Page 37 1. products(01~41) 3/14/08 22:01 Page 37 As shown in the example, when the combination rate exceeds 100%, the capacity of outdoor unit is calculated using 100, 110, 120, 130% tables. However, when the combination rate is below 100%, use capacity presented at the 100% table. Thus, outdoor unit capacity can be calculated as follows: Combination rate of actual indoor and outdoor units= 130% Refer to 130% capacity table...
  • Page 38 1. products(01~41) 3/14/08 22:01 Page 38 Products DVM design process 5-2. DVM design process example (Cooling) ❈ Piping length : L + [the longest pipe out of (A, B, C, D)] Piping height : The highest pipe out of (H1, H2, H3, H4) Maximum level difference : H4 5) Calculate the actual capacity of each outdoor unit The actual capacity of each outdoor unit is as follows:...
  • Page 39 1. products(01~41) 3/14/08 22:01 Page 39 6) Comparison between the actual capacity of each indoor unit & cooling and heating load Here, the calculated actual capacity is the one that is obtained when all indoor units are in operation at the same time.
  • Page 40 In case of a heat pump model, execute the following equipment selection procedure. Samsung supplies two kinds of DVM Selection Program called DVM-Pro sales & CAD mode respectively. DVM-Pro(CAD), developed based on technical data, will help DVM designer to select DVM products as well as CAC &...
  • Page 41 Page 41 2) DVM-Pro (CAD Mode) Samsung will supply powerful CAD drawing program called ‘DVM-Pro CAD’. It has all technical data of DVM products including block diagram. It will be helpful for unfamiliar users to CAD program as well as expert users.
  • Page 42 3/14/08 22:09 Page 2 DVM PLUS III II-2...
  • Page 43 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 3 Indoor Units Slim 1 way cassette ....2 way cassette ..... Mini 4 way cassette .
  • Page 44 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 4 Indoor Units II-4...
  • Page 45 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 5 Slim 1 way cassette (AVXCSH✴✴✴E✴) 1-1. Features ---------------------------------------------------------------- 1-2. Specifications ---------------------------------------------------------- 1-3. Capacity tables -------------------------------------------------------- 1-4. Dimensional drawing -------------------------------------------------- 1-5. PCB connector lay-out ------------------------------------------------ 1-6. Electrical wiring diagram ---------------------------------------------- 1-7. Sound pressure level -------------------------------------------------- 1-8.
  • Page 46 Ensure that there is sufficient installation space. Allow at least 170mm for the installation. Lighter indoor unit The first to apply ABS cabinets into its indoor units, Samsung has 10.5kg 38% Down achieved the lightest units on the market. Its slim lightweight design makes installation and maintenance a breeze.
  • Page 47 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 7 1-2. Specifications 1) Technical specifications Model AVXCSH022E✴ AVXCSH028E✴ AVXCSH036E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 HP / HR HP / HR HP / HR Mode* Performance Capacity Cooling* 7,500 9,500 12,200 Btu/h Heating* Btu/h 8,500 10,900 13,600...
  • Page 48 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 8 Indoor Units Slim 1 way cassette 1-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB)
  • Page 49 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 9 2) Heating TC : Total Capacity(kW) Indoor temperature (ºC, WB) Outdoor 16.0 18.0 20.0 22.0 24.0 Model temperature (ºC) II-9...
  • Page 50 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 10 Indoor Units Slim 1 way cassette 1-4. Dimensional drawing Unit:mm Suspension bolts(M8~M10) X 4EA Description Name 2.2kW 2.8kW 3.6kW Liquid pipe connection Ø6.35 Flare Gas pipe connection Ø12.70 Flare Drain pipe connection VP20 (OD 25, ID 20) Conduit for power supply &...
  • Page 51 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 11 1-5. PCB connector lay-out 14 13 FUNCTION CN # COLOR FUNCTION CN61 Sliding Panel 1(Only for sliding panel) CN62 White Sliding Panel 2 (Only for sliding panel) Main Address Setting CN60 White Louver (00~63) CN10 Black MICOM Download...
  • Page 52 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 12 Indoor Units Slim 1 way cassette 1-6. Electrical wiring diagram II-12...
  • Page 53 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 13 1-7. Sound pressure level 1) Operation sound level Unit : dB(A) Model High AVXCSH022E✴ AVXCSH028E✴ Microphone AVXCSH036E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 54 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 14 Products Slim 1 way cassette 1-8. Temperature and air flow distribution AVXCSH036E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 60° 1.0m/s 0.8m/s 0.2m/s 0.2m/s 0.6m/s 0.6m/s Floor distance 2) Cooling temperature distribution ◆...
  • Page 55 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 15 2 way cassette (AVXC2H✴✴✴E✴) 2-1. Features ---------------------------------------------------------------- 2-2. Specifications ---------------------------------------------------------- 2-3. Capacity tables -------------------------------------------------------- 2-4. Dimensional drawing -------------------------------------------------- 2-5. PCB connector lay-out ------------------------------------------------ 2-6. Electrical wiring diagram ---------------------------------------------- 2-7. Sound pressure level -------------------------------------------------- 2-8. Temperature and air flow distribution -------------------------------- II-15...
  • Page 56 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 16 Indoor Units 2 way cassette 2-1. Features Standard formula for easy installation The dimensions of the 2 way cassette allows for easy installation into standard ceiling tiles (W600 x H600), so everything just falls into place.
  • Page 57 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 17 2-2. Specifications 1) Technical specifications Model AVXC2H056E✴ AVXC2H071E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 HP / HR HP / HR Mode* Performance Capacity Cooling* 19,100 24,200 Btu/h Heating* Btu/h 21,400 27,200 Condensate (with High fan speed) Liters/h 2.87 3.19...
  • Page 58 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 18 Indoor Units 2 way cassette 2-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB)
  • Page 59 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 19 2-4. Dimensional drawing Unit:mm Suspension bolts(M8~M10) X 4EA Description Name 5.6kW 7.1kW Liquid pipe connection Ø6.35 Flare Ø9.52 Flare Gas pipe connection Ø12.70 Flare Ø15.88 Flare Drain pipe connection VP25(OD 32, ID 25) Conduit for power supply & communication wiring Air inlet grille Air outlet louver Fresh air intake...
  • Page 60 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 20 Indoor Units 2 way cassette 2-5. PCB Connector Lay-out Main PCB Sub PCB Main PCB FUNCTION CN # COLOR FUNCTION CN75 Black Ventilator Main Address Setting (00~63) Communication with CN31 Outdoor Units (COM1) SW01 SW02 Communication with Wired SW03...
  • Page 61 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 21 2-6. Electrical wiring diagram II-21...
  • Page 62 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 22 Indoor Units 2 way cassette 2-7. Sound pressure level 1) Operation sound level Unit : dB(A) 1.5m Model High AVXC2H056E✴ Microphone AVXC2H071E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 63 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 23 2-8. Temperature and air flow distribution AVXC2H071E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 54° 0.8m/s 0.8m/s 0.6m/s 0.6m/s 0.2m/s 0.4m/s 0.4m/s 0.4m/s 0.4m/s 0.2m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 54° Floor distance 3) Heating air velocity distribution ◆...
  • Page 64 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 24 Indoor Units II-24...
  • Page 65 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 25 Mini 4 way cassette (AVXCMH✴✴✴E✴) 3-1. Features ---------------------------------------------------------------- 3-2. Specifications ---------------------------------------------------------- 3-3. Capacity tables -------------------------------------------------------- 3-4. Dimensional drawing -------------------------------------------------- 3-5. PCB connector lay-out ------------------------------------------------ 3-6. Electrical wiring diagram ---------------------------------------------- 3-7. Sound pressure level -------------------------------------------------- 3-8.
  • Page 66 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 26 Indoor Units Mini 4 way cassette 3-1. Features Unit : mm Ideal compact size The mini 4 way cassette can be installed one standard ceiling tiles (W600xH600),which can save installation time. 670(Panel) 575(Body) Fan speed adjustment Fan speed can be adjusted according to ceiling height by adjusting dip switch of indoor unit’s PCB.
  • Page 67 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 27 3-2. Specifications 1) Technical specifications Model AVXCMH028E✴ AVXCMH036E✴ AVXCMH056E✴ AVXCMH060E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 HP / HR HP / HR HP / HR HP / HR Mode* Performance Capacity Cooling* 9,500 12,200 19,100 20,400...
  • Page 68 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 28 Indoor Units Mini 4 way cassette 3-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB)
  • Page 69 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 29 2) Heating TC : Total Capacity(kW) Indoor temperature (ºC, WB) Outdoor 16.0 18.0 20.0 22.0 24.0 Model temperature (ºC) II-29...
  • Page 70 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 30 Indoor Units Mini 4 way cassette 3-4. Dimensional drawing Unit:mm Suspenslon bolts(M8~M10) X 4EA Description Name 2.8kW 3.6kW 5.2kW 6.0kW Liquid pipe connection Ø6.35 Flare Gas pipe connection Ø12.70 Flare Drain pipe connection VP25(OD 32, ID 25) Conduit for power supply &...
  • Page 71 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 31 3-5. PCB connector lay-out FUNCTION CN # COLOR FUNCTION CN62 Blue CN60 White Louver Main Address Setting (00~63) CN81 Error Check, Indoor unit Operation CN83 External Contact Control SW01 SW02 CN51 Black Float Switch SW03 SW04 CN41...
  • Page 72 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 32 Indoor Units Mini 4 way cassette 3-6. Electrical wiring diagram II-32...
  • Page 73 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 33 3-7. Sound pressure level 1) Operation sound level Unit : dB(A) Model High AVXCMH028E✴ 1.5m AVXCMH036E✴ AVXCMH056E✴ Microphone AVXCMH060E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 74 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 34 Indoor Units Mini 4 way cassette 3-8. Temperature and air flow distribution AVXCMH036E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 37° 0.6m/s 0.6m/s 0.4m/s 0.4m/s 0.2m/s 0.2m/s 2.5 m 1.5 m 1.5m 2.5 m Floor distance 2) Cooling temperature distribution...
  • Page 75 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 35 AVXCMH060E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 37° 0.8m/s 0.8m/s 0.6m/s 0.6m/s 0.4m/s 0.4m/s 0.2m/s 0.2m/s 2.5 m 1.5 m 1.5m 2.5 m Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 37° 2.5 m 1.5 m 1.5m...
  • Page 76 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 36 Indoor Units II-36...
  • Page 77 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 37 4 way cassette (AVXC4H✴✴✴E✴) 4-1. Features ---------------------------------------------------------------- 4-2. Specifications ---------------------------------------------------------- 4-3. Capacity tables -------------------------------------------------------- 4-4. Dimensional drawing -------------------------------------------------- 4-5. PCB connector lay-out ------------------------------------------------ 4-6. Electrical wiring diagram ---------------------------------------------- 4-7. Sound pressure level -------------------------------------------------- 4-8. Temperature and air flow distribution -------------------------------- II-37...
  • Page 78 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 38 Indoor Units 4 way cassette 4-1. Features New turbo fan Quiet operation : The aerodynamically designed ‘Turbo fan’ minimizes noise from the turbulence of blade movement. ‘A’ View ‘B’ View ‘C’ View Uniform distribution : The new turbo fan with side blades provides extreme cooling or heating airflow through 4 separate outlets, so the entire room gets cool or warm faster.
  • Page 79 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 39 4-2. Specifications 1) Technical specifications Model AVXC4H045E✴ AVXC4H056E✴ AVXC4H071E✴ AVXC4H090E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 Heat Pump Heat Pump HP / HR HP / HR Mode* Performance Capacity Cooling* 15,300 19,100 24,200 30,700 Btu/h Heating*...
  • Page 80 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 40 Indoor Units 4 way cassette 4-2. Specifications 1) Technical specifications Model AVXC4H112E✴ AVXC4H128E✴ AVXC4H140E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 HP / HR HP / HR HP / HR Mode* Performance Capacity Cooling* 11.2 12.8 14.0 38,200...
  • Page 81 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 41 4-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB) Model...
  • Page 82 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 42 Indoor Units 4 way cassette 4-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB)
  • Page 83 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 43 TC : Total Capacity(kW) Indoor temperature (ºC, WB) Outdoor 16.0 18.0 20.0 22.0 24.0 Model temperature (ºC) 10.3 10.1 10.0 10.6 10.3 10.0 10.9 10.5 10.0 11.2 10.6 10.0 11.6 10.8 10.0 10.2 10.1 10.7 10.6 10.5...
  • Page 84 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 44 Indoor Units 4 way cassette 4-4. Dimensional drawing 1) AVXC4H045/056/071/090E✴ Unit:mm Suspenslon bolts(M8~M10) X 4EA Description Name 4.5kW 5.6kW 7.1kW 9.0kW Liquid pipe connection Ø6.35 Flare Ø9.52 Flare Gas pipe connection Ø12.70 Flare Ø15.88 Flare Drain pipe connection VP25(OD 32, ID 25) Conduit for power supply &...
  • Page 85 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 45 2) AVXC4H112/128/140E✴ Unit:mm Suspenslon bolts(M8~M10) X 4EA Description Name 11.2kW 12.8kW 14.0kW Liquid pipe connection Ø9.52 Flare Gas pipe connection Ø15.88 Flare Drain pipe connection VP25(OD 32, ID 25) Conduit for power supply & communication wiring Air inlet grille Air outlet louver Fresh air intake...
  • Page 86 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 46 Indoor Units 4 way cassette 4-5. PCB connector lay-out Main PCB Noise filter PCB Main PCB FUNCTION CN # COLOR FUNCTION CN62 Blue Main Address Setting (00~63) CN60 White Louver SW01 SW02 CN81 Error Check, Indoor unit Operation CN83 External Contact Control SW03...
  • Page 87 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 47 4-6. Electrical wiring diagram II-47...
  • Page 88 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 48 Indoor Units 4 way cassette 4-7. Sound pressure level 1) Operation sound level Unit : dB(A) Unit : dB(A) Model High Model High AVXC4H045E✴ AVXC4H112E✴ 1.5m AVXC4H056E✴ AVXC4H128E✴ AVXC4H071E✴ AVXC4H140E✴ Microphone AVXC4H090E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 89 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 49 4-8. Temperature and air flow distribution AVXC4H090E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 37° 1.0m/s 1.0m/s 0.8m/s 0.8m/s 0.6m/s 0.2m/s 0.2m/s 0.6m/s 0.4m/s 0.4m/s 0.2m/s 0.2m/s Floor distance 2) Cooling temperature distribution ◆...
  • Page 90 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 50 Indoor Units 4 way cassette 4-8. Temperature and air flow distribution AVXC4H140E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 37° 1.0m/s 1.0m/s 0.2m/s 0.2m/s 0.8m/s 0.8m/s 0.6m/s 0.6m/s 0.4m/s 0.4m/s 0.3m/s 0.3m/s 0.2m/s 0.2m/s 0.2m/s...
  • Page 91 chapter2_Indoor units(002-051) 3/14/08 22:09 Page 51 Slim duct (AVXDSH✴✴✴E✴) 5-1. Features ---------------------------------------------------------------- 5-2. Specifications ---------------------------------------------------------- 5-3. Capacity tables -------------------------------------------------------- 5-4. Dimensional drawing -------------------------------------------------- 5-5. PCB connector lay-out ------------------------------------------------ 5-6. Electrical wiring diagram ---------------------------------------------- 5-7. Sound pressure level -------------------------------------------------- 5-8. Recommended operation range ------------------------------------ II-51...
  • Page 92 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 52 Indoor Units Slim duct 5-1. Features Slim design Only 199mm thick, this slim design makes installation, maintenance, and repair easy. 199mm 199mm 220mm 225mm Easy filter cleaning After 1,000 hours of operation the filter clean indicator will alert you that the filter should be cleaned.
  • Page 93 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 53 5-2. Specifications 1) Technical specifications Model AVXDSH022E✴ AVXDSH028E✴ AVXDSH036E✴ AVXDSH045E✴ AVXDSH056E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 HP / HR HP / HR HP / HR HP / HR HP / HR Mode* Performance Capacity...
  • Page 94 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 54 Indoor Units Slim duct 5-2. Specifications 1) Technical specifications Model AVXDSH071E✴ AVXDSH090E✴ AVXDSH112E✴ AVXDSH128E✴ AVXDSH140E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 HP / HR HP / HR HP / HR HP / HR HP / HR Mode* Performance...
  • Page 95 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 55 5-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB) Model...
  • Page 96 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 56 Indoor Units Slim duct 5-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB)
  • Page 97 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 57 2) Heating TC : Total Capacity(kW) Indoor temperature (ºC, WB) Outdoor 16.0 18.0 20.0 22.0 24.0 Model temperature (ºC) II-57...
  • Page 98 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 58 Indoor Units Slim duct 5-3. Capacity tables 2) Heating TC : Total Capacity(kW) Indoor temperature (ºC, WB) Outdoor 16.0 18.0 20.0 22.0 24.0 Model temperature (ºC) 10.3 10.1 10.0 10.6 10.3 10.0 10.9 10.5 10.0 11.2 10.6...
  • Page 99 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 59 5-4. Dimensional drawing 1) AVXDSH022/028/036E✴ Unit:mm Suspenslon bolts(M8~M10) X 4EA Duct flange connection bolts(M4) X 22EA Description Name 2.2kW 2.8kW 3.6kW Liquid pipe connection Ø6.35 Flare Gas pipe connection Ø12.70 Flare Drai n pi p e connecti o n wi t hout opti o nal drai n pump ki t s VP25(OD 32, ID 25) Drain pipe connection with optional drain pump kits Quick lock...
  • Page 100 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 60 Indoor Units Slim duct 5-4. Dimensional drawing 2) AVXDSH045/056/071E✴ Unit:mm Suspenslon bolts(M8~M10) X 4EA Duct flange connection bolts(M4) X 26EA Description Name 4.5kW 5.6kW 7.1kW Liquid pipe connection Ø6.35 Flare Ø9.52 Flare Gas pipe connection Ø12.70 Flare Ø15.88 Flare Drai n pi p e connecti o n wi t hout opti o nal drai n pump ki t s...
  • Page 101 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 61 3) AVXDSH090/112/128/140E✴ Unit:mm Suspenslon bolts(M8~M10) X 4EA Duct flange connection bolts(M4) X 32EA Description Name 9.0kW 11.2kW 12.8kW 14.0kW Liquid pipe connection Ø9.52 Flare Gas pipe connection Ø15.88 Flare Drai n pi p e connecti o n wi t hout opti o nal drai n pump ki t s VP25(OD 32, ID 25) Drain pipe connection with optional drain pump kits Quick lock...
  • Page 102 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 62 Indoor Units Slim duct 5-5. PCB connector lay-out 1) AVXDSH022/028/036/045/056/071E✴ FUNCTION CN # COLOR FUNCTION CN51 Black Float Switch CN41 White Room Sensor, Eva-In Sensor Main Address Setting (00~63) CN42 White Eva-Out Sensor SW01 SW02 CN32 White...
  • Page 103 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 63 2) AVXDSH090/112/128/140E✴ Main PCB BLDC Driver PCB Main PCB FUNCTION CN # COLOR FUNCTION CN51 Black Float Switch Main Address Setting CN41 White Room Sensor, Eva-In Sensor (00~63) CN42 White Eva-Out Sensor SW01 SW02 CN32 White DC12V for Wired Remote Controller...
  • Page 104 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 64 Indoor Units Slim duct 5-6. Electrical wiring diagram 1) AVXDSH022/028/036/045/056/071E✴ MICOM Download II-64...
  • Page 105 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 65 2) AVXDSH090/112/128/140E✴ MICOM Download II-65...
  • Page 106 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 66 Indoor Units Slim duct 5-7. Sound pressure level 1) Operation sound level Unit : dB(A) Unit : dB(A) Model High Model High Discharge Suction AVXDSH022E✴ AVXDSH071E✴ Duct Duct AVXDSH028E✴ AVXDSH090E✴ AVXDSH036E✴ AVXDSH112E✴ 1.5m AVXDSH045E✴ AVXDSH128E✴...
  • Page 107 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 67 (6) AVXDSH071E✴ (7)AVXDSH090E✴ (8) AVXDSH112E✴ HIGH HIGH NC 45 NC 45 NC 45 HIGH NC 40 NC 40 NC 40 NC 35 NC 35 NC 35 NC 30 NC 30 NC 30 NC 25 NC 25 NC 25 NC 20...
  • Page 108 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 68 Indoor Units Slim duct 5-8. Recommended operation range (1) AVXDSH022E✴ (2) AVXDSH028E✴ (3) AVXDSH036E✴ 220V/50Hz 220V/50Hz 220V/50Hz 49.0 0.20 49.0 0.20 49.0 0.20 Upper ESP Limit Upper ESP Limit Upper ESP Limit 39.2 0.16 39.2 0.16 39.2...
  • Page 109 chapter2_Indoor units(052~107) 3/21/08 11:23 Page 69 (6) AVXDSH071E✴ (7) AVXDSH090E✴ (8) AVXDSH112E✴ 220V/50Hz 220V/50Hz 220V/50Hz 49.0 0.20 68.6 0.28 68.6 0.28 Upper ESP Limit Upper ESP Limit 58.8 0.24 58.8 0.24 39.2 0.16 High ESP Area High ESP Area 49.0 0.20 49.0 0.20...
  • Page 110 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 70 Indoor Units II-70...
  • Page 111 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 71 duct (Middle static pressure) (AVXDUH✴✴✴E✴) 6-1. Features ---------------------------------------------------------------- 6-2. Specifications ---------------------------------------------------------- 6-3. Capacity tables -------------------------------------------------------- 6-4. Dimensional drawing -------------------------------------------------- 6-5. PCB connector lay-out ------------------------------------------------ 6-6. Electrical wiring diagram ---------------------------------------------- 6-7. Sound pressure level -------------------------------------------------- 6-8.
  • Page 112 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 72 Indoor Units duct (Middle static pressure) 6-1. Features Narrow width (5.6kW) MSP Duct type with only 900mm allows installation space to be saved. 900mm ❊ Width measured without control box. Easy to maintain The parts are easily accessible by simply opening the bottom panel,which reduces time and maintenance costs. Smart pressure control The smart pressure control system adjusts fan speed according to external static pressure,so the MSP duct always gives you consistent...
  • Page 113 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 73 6-2. Specifications 1) Technical specifications Model AVXDUH056E✴ AVXDUH071E✴ AVXDUH090E✴ AVXDUH112E✴ AVXUSH128E✴ AVXDUH140E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 Mode* HP / HR HP / HR HP / HR HP / HR HP / HR HP / HR Performance...
  • Page 114 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 74 Indoor Units duct (Middle static pressure) 6-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB)
  • Page 115 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 75 TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB) Model temperature ( º...
  • Page 116 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 76 Indoor Units duct (Middle static pressure) 6-3. Capacity tables 2) Heating TC : Total Capacity(kW) Indoor temperature (ºC, WB) Outdoor 16.0 18.0 20.0 22.0 24.0 Model temperature (ºC) 10.3 10.1 10.0 10.6 10.3 10.0 10.9 10.5 10.0...
  • Page 117 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 77 6-4. Dimensional drawing 1) AVXDUH056/071E✴ Unit:mm Suspenslon bolts(M8~M10) X 4EA Duct flange connection bolts(M4) X 16EA Description Name 5.6kW 7.1kW Liquid pipe connection Ø6.35 Flare Ø9.52 Flare Gas pipe connection Ø12.70 Flare Ø15.88 Flare Drai n pi p e connecti o n wi t hout opti o nal drai n pump ki t s VP25(OD 32, ID 25) Drain pipe connection with optional drain pump kits...
  • Page 118 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 78 Indoor Units duct (Middle static pressure) 6-4. Dimensional drawing 2) AVXDUH090E✴ Unit:mm Suspenslon bolts(M8~M10) X 4EA Duct flange connection bolts(M4) X 16EA Description Name 9.0kW Liquid pipe connection Ø9.52 Flare Gas pipe connection Ø15.88 Flare Drai n pi p e connecti o n wi t hout opti o nal drai n pump ki t s VP25(OD 32, ID 25) Drain pipe connection with optional drain pump kits...
  • Page 119 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 79 3) AVXDUH112E✴ Unit:mm Suspenslon bolts(M8~M10) X 4EA Duct flange connection bolts(M4) X 18EA Description Name 11.2kW Liquid pipe connection Ø9.52 Flare Gas pipe connection Ø15.88 Flare Drai n pi p e connecti o n wi t hout opti o nal drai n pump ki t s VP25(OD 32, ID 25) Drain pipe connection with optional drain pump kits Quick lock...
  • Page 120 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 80 Indoor Units duct (Middle static pressure) 6-4. Dimensional drawing 4) AVXDUH128/140E✴ Unit:mm Suspenslon bolts(M8~M10) X 4EA Duct flange connection bolts(M4) X 20EA Description Name 12.8kW 14.0kW Liquid pipe connection Ø9.52 Flare Gas pipe connection Ø15.88 Flare Drai n pi p e connecti o n wi t hout opti o nal drai n pump ki t s VP25(OD 32, ID 25)
  • Page 121 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 81 6-5. PCB connector lay-out 1) AVXDUH056/071/090E✴ FUNCTION CN # COLOR FUNCTION CN51 Black Float Switch CN41 White Room Sensor, Eva-In Sensor Main Address Setting (00~63) CN42 White Eva-Out Sensor SW01 SW02 CN32 White DC12V for Wired Remote Controller CN83 External Contact Control SW03...
  • Page 122 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 82 Indoor Units duct (Middle static pressure) 6-5. PCB connector lay-out 2) AVXDUH112/128/140E✴ FUNCTION CN # COLOR FUNCTION CN51 Black Float Switch CN41 White Room Sensor, Eva-In Sensor Main Address Setting CN42 White Eva-Out Sensor (00~63) CN32 White...
  • Page 123 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 83 6-6. Electrical wiring diagram 1) AVXDUH056/071/090E✴ MICOM Download II-83...
  • Page 124 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 84 Indoor Units duct (Middle static pressure) 6-6. Electrical wiring diagram 2) AVXDUH112/128/140E✴ MICOM Download II-84...
  • Page 125 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 85 6-7. Sound pressure level 1) Operation sound level Unit : dB(A) Model High Discharge Suction AVXDUH056E✴ Duct Duct AVXDUH071E✴ AVXDUH090E✴ 1.5m AVXDUH112E✴ Microphone AVXDUH128E✴ AVXDUH140E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 126 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 86 Indoor Units duct (Middle static pressure) 6-8. Recommended operation range (1) AVXDUH056E✴ (2) AVXDUH071E✴ (3) AVXDUH090E✴ 220V/50Hz 220V/50Hz 220V/50Hz External Static External Static External Static AVXDUH056E✴ AVXDUH071E✴ AVXDUH090E✴ pressure (mmAq) pressure (mmAq) pressure (mmAq) (4) AVXDUH112E✴...
  • Page 127 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 87 Console (AVXTJH✴✴✴E✴) 7-1. Features ---------------------------------------------------------------- 7-2. Specifications ---------------------------------------------------------- 7-3. Capacity tables -------------------------------------------------------- 7-4. Dimensional drawing -------------------------------------------------- 7-5. PCB connector lay-out ------------------------------------------------ 7-6. Electrical wiring diagram ---------------------------------------------- 7-7. Sound pressure level -------------------------------------------------- 7-8. Recommended operation range ------------------------------------ II-87...
  • Page 128 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 88 Indoor Units Console 7-1. Features Slim design This newly introduced console type is only 199mm thick, the slimmest on the market. Its slim design easily integrates the unit into your decor. It can't get any slimmer. 2way air outlets There are two separate air outlets for cooling and heating.
  • Page 129 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 89 7-2. Specifications 1) Technical specifications Model AVXTJH028E✴ AVXTJH036E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 HP / HR HP / HR Mode* Performance Capacity Cooling* 9,500 12,200 Btu/h Heating* 10,900 13,600 Btu/h Condensate (with High fan speed) Liters/h 0.96 1.75...
  • Page 130 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 90 Indoor Units Console 7-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB)
  • Page 131 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 91 7-4. Dimensional drawing Unit:mm Description Name 2.8kW 3.6kW Liquid pipe connection Ø6.35 Flare Gas pipe connection Ø12.70 Flare Drain pipe connection ID 18 Hose Conduit for power supply & communication wiring Air inlet grille Air outlet louver II-91...
  • Page 132 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 92 Indoor Units Console 7-5. PCB connector lay-out Main PCB Sub PCB Main PCB FUNCTION CN # COLOR FUNCTION Communication with Wired Remote Main Address Setting CN33 Blue Controller (COM2) (00~63) CN31 Communication with Outdoor Units (COM1) SW01 SW02 CN32...
  • Page 133 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 93 Damper PCB Display PCB Damper PCB Display PCB CN # COLOR FUNCTION CN # COLOR FUNCTION CN01 White Damper Switch CN01 White Panel Display II-93...
  • Page 134 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 94 Indoor Units Console 7-6. Electrical wiring diagram CN20(WHT) CN10(BLK) II-94...
  • Page 135 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 95 7-7. Sound pressure level 1) Operation sound level Microphone Unit : dB(A) Model High AVXTJH028E✴ AVXTJH036E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 136 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 96 Indoor Units Console 7-8. Temperature and air flow distribution AVXTJH036E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 36° 0.2m/s 0.8m/s 1.0m/s 0.6m/s 0.4m/s 0.2m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 36° Floor distance 3) Heating air velocity distribution ◆...
  • Page 137 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 97 Ceiling (AVXTFH✴✴✴E✴) 8-1. Features ---------------------------------------------------------------- 8-2. Specifications ---------------------------------------------------------- 8-3. Capacity tables -------------------------------------------------------- 8-4. Dimensional drawing -------------------------------------------------- 8-5. PCB connector lay-out ------------------------------------------------ 8-6. Electrical wiring diagram ---------------------------------------------- 8-7. Sound pressure level -------------------------------------------------- 8-8. Recommended operation range ------------------------------------ II-97...
  • Page 138 Under Ceiling Floor Standing Compact but powerful Samsung’s ceiling type air conditioner boasts a slim, compact design, half the size of its competitors, with cooling power comparable to competitor’s larger products. 7.1kW Model Size...
  • Page 139 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 99 8-2. Specifications 1) Technical specifications Model AVXTFH056E✴ AVXTFH071E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 HP / HR HP / HR Mode* Performance Capacity Cooling* Btu/h 19,100 24,200 Heating* Btu/h 21,400 27,200 Condensate (with High fan speed) 6.30 8.00 Liters/h...
  • Page 140 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 100 Indoor Units Ceiling 8-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB)
  • Page 141 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 101 8-4. Dimensional drawing Unit:mm Description Name 5.6kW 7.1kW Liquid pipe connection Ø6.35 Flare Ø9.52 Flare Gas pipe connection Ø12.70 Flare Ø15.88 Flare Drain pipe connection ID 18 Hose Conduit for power supply & communication wiring Air inlet grille Air outlet louver II-101...
  • Page 142 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 102 Indoor Units Ceiling 8-5. PCB connector lay-out FUNCTION CN # COLOR FUNCTION CN71 Blue AC 230V Input CN74 Yellow Drain Pump Main Address Setting CN75 Black Ventilator (00~63) CN73 White Fan Motor SW01 SW02 CN32 White DC12V for Wired Remote Controller...
  • Page 143 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 103 8-6. Electrical wiring diagram MICOM Download II-103...
  • Page 144 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 104 Indoor Units Ceiling 8-7. Sound pressure level 1) Operation sound level Unit : dB(A) Model High Microphone AVXTFH056E✴ AVXTFH071E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 145 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 105 8-8. Temperature and air flow distribution AVXTFH071E✴ (Floor installation) 1) Cooling air velocity distribution ◆ Discharge angle : 36° 0.2m/s 0.4m/s 0.6m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 36° Floor distance 3) Heating air velocity distribution ◆...
  • Page 146 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 106 Indoor Units Ceiling 8-8. Temperature and air flow distribution AVXTFH071E✴ (Ceiling installation) 1) Cooling air velocity distribution ◆ Discharge angle : 36° 1.0m/s 0.2m/s 0.4m/s 0.2m/s 0.6m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 36° Floor distance 3) Heating air velocity distribution ◆...
  • Page 147 chapter2_Indoor units(052~107) 3/14/08 22:15 Page 107 (AVXWBH✴✴✴E✴) 9-1. Features ---------------------------------------------------------------- 9-2. Specifications ---------------------------------------------------------- 9-3. Capacity tables -------------------------------------------------------- 9-4. Dimensional drawing -------------------------------------------------- 9-5. PCB connector lay-out ------------------------------------------------ 9-6. Electrical wiring diagram ---------------------------------------------- 9-7. Sound pressure level -------------------------------------------------- 9-8. Temperature and air flow distribution -------------------------------- II-107...
  • Page 148 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 108 Indoor Units 9-1. Features Auto roof shutter (2.8/3.6kW) This unique air conditioner automatically seals off to prevent dirt infiltration when not in operation. MPI (Micro Plasma Ion) The purified zone created by Micro Plasma Ion : The Micro Plasma Ion device creates intensely purified zone.With innovative technologies ,it generates 480,000 ions to purify the air.
  • Page 149 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 109 9-2. Specifications 1) Technical specifications Model AVXWBH028E✴ AVXWBH036E✴ AVXWBH056E✴ AVXWBH071E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 HP / HR HP / HR HP / HR HP / HR Mode* Performance Capacity Cooling* 9,500 12,200 19,100 23,200...
  • Page 150 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 110 Indoor Units 9-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB) Model...
  • Page 151 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 111 2) Heating TC : Total Capacity(kW) Indoor temperature (ºC, WB) Outdoor 16.0 18.0 20.0 22.0 24.0 Model temperature (ºC) II-111...
  • Page 152 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 112 Indoor Units 9-4. Dimensional drawing 1) AVXWBH028/036E✴ Unit:mm Description Name 2.8kW 3.6kW Liquid pipe connection Ø6.35 Flare Gas pipe connection Ø12.70 Flare Drain pipe connection ID 18 Hose Conduit for power supply & communication wiring Air inlet grille Air outlet louver II-112...
  • Page 153 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 113 2) AVXWBH056/071E✴ Unit:mm 1100 Description Name 5.6kW 7.1kW Liquid pipe connection Ø6.35 Flare Ø9.52 Flare Gas pipe connection Ø12.70 Flare Ø15.88 Flare Drain pipe connection ID 18 Hose Conduit for power supply & communication wiring Air inlet grille Air outlet louver II-113...
  • Page 154 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 114 Indoor Units 9-5. PCB connector lay-out Main PCB Sub PCB 12 3 Main PCB FUNCTION CN # COLOR FUNCTION CN73 White Fan Motor Main Address Setting (00~63) CN71 Blue AC 230V Input SW01 SW02 CN86 Yellow CN44...
  • Page 155 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 115 9-6. Electrical wiring diagram II-115...
  • Page 156 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 116 Indoor Units 9-7. Sound pressure level 1) Operation sound level Unit : dB(A) Model High AVXWBH028E✴ AVXWBH036E✴ AVXWBH056E✴ Microphone AVXWBH071E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 157 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 117 9-8. Temperature and air flow distribution AVXWBH036E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 60° 1.0m/s 0.8m/s 0.6m/s 1.2m/s 0.4m/s 0.4m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 60° Floor distance 3) Heating air velocity distribution ◆...
  • Page 158 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 118 Indoor Units 9-8. Temperature and air flow distribution AVXWBH071E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 60° 0.4m/s 1.2m/s 0.2m/s 0.6m/s 1.0m/s 0.8m/s 0.4m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 60° Floor distance 3) Heating air velocity distribution ◆...
  • Page 159 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 119 Neo-Forte (AVXWNH✴✴✴E✴) 10-1. Features---------------------------------------------------------------- 10-2. Specifications -------------------------------------------------------- 10-3. Capacity tables ------------------------------------------------------ 10-4. Dimensional drawing ------------------------------------------------ 10-5. PCB connector lay-out ---------------------------------------------- 10-6. Electrical wiring diagram -------------------------------------------- 10-7. Sound pressure level ------------------------------------------------ 10-8. Temperature and air flow distribution ------------------------------ II-119...
  • Page 160 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 120 Indoor Units Neo-Forte 10-1. Features Good’sleep II Innovative technology developed to control the air temperature during your sleep and maintain optimum skin temperature to enjoy a comfortable sleep and also a refreshed wake up. Catechin filter Catechin, extracted from green tea,is contained in the filter and deactivates captured bacteria and unpleasant odors.
  • Page 161 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 121 10-2. Specifications 1) Technical specifications Model AVXWNH022E✴ AVXWNH028E✴ AVXWNH036E✴ AVXWNH056E✴ AVXWNH071E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 HP / HR HP / HR HP / HR HP / HR HP / HR Mode* Performance Capacity...
  • Page 162 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 122 Indoor Units Neo-Forte 10-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB)
  • Page 163 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 123 2) Heating TC : Total Capacity(kW) Indoor temperature (ºC, WB) Outdoor 16.0 18.0 20.0 22.0 24.0 Model temperature (ºC) II-123...
  • Page 164 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 124 Indoor Units Neo-Forte 10-4. Dimensional drawing 1) AVXWNH022/028/036E✴ Unit:mm Description Name 2.2kW 2.8kW 3.6kW Liquid pipe connection Ø6.35 Flare Gas pipe connection Ø12.70 Flare Drain pipe connection ID 18 Hose Conduit for power supply & communication wiring Air inlet grille Air outlet louver II-124...
  • Page 165 chapter2_Indoor units(108~143) 3/14/08 22:37 Page 125 2) AVXWNH056/071E✴ Unit:mm Description Name 5.6kW 7.1kW Liquid pipe connection Ø6.35 Flare Ø9.52 Flare Gas pipe connection Ø12.70 Flare Ø15.88 Flare Drain pipe connection ID 18 Hose Conduit for power supply & communication wiring Air inlet grille Air outlet louver II-125...
  • Page 166 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 126 Indoor Units Neo-Forte 10-5. PCB connector lay-out Main PCB Sub PCB Main PCB FUNCTION CN # COLOR FUNCTION CN73 White Fan Motor Main Address Setting (00~63) CN71 Blue AC 230V Input SW01 SW02 CN44 Blue Hall IC CN41...
  • Page 167 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 127 10-6. Electrical wiring diagram II-127...
  • Page 168 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 128 Indoor Units Neo-Forte 10-7. Sound pressure level 1) Operation sound level Unit : dB(A) Model High AVXWNH022E✴ AVXWNH028E✴ AVXWNH036E✴ AVXWNH056E✴ Microphone AVXWNH071E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 169 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 129 10-8. Temperature and air flow distribution AVXWNH036E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 60° 1.4m/s 1.2m/s 0.2m/s 0.6m/s 1.0m/s 0.4m/s 0.2m/s 0.8m/s 0.6m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 60° Floor distance 3) Heating air velocity distribution ◆...
  • Page 170 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 130 Indoor Units Neo-Forte 10-8. Temperature and air flow distribution AVXWNH071E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 60° 1.4m/s 1.2m/s 1.0m/s 0.8m/s 0.6m/s 0.4m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 60° Floor distance 3) Heating air velocity distribution ◆...
  • Page 171 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 131 Vivace (AVXWVH✴✴✴E✴) 11-1. Features---------------------------------------------------------------- 11-2. Specifications -------------------------------------------------------- 11-3. Capacity tables ------------------------------------------------------ 11-4. Dimensional drawing ------------------------------------------------ 11-5. PCB connector lay-out ---------------------------------------------- 11-6. Electrical wiring diagram -------------------------------------------- 11-7. Sound pressure level ------------------------------------------------ 11-8. Temperature and air flow distribution ------------------------------ II-131...
  • Page 172 11-1. Features Shadow mirror By reflecting your interior on the shadow mirror, Vivace matches with your interior perfectly. The Samsung’s shadow mirror reflects adequate amount of light adding elegant image to your interior. MPI (Micro Plasma Ion) The world's first technology that generates active hydrogen atoms together with oxygen ions to improve your indoor air quality.
  • Page 173 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 133 11-2. Specifications 1) Technical specifications Model AVXWVH022E✴ AVXWVH028E✴ AVXWVH036E✴ AVXWVH056E✴ AVXWVH071E✴ Power Supply ø/V/Hz 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 1/220~240/50 HP / HR HP / HR HP / HR HP / HR HP / HR Mode* Performance Capacity...
  • Page 174 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 134 Indoor Units Vivace 11-3. Capacity tables 1) Cooling TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW) Indoor temperature (ºC, WB) Outdoor 20 (ºC, DB) 23 (ºC, DB) 26 (ºC, DB) 27 (ºC, DB) 28 (ºC, DB) 30 (ºC, DB) 32 (ºC, DB)
  • Page 175 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 135 2) Heating TC : Total Capacity(kW) Indoor temperature (ºC, WB) Outdoor 16.0 18.0 20.0 22.0 24.0 Model temperature (ºC) II-135...
  • Page 176 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 136 Indoor Units Vivace 11-4. Dimensional drawing 1) AVXWVH022/028/036E✴ Unit:mm Description Name 2.2kW 2.8kW 3.6kW Liquid pipe connection Ø6.35 Flare Gas pipe connection Ø12.70 Flare Drain pipe connection ID 18 Hose Conduit for power supply & communication wiring Air inlet grille Air outlet louver II-136...
  • Page 177 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 137 2) AVXWVH056/071E✴ Unit:mm Description Name 5.6kW 7.1kW Liquid pipe connection Ø6.35 Flare Ø9.52 Flare Gas pipe connection Ø12.70 Flare Ø15.88 Flare Drain pipe connection ID 18 Hose Conduit for power supply & communication wiring Air inlet grille Air outlet louver II-137...
  • Page 178 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 138 Indoor Units Vivace 11-5. PCB connector lay-out Main PCB Sub PCB 12 3 Main PCB FUNCTION CN # COLOR FUNCTION CN73 White Fan Motor Main Address Setting (00~63) CN71 Blue AC 230V Input SW01 SW02 CN86 Yellow...
  • Page 179 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 139 11-6. Electrical wiring diagram 16 10 II-139...
  • Page 180 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 140 Indoor Units Vivace 11-7. Sound pressure level 1) Operation sound level Unit : dB(A) Model High AVXWVH022E✴ AVXWVH028E✴ AVXWVH036E✴ AVXWVH056E✴ Microphone AVXWVH071E✴ ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 181 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 141 11-8. Temperature and air flow distribution AVXWVH036E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 60° 1.2m/s 1.0m/s 0.6m/s 0.4m/s 0.8m/s 0.2m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 60° Floor distance 3) Heating air velocity distribution ◆...
  • Page 182 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 142 Indoor Units Vivace 11-8. Temperature and air flow distribution AVXWVH071E✴ 1) Cooling air velocity distribution ◆ Discharge angle : 60° 1.4m/s 0.2m/s 1.2m/s 0.4m/s 1.0m/s 0.6m/s 0.8m/s Floor distance 2) Cooling temperature distribution ◆ Discharge angle : 60° Floor distance 3) Heating air velocity distribution ◆...
  • Page 183 chapter2_Indoor units(108~143) 3/14/08 22:38 Page 143 II-143...
  • Page 184 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 2 DVM PLUS III III-2...
  • Page 185 III. Outdoor Units DVM PLUS III, DVM PLUS III HR ..III- Mini DVM ......
  • Page 186 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 4 Outdoor Units III-4...
  • Page 187 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 5 DVM PLUS III, DVM PLUS III HR 1-1. Specifications ---------------------------------------------------------- III - 1-2. Capacity tables -------------------------------------------------------- III - 1-3. Capacity correction ---------------------------------------------------- III - 1-4. Dimensional drawing -------------------------------------------------- III - 1-5. PCB connector lay-out ------------------------------------------------...
  • Page 188 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 6 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 1) Technical specifications DVM PLUS III (1) Basic model Type Model Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVHT160GE ø/V/Hz Power Supply 3/ 380~415/ 50 3/ 380~415/ 50...
  • Page 189 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 7 (2) Compact combinations Type Model Compact Combinations 18 HP 20 HP 22 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVHT160GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 50.4...
  • Page 190 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 8 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 1) Technical specifications DVM PLUS III (2) Compact combinations Type Model Compact Combinations 24 HP 26 HP 28 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE...
  • Page 191 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 9 Type Model Compact Combinations 30 HP 32 HP 34 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVHT160GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 84.0 89.6 95.2 Btu/h...
  • Page 192 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 10 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 1) Technical specifications DVM PLUS III (2) Compact combinations Type Model Compact Combinations 36 HP 38 HP 40 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE...
  • Page 193 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 11 Type Model Compact Combinations 42 HP 44 HP 46 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVHT160GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 117.6 123.2 128.8 Btu/h...
  • Page 194 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 12 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 1) Technical specifications DVM PLUS III (2) Compact combinations Type Model Compact Combinations 48 HP 50 HP 52 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE...
  • Page 195 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 13 Type Model Compact Combinations 54 HP 56 HP 58 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVHT160GE Power Supply ø/V/Hz 3/380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 151.2 156.8 162.4 Btu/h 515,900...
  • Page 196 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 14 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 1) Technical specifications DVM PLUS III (2) Compact combinations Type Model Compact Combinations 60 HP 62 HP 64 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE...
  • Page 197 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 15 (3) High efficiency combinations Type Model High Efficiency Combinations 16 HP 18 HP 20 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE Power Supply ø/V/Hz 3/380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 44.8...
  • Page 198 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 16 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 1) Technical specifications DVM PLUS III (3) High efficiency combinations Type Model High Efficiency Combinations 22 HP 24 HP 26 HP Basic RVXVHT080GE RVXVHT100GE...
  • Page 199 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 17 Type Model High Efficiency Combinations 28 HP 30 HP 32 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 78.4 84.0 89.6 Btu/h...
  • Page 200 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 18 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 1) Technical specifications DVM PLUS III (3) High efficiency combinations Type Model High Efficiency Combinations 34 HP 36 HP 38 HP Basic RVXVHT080GE RVXVHT100GE...
  • Page 201 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 19 Type Model High Efficiency Combinations 40 HP 42 HP 44 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 112.0 117.6 123.2 Btu/h...
  • Page 202 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 20 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 1) Technical specifications DVM PLUS III (3) High efficiency combinations Type Model High Efficiency Combinations 46 HP 48 HP 50 HP Basic RVXVHT080GE RVXVHT100GE...
  • Page 203 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 21 Type Model High Efficiency Combinations 52 HP 54 HP 56 HP Basic RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 145.6 151.2 156.8 Btu/h...
  • Page 204 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 22 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 2) Technical specifications DVM PLUS III HR DVM PLUS III (1) Basic model Type Model Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE RVXVRT160GE ø/V/Hz Power Supply...
  • Page 205 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 23 (2) Compact combinations Type Model Compact 18 HP 20 HP 22 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE RVXVRT160GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 50.4 56.0...
  • Page 206 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 24 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 2) Technical specifications DVM PLUS III HR (2) Compact combinations Type Model Compact 24 HP 26 HP 28 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE...
  • Page 207 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 25 Type Model Compact 30 HP 32 HP 34 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE RVXVRT160GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 84.0 89.6 95.2 Btu/h 286,700...
  • Page 208 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 26 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 2) Technical specifications DVM PLUS III HR (2) Compact combinations Type Model Compact 36 HP 38 HP 40 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE...
  • Page 209 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 27 Type Model Compact 42 HP 44 HP 46 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE RVXVRT160GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 117.6 123.2 128.8 Btu/h 401,300...
  • Page 210 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 28 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 2) Technical specifications DVM PLUS III HR (2) Compact combinations Type Model Compact 48 HP 50 HP 52 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE...
  • Page 211 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 29 Type Model Compact 54 HP 56 HP 58 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE RVXVRT160GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 151.2 156.8 162.4 Btu/h 515,900...
  • Page 212 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 30 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 2) Technical specifications DVM PLUS III HR (2) Compact combinations Type Model Compact 60 HP 62 HP 64 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE...
  • Page 213 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 31 (3) High efficiency combinations Type Model High Efficiency 16 HP 18 HP 20 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 44.8...
  • Page 214 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 32 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 2) Technical specifications DVM PLUS III HR (3) High efficiency combinations Type Model High Efficiency 22 HP 24 HP 26 HP Basic RVXVRT080GE RVXVRT100GE...
  • Page 215 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 33 Type Model High Efficiency 28 HP 30 HP 32 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 78.4 84.0 89.6 Btu/h 267,400...
  • Page 216 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 34 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 2) Technical specifications DVM PLHRUS III HR (3) High efficiency combinations Type Model High Efficiency 34 HP 36 HP 38 HP Basic RVXVRT080GE RVXVRT100GE...
  • Page 217 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 35 Type Model High Efficiency 40 HP 42 HP 44 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 112.0 117.6 123.2 Btu/h 382,200...
  • Page 218 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 36 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-1. Specifications 2) Technical specifications DVM PLUS III HR (3) High efficiency combinations Type Model High Efficiency 46 HP 48 HP 50 HP Basic RVXVRT080GE RVXVRT100GE...
  • Page 219 3-1.DVM,HR3_Outdoor(002~037) 3/21/08 11:19 Page 37 Type Model High Efficiency 52 HP 54 HP 56 HP Basic RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE Power Supply ø/V/Hz 3/ 380~415/ 50 3/ 380~415/ 50 3/ 380~415/ 50 Mode* Performance Horse Power Capacity Cooling* 145.6 151.2 156.8 Btu/h 496,800...
  • Page 220 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 38 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (1) RVXVHT080GE / RVXVRT080GE Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 221 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 39 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 222 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 40 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (1) RVXVHT080GE / RVXVRT080GE Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC...
  • Page 223 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 41 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 16.11 4.95 15.96 5.15 15.88 5.34 15.88 5.53 15.81 5.72...
  • Page 224 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 42 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (2) RVXVHT100GE / RVXVRT100GE Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 225 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 43 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 226 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 44 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (2) RVXVHT100GE / RVXVRT100GE Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC...
  • Page 227 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 45 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 20.14 6.43 19.95 6.69 19.86 6.93 19.86 7.18 19.76 7.43...
  • Page 228 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 46 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (3) RVXVHT120GE / RVXVRT120GE Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 229 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 47 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 230 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 48 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (3) RVXVHT120GE / RVXVRT120GE Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC...
  • Page 231 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 49 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 24.17 8.72 23.94 8.82 23.83 8.93 23.83 9.04 23.71 9.15...
  • Page 232 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 50 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (4) RVXVHT140GE / RVXVRT140GE Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 233 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 51 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 234 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 52 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (4) RVXVHT140GE / RVXVRT140GE Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC...
  • Page 235 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 53 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 28.20 9.34 27.93 9.71 27.80 10.07 27.80 10.43 27.66 10.79...
  • Page 236 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 54 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (5) RVXVHT160GE / RVXVRT160GE Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 237 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 55 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 238 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 56 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 1) Basic model (5) RVXVHT160GE / RVXVRT160GE Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC...
  • Page 239 3-1.DVM,HR3_Outdoor(038~057) 3/21/08 11:18 Page 57 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 32.22 13.47 31.92 14.01 31.77 14.53 31.77 15.05 31.62 15.56...
  • Page 240 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 58 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (1) 18HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 241 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 59 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 242 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 60 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (1) 18HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 243 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 61 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 36.25 11.38 35.91 11.83 35.74 12.27 35.74 12.71 35.57 13.15...
  • Page 244 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 62 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (2) 20HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 245 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 63 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 246 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 64 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (2) 20HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 247 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 65 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 40.28 12.86 39.90 13.37 39.71 13.87 39.71 14.36 39.52 14.86...
  • Page 248 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 66 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (3) 22HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 249 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 67 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 250 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 68 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (3) 22HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 251 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 69 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 44.31 15.15 43.89 15.51 43.68 15.87 43.68 16.22 43.47 16.58...
  • Page 252 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 70 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (4) 24HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 253 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 71 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 254 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 72 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (4) 24HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 255 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 73 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 48.34 15.77 47.88 16.40 47.65 17.01 47.65 17.61 47.42 18.22...
  • Page 256 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 74 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (5) 26HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 257 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 75 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 258 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 76 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (5) 26HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 259 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 77 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 52.36 18.06 51.87 18.54 51.62 19.01 51.62 19.47 51.38 19.94...
  • Page 260 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 78 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (6) 28HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 261 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 79 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 262 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 80 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (6) 28HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 263 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 81 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 56.39 18.68 55.86 19.43 55.59 20.14 55.59 20.86 55.33 21.58...
  • Page 264 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 82 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (7) 30HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 265 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 83 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 266 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 84 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (7) 30HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 267 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 85 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 60.42 22.81 59.85 23.72 59.57 24.60 59.57 25.48 59.28 26.35...
  • Page 268 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 86 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (8) 32HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 269 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 87 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 270 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 88 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (8) 32HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 271 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 89 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 64.45 26.95 63.84 28.02 63.54 29.06 63.54 30.09 63.23 31.13...
  • Page 272 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 90 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (9) 34HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 273 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 91 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 274 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 92 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (9) 34HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 275 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 93 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 68.48 23.86 67.83 24.33 67.51 24.80 67.51 25.26 67.18 25.73...
  • Page 276 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 94 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (10) 36HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 277 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 95 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 278 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 96 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (10) 36HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 279 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 97 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 72.50 26.15 71.82 26.47 71.48 26.80 71.48 27.12 71.14 27.45...
  • Page 280 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 98 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (11) 38HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 281 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 99 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 282 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 100 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (11) 38HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 283 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 101 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 76.53 26.77 75.81 27.36 75.45 27.94 75.45 28.51 75.09 29.09...
  • Page 284 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 102 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (12) 40HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 285 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 103 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 286 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 104 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (12) 40HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 287 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 105 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 80.56 30.91 79.80 31.66 79.42 32.39 79.42 33.13 79.04 33.86...
  • Page 288 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 106 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (13) 42HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 289 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 107 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 290 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 108 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (13) 42HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 291 3-1.DVM,HR3_Outdoor(058~109) 3/21/08 11:16 Page 109 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 84.59 31.53 83.79 32.55 83.39 33.53 83.39 34.52 82.99 35.51...
  • Page 292 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 110 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (14) 44HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 293 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 111 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 294 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 112 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (14) 44HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 295 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 113 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 88.62 32.15 87.78 33.44 87.36 34.67 87.36 35.91 86.94 37.15...
  • Page 296 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 114 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (15) 46HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 297 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 115 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 298 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 116 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (15) 46HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 299 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 117 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 92.64 36.29 91.77 37.73 91.33 39.13 91.33 40.52 90.90 41.92...
  • Page 300 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 118 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (16) 48HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 301 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 119 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 302 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 120 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (16) 48HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 303 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 121 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 96.67 40.42 95.76 42.03 95.30 43.58 95.30 45.14 94.85 46.69...
  • Page 304 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 122 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (17) 50HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 305 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 123 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 306 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 124 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (17) 50HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 307 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 125 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 100.70 35.49 99.75 36.18 99.28 36.87 99.28 37.55 98.80 38.24...
  • Page 308 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 126 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (18) 52HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 309 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 127 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 310 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 128 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (18) 52HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 311 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 129 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 104.73 39.62 103.74 40.48 103.25 41.33 103.25 42.17 102.75 43.01...
  • Page 312 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 130 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (19) 54HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 313 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 131 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 314 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 132 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (19) 54HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 315 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 133 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 108.76 42.09 107.73 43.53 107.22 44.92 107.22 46.31 106.70 47.71...
  • Page 316 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 134 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (20) 56HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 317 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 135 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 318 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 136 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (20) 56HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 319 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 137 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 112.78 42.72 111.72 44.42 111.19 46.06 111.19 47.71 110.66 49.35...
  • Page 320 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 138 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (21) 58HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 321 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 139 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 322 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 140 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (21) 58HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 323 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 141 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 116.81 46.85 115.71 48.72 115.16 50.52 115.16 52.32 114.61 54.12...
  • Page 324 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 142 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (22) 60HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 325 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 143 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 326 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 144 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (22) 60HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 327 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 145 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 120.84 49.13 119.70 50.85 119.13 52.52 119.13 54.18 118.56 55.84...
  • Page 328 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 146 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (23) 62HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 329 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 147 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 330 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 148 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (23) 62HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 331 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 149 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 124.87 49.76 123.69 51.74 123.10 53.66 123.10 55.57 122.51 57.48...
  • Page 332 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 150 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (24) 64HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB)
  • Page 333 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 151 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor tempera- 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ture( º...
  • Page 334 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 152 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 2) Compact combinations (24) 64HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC...
  • Page 335 3-1.DVM,HR3_Outdoor(110~153) 3/21/08 11:15 Page 153 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 128.90 53.89 127.68 56.04 127.07 58.11 127.07 60.18 126.46 62.26...
  • Page 336 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 154 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (1) 16HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 337 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 155 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 338 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 156 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (1) 16HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 339 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 157 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 32.22 9.90 31.92 10.29 31.77 10.67 31.77 11.05 31.62 11.43...
  • Page 340 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 158 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (2) 18HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 341 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 159 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 342 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 160 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (2) 18HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 343 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 161 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 36.25 11.38 35.91 11.83 35.74 12.27 35.74 12.71 35.57 13.15...
  • Page 344 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 162 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (3) 20HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 345 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 163 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 346 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 164 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (3) 20HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 347 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 165 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 40.28 12.86 39.90 13.37 39.71 13.87 39.71 14.36 39.52 14.86...
  • Page 348 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 166 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (4) 22HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 349 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 167 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 350 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 168 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (4) 22HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 351 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 169 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 44.31 15.15 43.89 15.51 43.68 15.87 43.68 16.22 43.47 16.58...
  • Page 352 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 170 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (5) 24HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 353 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 171 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 354 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 172 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (5) 24HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 355 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 173 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 48.34 14.85 47.88 15.44 47.65 16.01 47.65 16.58 47.42 17.15...
  • Page 356 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 174 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (6) 26HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 357 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 175 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 358 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 176 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (6) 26HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 359 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 177 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 52.36 16.33 51.87 16.98 51.62 17.61 51.62 18.24 51.38 18.86...
  • Page 360 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 178 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (7) 28HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 361 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 179 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 362 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 180 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (7) 28HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 363 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 181 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 56.39 17.81 55.86 18.52 55.59 19.21 55.59 19.89 55.33 20.58...
  • Page 364 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 182 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (8) 30HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 365 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 183 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 366 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 184 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (8) 30HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 367 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 185 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 60.42 19.29 59.85 20.06 59.57 20.80 59.57 21.55 59.28 22.29...
  • Page 368 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 186 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (9) 32HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 369 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 187 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 370 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 188 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (9) 32HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 371 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 189 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 64.45 21.58 63.84 22.20 63.54 22.80 63.54 23.40 63.23 24.01...
  • Page 372 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 190 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (10) 34HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 373 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 191 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 374 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 192 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (10) 34HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 375 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 193 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 68.48 22.20 67.83 23.09 67.51 23.94 67.51 24.80 67.18 25.65...
  • Page 376 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 194 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (11) 36HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 377 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 195 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 378 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 196 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (11) 36HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 379 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 197 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 72.50 24.49 71.82 25.22 71.48 25.94 71.48 26.65 71.14 27.37...
  • Page 380 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 198 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (12) 38HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 381 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 199 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 382 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 200 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (12) 38HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 383 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 201 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 76.53 25.11 75.81 26.11 75.45 27.08 75.45 28.05 75.09 29.01...
  • Page 384 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 202 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (13) 40HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 385 3-1.DVM,HR3_Outdoor(154~203) 3/21/08 11:14 Page 203 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 386 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 204 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (13) 40HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 387 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 205 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 80.56 27.40 79.80 28.25 79.42 29.08 79.42 29.90 79.04 30.73...
  • Page 388 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 206 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (14) 42HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 389 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 207 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 390 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 208 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (14) 42HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 391 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 209 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 84.59 28.02 83.79 29.14 83.39 30.22 83.39 31.30 82.99 32.37...
  • Page 392 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 210 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (15) 44HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 393 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 211 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 394 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 212 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (15) 44HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 395 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 213 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 88.62 28.63 87.78 29.77 87.36 30.88 87.36 31.98 86.94 33.08...
  • Page 396 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 214 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (16) 46HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 397 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 215 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 398 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 216 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (16) 46HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 399 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 217 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 92.64 30.92 91.77 31.91 91.33 32.87 91.33 33.84 90.90 34.80...
  • Page 400 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 218 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (17) 48HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 401 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 219 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 402 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 220 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (17) 48HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 403 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 221 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 96.67 31.54 95.76 32.80 95.30 34.01 95.30 35.23 94.85 36.44...
  • Page 404 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 222 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (18) 50HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 405 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 223 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 406 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 224 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (18) 50HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 407 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 225 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 100.70 33.83 99.75 34.94 99.28 36.01 99.28 37.09 98.80 38.16...
  • Page 408 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 226 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (19) 52HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 409 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 227 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 410 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 228 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (19) 52HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 411 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 229 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 104.73 36.11 103.74 37.07 103.25 38.01 103.25 38.94 102.75 39.88...
  • Page 412 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 230 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (20) 54HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 413 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 231 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 414 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 232 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (20) 54HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 415 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 233 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 108.76 36.74 107.73 37.96 107.22 39.15 107.22 40.33 106.70 41.52...
  • Page 416 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 234 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (21) 56HP(Heat Pump / Heat Recovery) Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 417 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 235 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) temperature( º...
  • Page 418 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 236 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-2. Capacity tables 3) High efficiency combinations (21) 56HP(Heat Pump / Heat Recovery) Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB)
  • Page 419 3-1.DVM,HR3_Outdoor(204~237) 3/21/08 11:13 Page 237 TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 112.78 37.36 111.72 38.85 111.19 40.29 111.19 41.73 110.66 43.16...
  • Page 420 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 238 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 1) 8HP Cooling 98.6% 90.9% 92.1% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 421 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 239 2) 10HP Cooling 85.7% 95.4% 85% 83.8% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 92.8% 97.7% 91.9% Main pipe size-up 100% 0 10...
  • Page 422 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 240 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 3) 12HP Cooling 91.7% 97.7% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 423 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 241 4) 14HP Cooling 87.3% 95.4% 85% 83.8% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 94%93.7% 97.5% 92% 91.8% Main pipe size-up 100% 0 10...
  • Page 424 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 242 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 5) 16HP Cooling 92.8% 97.6% 88.8% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 425 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 243 6) 18HP Cooling 89.9% 100 % 95% 84.9% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 94.9% 97.8% 92.4% Main pipe size-up 100% 0 10...
  • Page 426 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 244 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 7) 20HP Cooling 86.7% 80.6% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 427 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 245 8) 22HP Cooling 85% 83.2% 91.9% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 91.6% 95.9% Main pipe size-up 100% 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 428 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 246 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 9) 24HP Cooling 80% 79.4% 89.6% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 429 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 247 10) 26HP Cooling 87.2% 97.5% 88.5% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 94% 93.6% 98.7% 94.3% Main pipe size-up 100% 0 10...
  • Page 430 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 248 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 11) 28HP Cooling 84.6% 96.4% 86.1% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 431 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 249 12) 30HP Cooling 81.9% 95.3%95% 85% 83.6% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 94% 93% 92% 91% 99.2% 95.4% Main pipe size-up...
  • Page 432 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 250 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 13) 32HP Cooling 80%79% 94.1% 80.9% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 433 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 251 14) 34HP Cooling 92.8% 78.1% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 97.1% 96.5% 89.1% Main pipe size-up 100% 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 434 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 252 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 15) 36HP Cooling 91.5% 98.3% 90.3% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 435 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 253 16) 38HP Cooling 90.1% 97.7% 88.9% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 95.8% 98.9% 94.5% Main pipe size-up 100% 0 10 100 90...
  • Page 436 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 254 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 17) 40HP Cooling 90 % 88 . 6% 100 % 95 % 87.2 % 95 % Main pipe size-up 100% 0 10 100 90...
  • Page 437 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 255 18) 42HP Cooling 88.1% 96.2% 85.6% Main pipe size-up 100% 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 94% 93.5% 98.1% 93% 92.9% Main pipe size-up 100% 0 10...
  • Page 438 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 256 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 19) 44HP Cooling 85.8% 95.4% 85% 83.8% Main pipe size-up 100% 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 439 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 257 20) 46HP Cooling 85% 83.9% 94.6% 82.1% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 97.3% 97% 91.1% Main pipe size-up 100% 0 10...
  • Page 440 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 258 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 21) 48HP Cooling 83.9% 93.8% 80.2% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 441 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 259 22) 50HP Cooling 85% 84.1% 96.7% 80%79.3% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 96.5% 99.3% 99% 95.4% Main pipe size-up 100% 0 10...
  • Page 442 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 260 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 23) 52HP Cooling 85% 84.1% 96.7% 80%79.3% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 443 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 261 24) 54HP Cooling 82.1% 95.7% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 95% 94.9% Main pipe size-up 100% 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m)
  • Page 444 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 262 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 25) 56HP Cooling 82.1% 95.7% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 445 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 263 26) 58HP Cooling 80.1% 94.6% 75% 74.5% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 96% 95.6% 98.7% 94.2% Main pipe size-up 100% 0 10...
  • Page 446 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 264 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 27) 60HP Cooling 80.1% 94.6% 75% 74.5% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 447 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 265 28) 62HP Cooling 80% 77.9% 93.5% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200 Pipe length(m) Heating 95.1% 98.5% 94% 93.8% Main pipe size-up 100% 0 10...
  • Page 448 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 266 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-3. Capacity correction 29) 64HP Cooling 80% 77.9% 93.5% Main pipe size-up 100 % 0 10 100 90 100 110 120 130 140 150 160 170 180 190 200...
  • Page 449 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 267 1-4. Dimensional drawing 1) RVXVHT080/100/120GE RVXVRT080/100/120GE Unit:mm Center of Gravity (Pitch of the foundation bolt holes) 14 15 Name Description Gas pipe connection Ø57.10, 1m knock-out hole High pressure gas pipe connection Ø57.10, 1m knock-out hole Liquid pipe connection Ø37.10, 1m knock-out hole Oil balance pipe connection between units...
  • Page 450 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 268 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-4. Dimensional drawing 2) RVXVHT140/160GE RVXVRT140/160GE Unit:mm Center of Gravity (Pitch of the foundation bolt holes) 14 15 Name Description Gas pipe connection Ø57.10, 1m knock-out hole High pressure gas pipe connection Ø57.10, 1m knock-out hole...
  • Page 451 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 269 1-5. PCB connector lay-out 1) Main PCB CN # COLOR FUNCTION CN # COLOR FUNCTION CN901 Power Trans Out (AC 17V) CN74 Hot gas Bypass Valve CN13 Black 5V for Interface Module CN71 White PWM Valve CN31 Communi c ati o n wi t h I n door Uni t s (COM1)
  • Page 452 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 270 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-5. PCB connector lay-out 2) BLDC Driver PCB CN # COLOR FUNCTION CN701 Blue AC 230V Input White Power Trans In (AC 230V) CN703 Black AC 230V Output...
  • Page 453 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 271 1-6. Electrical wiring diagram 33 34 Unit option MAIN unit SUB 1 unit SUB 2 unit SUB 3 unit III-271...
  • Page 454 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 272 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-7. Sound pressure level 1) Operation sound level Unit : dB(A) Model High Microphone RVXVHT080GE RVXVRT080GE RVXVHT100GE RVXVRT100GE RVXVHT120GE RVXVRT120GE RVXVHT140GE RVXVRT140GE Front RVXVHT160GE RVXVRT160GE ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 455 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 273 Heat Recovery (5) RVXVHT160GE (1) RVXVRT080GE Octave band center frequency(Hz) Octave band center frequency(Hz) (2) RVXVRT100GE (3) RVXVRT120GE Octave band center frequency(Hz) Octave band center frequency(Hz) (4) RVXVRT140GE (5) RVXVRT160GE Octave band center frequency(Hz) Octave band center frequency(Hz) III-273...
  • Page 456 3-1.DVM,HR3_Outdoor(238~293) 3/21/08 11:21 Page 274 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-8. Operation limit 1) Cooling 2) Heating Range for continuous operation Indoor temperature(ºCWB) Indoor temperature(ºCDB) 1-9. Cycle operation mode 1) Description of cycle function parts No Classification...
  • Page 457 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 275 No Classification Description No Classification Description Crank case heater of DVI compressor HR EEV Crank case heater of FVI compressor 1 HR EEV check valve Crank case heater of FVI compressor 2 High pressure gas service valve in HR/MCU unit Low pressure gas service valve in HP unit (Heat Pump) Sump(Base) temperature sensor Oil temperature sensor...
  • Page 458 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 276 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-9. Cycle operation mode 2) Cycle diagrams (1) RVXVHT080/100/120EE (DVM PLUS III - 8/10/12 HP) III-276...
  • Page 459 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 277 (2) RVXVHT140/160EE (DVM PLUS -14/16 HP) III-277...
  • Page 460 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 278 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-9. Cycle operation mode 2) Cycle diagrams (3) RVXVRT080/100/120EE (DVM PLUS HR - 8/10/12 HP) III-278...
  • Page 461 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 279 (4) RVXVRT140/160EE (DVM PLUS HR-14/16 HP) III-279...
  • Page 462 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 280 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-9. Cycle operation mode 2) Cycle diagrams (5) MCU’s MCU-4EAE1 MCU-4EAEV1 MCU-6EAE1 III-280...
  • Page 463 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 281 (6) EEV kits & Indoor units MXD series MEV series ➊ ❷ ➊ 2 rooms 3 rooms Single room Indoor units ➊ ❷ Indoor units with built-in EEV Indoor units without EEV (Wall mount & Ceiling units) III-281...
  • Page 464 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 282 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-9. Cycle operation mode 3) DVM PLUS III (Heat Pump) (1) Cooling operation Unit Outdoor unit Indoor unit Outdoor unit Cooling operation 1 2 3 4...
  • Page 465 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 283 (2) Heating operation Unit Outdoor unit Indoor unit Outdoor unit Cooling operation Heating operation 5 6 7 8 III-283...
  • Page 466 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 284 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-9. Cycle operation mode 4) DVM PLUS III HR (Heat Recovery) (1) Cooling operation Unit Outdoor unit Indoor unit Outdoor unit Cooling operation 1 2 3...
  • Page 467 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 285 (2) HR operation (Main cooling) Unit Outdoor unit Indoor unit Outdoor unit Cooling operation 1 2 3 Heating operation 1 A B III-285...
  • Page 468 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 286 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-9. Cycle operation mode 4) DVM PLUS III HR (3) Heating operation Unit Outdoor unit Indoor unit Outdoor unit Cooling operation Heating operation 7 8 9 10 11...
  • Page 469 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 287 (4) HR operation (Main heating) Unit Outdoor unit Indoor unit Outdoor unit Cooling operation D 11 Heating operation 8 9 10 11 III-287...
  • Page 470 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 288 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-10. Cycle function parts 1) RVXVHT080GE / RVXVHT100GE / RVXVHT120GE Accumulator Low pressure sensor Oil separator PWM valve DVI compressor FVI compressor 1 Ambient air temp. sensor...
  • Page 471 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 289 2) RVXVHT140GE / RVXVHT160GE Accumulator Low pressure sensor Oil separator PWM valve DVI compressor FVI compressor 1 FVI compressor 2 Ambient air temp. sensor Liquid tube sensor High pressure sensor Turbo intercooler Hot gas bypass valve Suction temp.
  • Page 472 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:02 Page 290 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-10. Cycle function parts 3) RVXVRT080GE / RVXRT100GE / RVXVRT120GE Accumulator Low pressure sensor Oil separator PWM valve DVI compressor FVI compressor 1 Ambient air temp. sensor...
  • Page 473 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:03 Page 291 4) RVXVRT140GE / RVXVRT160GE Accumulator Oil separator PWM valve DVI compressor FVI compressor 1 FVI compressor 2 Ambient air temp. sensor Liquid tube sensor HR EEV High pressure sensor Main cooling valve Turbo intercooler Hot gas bypass valve 4way valve Suction temp.
  • Page 474 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:03 Page 292 Outdoor Units DVM PLUS III, DVM PLUS III HR 1-10. Cycle function parts 5) A description of cycle function parts Cycle parts Functions DVI compressor coupled with vapor injection controls the capacity 10 to 100% of its capacity.
  • Page 475 3-1.DVM,HR3_Outdoor(238~293) 3/15/08 1:03 Page 293 Mini DVM 2-1. Specifications ---------------------------------------------------------- III - 2-2. Capacity tables -------------------------------------------------------- III - 2-3. Capacity correction ---------------------------------------------------- III - 2-4. Dimensional drawing -------------------------------------------------- III - 2-5. PCB connector lay-out ------------------------------------------------ III - III - 2-6. Electrical wiring diagram ---------------------------------------------- III - 2-7.
  • Page 476 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 294 Outdoor Units Mini DVM 2-1. Specifications Type Model RVXMHF040EA RVXMHF050EA RVXMHF050GA RVXMHF060GA ø/V/Hz Power Supply 1/220~240/50 1/220~240/50 3/380~415/50 3/380~415/50 Mode* Performance Horse Power Capacity Cooling* 12.5 14.0 14.0 16.0 Btu/h 42,700 47,800 47,800 54,600 Heating* 14.5 16.0...
  • Page 477 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 295 2-2. Capacity tables 1) 4HP Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor temperature 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index)
  • Page 478 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 296 Outdoor Units Mini DVM 2-2. Capacity tables 1) 4HP Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor temperature 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB)
  • Page 479 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 297 1) 4HP Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 10.0 10.5 10.3 10.1 11.0 10.8...
  • Page 480 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 298 Outdoor Units Mini DVM 2-2. Capacity tables 1) 4HP Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 10.1...
  • Page 481 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 299 2) 5HP Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor temperature 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ( º...
  • Page 482 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 300 Outdoor Units Mini DVM 2-2. Capacity tables 2) 5HP Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor temperature 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB)
  • Page 483 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 301 2) 5HP Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 11.0 10.7 10.4 10.1 10.6 11.6...
  • Page 484 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 302 Outdoor Units Mini DVM 2-2. Capacity tables 2) 5HP Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 10.2...
  • Page 485 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 303 3) 6HP Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor temperature 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB) 24 (ºC, WB) (Capacity index) ( º...
  • Page 486 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 304 Outdoor Units Mini DVM 2-2. Capacity tables 3) 6HP Cooling TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Combination% Outdoor temperature 14 (ºC, WB) 16 (ºC, WB) 18 (ºC, WB) 19 (ºC, WB) 20 (ºC, WB) 22 (ºC, WB)
  • Page 487 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 305 3) 6HP Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 12.4 12.1 11.7 11.4 11.1 12.0...
  • Page 488 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 306 Outdoor Units Mini DVM 2-2. Capacity tables 2) 6HP Heating TC : Total Capacity, PI : Power Input Indoor temperature (ºC, WB) Outdoor Combination% 16.0 ºC 18.0 ºC 20.0 ºC 22.0 ºC 24.0 ºC temperature (ºC) (Capacity index) 11.4...
  • Page 489 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 307 2-3. Capacity correction 1) 4HP Cooling Pipe length(m) Heating Pipe length(m) III-307...
  • Page 490 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 308 Outdoor Units Mini DVM 2-3. Capacity correction 2) 5HP Cooling Pipe length(m) Heating Pipe length(m) III-308...
  • Page 491 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 309 3) 6HP Cooling Pipe length(m) Heating Pipe length(m) III-309...
  • Page 492 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 310 Outdoor Units Mini DVM 2-4. Dimensional diagram Unit:mm Name Description Gas pipe connection Ø9.52(4/5/6HP) Liquid pipe connection Ø15.88(4/5HP), Ø19.05(6HP) Condesate drain hole Ø20 Power&Communication wiring conduit Ø27.8x6 III-310...
  • Page 493 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 311 2-5. PCB connector lay-out CN # COLOR FUNCTION CN # COLOR FUNCTION CN48 Sump Sensor CN77 Black Compressor Control CN62 Blue CN71 White PWM Valve OPT1 White Mode Selector (Cooling/Heating) CN73 Yellow 4way Valve CN11 Trans Out (AC 17V) CN81...
  • Page 494 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 312 Outdoor Units Mini DVM 2-6. Electrical wiring diagram 1) RVXMHF040EA MICOM Download CN91(WHT) OPT1(WHT) III-312...
  • Page 495 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 313 2) RVXMHF050EA MICOM Download CN91(WHT) OPT1(WHT) III-313...
  • Page 496 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 314 Outdoor Units Mini DVM 2-6. Electrical wiring diagram 3) RVXMHF050G✴/RVXMHF060G✴ MICOM Download CN91(WHT) OPT1(WHT) III-314...
  • Page 497 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 315 2-7. Sound pressure level 1) Operation sound level Model dB(A) 1.5m 4 HP 5 HP 6 HP ◆ These operation values were obtained in a dead room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed.
  • Page 498 3-2.mini_Outdoor unit(294~321) 3/21/08 11:22 Page 316 Outdoor Units Mini DVM 2-8. Operation limit 1) Cooling 2) Heating Range for continuous operation Indoor temperature(ºCWB) Indoor temperature(ºCDB) ◆ On heating operation, frost can be formed on heat exchanger according to outdoor temperature. (Frost on heat exchanger results in decreasing the performance.) To remove frost on heat exchanger of outdoor unit, defrost operation is carried out periodically.
  • Page 499 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 317 2-9. Cycle operation mode 1) Description of cycle function parts No Classification Description No Classification Description Digital scroll compressor Capillary tube PWM solenoid valve Accumulator Hot gas bypass solenoid valve Receiver Reversing solenoid valve (4 way valve) Discharge temperature sensor Liquid bypass solenoid valve Sump sensor...
  • Page 500 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 318 Outdoor Units Mini DVM 2-9. Cycle operation mode 2) Cycle diagrams (1) RVXMHF040/050/060✴✴ (Mini DVM - 4/5/6 HP) III-318...
  • Page 501 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 319 (2) Cooling operation Unit Outdoor unit Indoor unit Outdoor unit Cooling operation 1 2 3 4 5 Heating operation III-319...
  • Page 502 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 320 Outdoor Units Mini DVM 2-9. Cycle operation mode 2) Cycle diagrams (3) Heating operation Unit Outdoor unit Indoor unit Outdoor unit Cooling operation Heating operation 5 6 7 8 9 10 III-320...
  • Page 503 3-2.mini_Outdoor unit(294~321) 3/15/08 4:06 Page 321 2-10. Cycle function parts 1) RVXMHF040/050/060✴✴ Ambient air temp. sensor 2) Description of cycle function parts Cycle parts Functions Digital scroll compressor Digital scroll compressor controls the capacities 10 to 100% of its capacity. It is used for variation of Digital compressor's capacity.
  • Page 504 4.Accessories(02~31) 3/6/08 13:59 Page 2 DVM PLUS III IV-2...
  • Page 505 4.Accessories(02~31) 3/6/08 13:59 Page 3 Accessories Panels & Drain pumps ....Branch joints ..... . . MCU kits .
  • Page 506 4.Accessories(02~31) 3/6/08 13:59 Page 4 Accessories IV-4...
  • Page 507 4.Accessories(02~31) 3/6/08 13:59 Page 5 Panels & Drain pumps 1-1. Panels-------------------------------------------------------------------- 1-2. Drain pumps ------------------------------------------------------------ IV-5...
  • Page 508 4.Accessories(02~31) 3/6/08 13:59 Page 6 Accessories Panels & Drain pumps 1-1. Panels 1) Models Model name Description PSSMA Slim 1 way cassette panel P2SMA 2 way cassette panel P4SMA 4 way cassette panel PMSMA Mini 4 way cassette panel 2) Dimensional drawing PSSMA P2SMA P4SMA...
  • Page 509 4.Accessories(02~31) 3/6/08 13:59 Page 7 Branch joints 2-1. Y-joints ------------------------------------------------------------------ 2-2. Y-joints (HR only)-------------------------------------------------------- 2-3. Header joints------------------------------------------------------------ 2-4. Outdoor joints ---------------------------------------------------------- 2-5. Outdoor joints (HR only) ---------------------------------------------- IV-7...
  • Page 510 4.Accessories(02~31) 3/6/08 13:59 Page 8 Accessories Branch joints 2-1. Y-joints 1) Models Model name Total indoor unit’s capacities MXJ-YA1509✴ 15.0 kW and below MXJ-YA2512✴ Over 15.0~40.6 kW and below MXJ-YA2812✴ Over 40.6~46.4 kW and below MXJ-YA2815✴ Over 46.4~69.6 kW and below MXJ-YA3119✴...
  • Page 511 4.Accessories(02~31) 3/6/08 13:59 Page 9 Y-joint for indoor unit ✴ MXJ-YA3119 Liquid x 1 EA x 2 EA x 1 EA ✴ MXJ-YA3819 Liquid x 1 EA x 1 EA x 2 EA x 1 EA ✴ MXJ-YA4422 Liquid x 1 EA x 1 EA x 1 EA x 2 EA...
  • Page 512 4.Accessories(02~31) 3/6/08 13:59 Page 10 Accessories Branch joints 2-2. Y-joints HR Only 1) Models Model name Total indoor unit’s capacities MXJ-YA1500✴ 23.2 kW and below MXJ-YA2500✴ Over 23.2~69.6 kW and below MXJ-YA3100✴ Over 69.6~139.2 kW and below MXJ-YA3800✴ Over 139.2 kW 2) Dimensional drawing Y-joint for HR (High pressure gas) ✴...
  • Page 513 4.Accessories(02~31) 3/6/08 13:59 Page 11 2-3. Header joints 1) Models Model name Total indoor unit’s capacities The maximum quantity of connection MXJ-HA2512✴ 46.4 kW and below MXJ-HA3115✴ 69.6 kW and below MXJ-HA3819✴ Over 69.6 kW 2) Dimensional drawing Header joint ✴...
  • Page 514 4.Accessories(02~31) 3/6/08 13:59 Page 12 Accessories Branch joints 2-4. Outdoor joints 1) Models Model name Total indoor unit’s capacities MXJ-T3819✴ Below 48 HP MXJ-T4422✴ Above 50 HP 2) Dimensional drawing Outdoor joint ✴ MXJ-T3819 Liquid x 1 EA x 2 EA x 2 EA ✴...
  • Page 515 4.Accessories(02~31) 3/6/08 13:59 Page 13 2-5. Outdoor joints HR Only (For High pressure gas pipe connection) 1) Models Model name Total indoor unit’s capacities MXJ-T3100✳ Below 48 HP MXJ-T3800✳ Above 50 HP 2) Dimensional drawing Outdoor joint ✳ ✳ MXJ-T3100 MXJ-T3800 High pressure gas High pressure gas...
  • Page 516 4.Accessories(02~31) 3/6/08 13:59 Page 14 Accessories IV-14...
  • Page 517 4.Accessories(02~31) 3/6/08 13:59 Page 15 MCU kits 3-1. Models ------------------------------------------------------------------ 3-2. Cycle function parts---------------------------------------------------- 3-3. Dimensional drawing -------------------------------------------------- 3-4. PCB connector lay-out ------------------------------------------------ 3-5. Electrical wiring diagram ---------------------------------------------- IV-15...
  • Page 518 4.Accessories(02~31) 3/6/08 13:59 Page 16 Accessories MCU kits 3-1. Models Description Model Quantity of connectable indoor units Weight (Net) Total capacity MCU-4EAE1 Up to 4 units 24kg Up to 44.8kW (16HP) Not included MCU-6EAE1 Up to 6 units 27kg Description Model Quantity of connectable indoor units Weight (Net)
  • Page 519 4.Accessories(02~31) 3/6/08 13:59 Page 17 3) MCU-4EAEV1 Heating solenoid valve Cooling solenoid valve MCU liquid bypass valve Gas pipe connection (Outdoor unit) High pressure gas pipe connection (Outdoor unit) Drain pipe Liquid pipe connection (Outdoor unit) Outdoor unit EEV bypass valve MCU EEV MCU main heating valve Liquid pipe...
  • Page 520 4.Accessories(02~31) 3/6/08 13:59 Page 18 Accessories MCU kits 3-3. Dimensional drawing 1) MCU-4EAE1 Unit:mm Name Liquid pipe connection from outdoor unit (Ø12.70, Flare) High pressure gas pipe connection from outdoor unit (Ø19.05, Brazing) Gas pipe connection from outdoor unit (Ø28.58, Flange) Liquid pipe connection to indoor units Gas pipe connection to indoor units Condensate drain pipe connection (ID 22.5/OD 26.5)
  • Page 521 4.Accessories(02~31) 3/6/08 13:59 Page 19 2) MCU-6EAE1 Unit:mm Name Liquid pipe connection from outdoor unit (Ø12.70, Flare) High pressure gas pipe connection from outdoor unit (Ø19.05, Brazing) Gas pipe connection from outdoor unit (Ø28.58, Flange) Liquid pipe connection to indoor units Gas pipe connection to indoor units Condensate drain pipe connection (ID 22.5/OD 26.5) Power and communication wiring conduits...
  • Page 522 4.Accessories(02~31) 3/6/08 13:59 Page 20 Accessories MCU kits 3) MCU-4EAEV1 Unit:mm Name Liquid pipe connection from outdoor unit (Ø12.70, Flare) High pressure gas pipe connection from outdoor unit (Ø19.05, Brazing) Gas pipe connection from outdoor unit (Ø28.58, Flange) Liquid pipe connection to indoor units Gas pipe connection to indoor units EEV Bypass valve Condensate drain pipe connection (ID 22.5/OD 26.5)
  • Page 523 4.Accessories(02~31) 3/6/08 13:59 Page 21 3-4. PCB connector lay-out CN # COLOR FUNCTION CN # COLOR FUNCTION CN71 Blue AC 230V Input CN62 Blue Main EEV CN72 Yellow Port A/B Cooling/Heating Solenoid Valve CN63 White EEV1 CN73 White Port C/D Cooling/Heating Solenoid Valve CN84 Black EEV2...
  • Page 524 4.Accessories(02~31) 3/6/08 13:59 Page 22 Accessories MCU kits 3-5. Electrical wiring diagram HIGH PRESSURE SENSOR AC 230V AC 230V AC 230V AC 230V IV-22...
  • Page 525 4.Accessories(02~31) 3/6/08 13:59 Page 23 EEV kits 4-1. Models ------------------------------------------------------------------ 4-2. Cycle function parts---------------------------------------------------- 4-3. Dimensional drawing -------------------------------------------------- 4-4. PCB connector lay-out ------------------------------------------------ 4-5. Electrical wiring diagram ---------------------------------------------- IV-23...
  • Page 526 4.Accessories(02~31) 3/6/08 13:59 Page 24 Accessories EEV kits 4-1. Models 1) Single EEV kits Description Connectable capacity of Quantity of connectable Model Weight (Net) Indoor units Remarks indoor units indoor units MEV-A13SA up to 3.6kW units Wall mounted units Extension MEV-A16SA 5.6 ~ 9.0kW units Ceiling units...
  • Page 527 4.Accessories(02~31) 3/6/08 13:59 Page 25 4-2. Cycle function parts 1) Single EEV kits EEV connector Liquid pipe connection to indoor unit Liquid pipe connection from outdoor unit 2) Two rooms EEV kits Liquid pipe connection EEVs Gas pipe connection Liquid pipe connection Indoor unit (Ceiling, wall mounted)
  • Page 528 4.Accessories(02~31) 3/6/08 13:59 Page 26 Accessories EEV kits 4-3. Dimensional drawing 1) Single EEV kits Unit:mm Name Liquid pipe connection from branch joint (Ø6.35, Flare) Liquid pipe connection to wall mounted/ceiling unit (Ø6.35, Flare) IV-26...
  • Page 529 4.Accessories(02~31) 3/6/08 13:59 Page 27 2) Two rooms EEV kits Unit:mm Name Pipe size (Ø, mm) Model Liquid pipe connection from branch joint MXD- MXD- MXD- MXD- A13K116A A13K200A A16K200A A22K200A Gas pipe connection from branch joint Liquid pipe connections to wall mounted/ceiling units 9.52 9.52 9.52...
  • Page 530 4.Accessories(02~31) 3/6/08 13:59 Page 28 Accessories EEV kits 3) Three rooms EEV kits Unit:mm Name Pipe size (Ø, mm) Model Liquid pipe connection from branch joint MXD- MXD- MXD- MXD- A13K216A A13K300A A16K213A A16K300A Gas pipe connection from branch joint Liquid pipe connections to wall mounted/ceiling units 9.52 9.52...
  • Page 531 4.Accessories(02~31) 3/6/08 13:59 Page 29 4-4. PCB connector lay-out CN # COLOR FUNCTION CN # COLOR FUNCTION CN31 Communication with Outdoor Unit CN62 Blue EEV B CN71 Blue AC 230V Input CN63 White EEV C CN61 Yellow EEV A CN91 White MICOM Download IV-29...
  • Page 532 4.Accessories(02~31) 3/6/08 13:59 Page 30 Accessories EEV kits 4-5. Electrical wiring diagram IV-30...
  • Page 533 4.Accessories(02~31) 3/6/08 13:59 Page 31 IV-31...
  • Page 534 05-1_control systems(002~045) 3/15/08 4:09 Page 2 DVM PLUS III...
  • Page 535 05-1_control systems(002~045) 3/15/08 4:09 Page 3 Control Systems Individual control system ....Centralized control system ... . Integrated management system .
  • Page 536 05-1_control systems(002~045) 3/15/08 4:09 Page 4 Control Systems...
  • Page 537 05-1_control systems(002~045) 3/15/08 4:09 Page 5 Individual control system 1-1. Wireless signal receiver kit -------------------------------------------- 1-2. Wireless remote controller -------------------------------------------- 1-3. Wired remote controller------------------------------------------------ 1-4. 7-day scheduler (MWR-BS00) --------------------------------------...
  • Page 538 05-1_control systems(002~045) 3/15/08 4:09 Page 6 Control Systems Individual control system 1-1. Wireless signal receiver kit 1) Features MRK-A00 MRW-10A (Receiver wire) Unit : mm Wireless signal receiver • Concealed wireless signal receiver • Filter replacement sign • Fan operation display •...
  • Page 539: Wireless Remote Controller

    05-1_control systems(002~045) 3/15/08 4:09 Page 7 1-2. Wireless remote controller 1) Features MR-AH01 MR-BH01 Easy and convenient operation control • Operation ON/OFF • Fan speed control • Operation temperature setting • Filter replacement alarm reset • Air flow control • Simple ON/OFF timer •...
  • Page 540 05-1_control systems(002~045) 3/15/08 4:09 Page 8 Control Systems Individual control system 1-2. Wireless remote controller 2) Description of buttons and functions MR-AH01 Name Description Operation mode setting button Press the button to select an operation mode. Temperature setting button Press the button to set the temperature by 1°C. Press the button to turn off the filter replacement alarm display LED on the Filter replacement alarm reset button indoor panel.
  • Page 541 05-1_control systems(002~045) 3/15/08 4:09 Page 9 MR-BH01 Name Description Filter replacement alarm reset display Blinks when “Filter reset” button is pressed. Operation mode display Indicates the operation mode. Fan speed display Indicates the fan speed settings (Low, Medium, High, and Auto.) Set temperature display Indicates the set temperature.
  • Page 542 05-1_control systems(002~045) 3/15/08 4:09 Page 10 Control Systems Individual control system 1-2. Wireless remote controller 3) Additional functions OPTION CODE SETTING MR-AH01 1. Remove batteries from the remote controller. 2. Press Temp. UP and Temp. DOWN buttons at the same time and then insert the batteries again. 3.
  • Page 543 05-1_control systems(002~045) 3/15/08 4:09 Page 11 1-3. Wired remote controller 1) MWR-TH01 (1) Features Easy and convenient operation control • On/Off control • Operation mode, Temperature setting, Fan speed, Air flow direction • Simple operation ON/OFF timer • Error display •...
  • Page 544 05-1_control systems(002~045) 3/15/08 4:09 Page 12 Control Systems Individual control system 1-3. Wired remote controller 1) MWR-TH01 (3) Description of buttons and functions Name Description Defrost operation icon Displayed when Defrost operation is started. Operation mode icon Indicates the current operation mode. Indicates that the remote controller prohibition option is set.
  • Page 545 05-1_control systems(002~045) 3/15/08 4:09 Page 13 PCB Description Name Description It is possible to set additional functions for Option switches wired remote controller. Master / Slave setting switch It is used for “2-Remote controller”. (Address switch) DS03 Communication wiring terminal Connection to indoor unit (F3/F4).
  • Page 546 05-1_control systems(002~045) 3/15/08 4:09 Page 14 Control Systems Individual control system 1-3. Wired remote controller 1) MWR-TH01 (4) Additional functions Group (RMC) address assignment ❈ Indoor unit and wired remote controller should be connected by COM2 (F3/F4) communication line. ❈ RMC address assignment function is only applicable when an indoor unit is connected with wired remote controller one-by-one.
  • Page 547 05-1_control systems(002~045) 3/15/08 4:09 Page 15 2) MWR-WS00 (1) Features Easy air conditioner control Energy saving operation • Operation ON / OFF control • Upper/Lower temperature limit setting • Set operation mode, setting temperature, fan speed, • Automatic operation stop function air flow direction •...
  • Page 548 05-1_control systems(002~045) 3/15/08 4:09 Page 16 Control Systems Individual control system 1-3. Wired remote controller 2) MWR-WS00 (3) Description of buttons and functions 9 13 Operation On/Off button Press this button to turn on all connected indoor units. Press again to turn off all connected indoor units. Setting temperature / indoor temperature / schedule display •...
  • Page 549 05-1_control systems(002~045) 3/15/08 4:09 Page 17 Special function display 3 : Displayed when automatic stop function is set. : Displayed when the wired/wireless remote controller is prohibited by upper-layer devices. Temperature setting button (applicable only for Cooling, Heating and Auto.) is pressed, increase by 1°C (°F).
  • Page 550 05-1_control systems(002~045) 3/15/08 4:09 Page 18 Control Systems Individual control system 1-3. Wired remote controller 2) MWR-WS00 (3) Description of buttons and functions PCB Description Name Description It is possible to set additional functions Option switches for wired remote controller. Software upgrade connector It is used to upgrade the micro-controller’s software.
  • Page 551 05-1_control systems(002~045) 3/15/08 4:09 Page 19 Service mode menu description Press Hr. and Min, temperature setting button for more than 5 seconds to enter Service mode. Menu Detailed description Display SW 8 OFF: Option code monitoring SW 8 ON: Option code setting Option code : Detailed indoor unit functions such as indoor unit model type, indoor unit capacity, blackout restoration, and drain pump control...
  • Page 552 05-1_control systems(002~045) 3/15/08 4:09 Page 20 Control Systems Individual control system 1-3. Wired remote controller 2) MWR-WS00 (4) Additional functions Service mode menu description Menu Detailed description Display SW 8 OFF : Monitor the compensation value of the temperature sensor in the wired remote controller SW 8 ON : Set the compensation value for temperature sensor in the wired remote controller.
  • Page 553 05-1_control systems(002~045) 3/15/08 4:09 Page 21 Menu Detailed description Display SW 8 OFF : Monitor the setting temperature compensation value under the Heating mode. SW 8 ON : Set the setting temperature compensation value. Setting temperature compensation value of the heating operation: Compensate the setting temperature used for heating operation control.
  • Page 554 05-1_control systems(002~045) 3/15/08 4:09 Page 22 Control Systems Individual control system 1-3. Wired remote controller 2) MWR-WS00 (5) Installation Operation checking Operation Display LCD is turned on for about 1second, Power input all segments are lit. Temperature display indicates Indoor unit Tracking Tracking is under way.
  • Page 555 05-1_control systems(002~045) 3/15/08 4:09 Page 23 3) MWR-SH00 (1) Features Easy air conditioner control • Compact design. • Operation On /Off control. • Set operation mode and fan speed. • Operation mode lock. • Filter replacement alarm and reset. (2) Dimensional drawing Unit : mm V-23...
  • Page 556 05-1_control systems(002~045) 3/15/08 4:09 Page 24 Control Systems Individual control system 1-3. Wired remote controller 3) MWR-SH00 (3) Description of buttons and functions Name Description Set temperature display Indicates the set temperature of the indoor unit. Defrost operation icon Displayed when Defrost operation is started. Operation mode icon Displays the current operation mode.
  • Page 557 05-1_control systems(002~045) 3/15/08 4:09 Page 25 PCB description Name Description Software upgrade connector It is used to upgrade the micro-controller’s software. It is possible to set additional functions for wired remote Option switches controller. Communication wiring terminal Connection to indoor unit (F3/F4). Power wiring terminal (12VDC) Connection to indoor unit (V1/V2).
  • Page 558 05-1_control systems(002~045) 3/15/08 4:09 Page 26 Control Systems Individual control system 1-3. Wired remote controller 3) MWR-SH00 (5) Installation Operation checking Operation Display LCD is turned on for about 1second, all segments are lit. Power input Temperature display indicates Tracking is under way. When communication with indoor units is made it Indoor unit Tracking displays the total number of indoor units connected with...
  • Page 559 05-1_control systems(002~045) 3/15/08 4:09 Page 27 Error code Display a type of error occurred in indoor units, outdoor units and, wired remote controller. (The following is errors related to a wired remote controller) Error code Description Remark When communication with indoor units is blocked for ↔...
  • Page 560 05-1_control systems(002~045) 3/15/08 4:09 Page 28 Control Systems Individual control system 1-3. Wired remote controller Connection examples • MWR-TH01 Wired • MWR-WS00 • MWR-SH00 Individual control Control 1 indoor unit with 1 wired remote controller F1/F2 Indoor unit Outdoor unit F3/F4 Wired R/C Control...
  • Page 561 05-1_control systems(002~045) 3/15/08 4:09 Page 29 Group control (3) Control multiple indoor units with 2 Wired remote controllers F1/F2 Indoor unit Outdoor unit F3/F4 Wired R/C Slave Master Master Slave ❈ Max. 16 indoor units can be connected. One of the two remote controllers must be set as a Master. It is not possible to use the different type of remote controller for 2-remote controller.
  • Page 562 05-1_control systems(002~045) 3/15/08 4:09 Page 30 Control Systems Individual control system 1-3. Wired remote controller 4) MWR-VH01 (1) Features Heat exchange unit (ERV) Control & Monitoring • Operation On/Off control. • Set ventilation mode, Fan speed. • Filter replacement alarm and reset. •...
  • Page 563 05-1_control systems(002~045) 3/15/08 4:09 Page 31 (3) Description of buttons and functions Name Description External control display Display when ERV is controlled synchronously with DVM indoor unit. Test display Indicates that an error occurs in ERVs. Indicates that the remote controller prohibition option is set. (Only upper controller, such Centralized controller display as the Centralized controller, can control indoor unit) 1)When synchronously controlled with system air conditioner : Displays operation delay time.
  • Page 564 05-1_control systems(002~045) 3/15/08 4:09 Page 32 Control Systems Individual control system 1-3. Wired remote controller 4) MWR-VH01 (3) Description of buttons and functions PCB description Name Description Master/Slave setting switch It is used for 2 remote controllers. (Address switch) It is possible to set additional functions for wired remote Option switches controller.
  • Page 565 05-1_control systems(002~045) 3/15/08 4:09 Page 33 Master/Slave setting switch When use the “2-Remote controller”, one remote controller must be MASTER, and the other must be SLAVE. • MASTER : Set the switch to 0 • SLAVE : Set the switch to 1 ❈...
  • Page 566 05-1_control systems(002~045) 3/15/08 4:09 Page 34 Control Systems Individual control system 1-3. Wired remote controller 4) MWR-VH01 (5) Connection examples Individual control Control 1 ERV with 1 wired remote controller Wired R/C Connection 1 : 1 Control Connected ERV Display Operation status of the connected ERV Error occurrence Displays an ERV error.
  • Page 567 05-1_control systems(002~045) 3/15/08 4:09 Page 35 1000m Length of transmission wiring Max. distance between the farthest ERV and ERV remote controller: 1000m Wired R/C DVM indoor unit synchronization 1 : 1 : 1 synchronous control COM1(F1/F2) Outdoor unit COM2 (F3/F4) Wired R/C Remote controller for indoor units (MWR-TH01, WS00, SH00) cannot be connected to the same COM2 communication line with the ERV remote controller.
  • Page 568 05-1_control systems(002~045) 3/15/08 4:09 Page 36 Control Systems Individual control system 1-3. Wired remote controller 4) MWR-VH01 (5) Connection examples DVM indoor unit synchronization 1 : N : 1 Synchronous control COM1(F1/F2) Outdoor unit COM2 (F3/F4) Wired R/C Remote controller for indoor units (MWR-TH01, WS00, SH00) cannot be connected to the same COM2 communication line with the ERV remote controller.
  • Page 569 05-1_control systems(002~045) 3/15/08 4:09 Page 37 DVM indoor unit synchronization N : 1 : 1 Synchronous control COM1(F1/F2) Outdoor unit COM2 (F3/F4) Wired R/C Remote controller for indoor units (MWR-TH01, WS00, SH00) cannot be connected to the same COM2 communication line with the ERV remote controller. The total number of indoor units and ERVs that can be connected to one ERV remote controller is Max.16.
  • Page 570 05-1_control systems(002~045) 3/15/08 4:09 Page 38 Control Systems Individual control system 1-3. Wired remote controller 4) MWR-VH01 (5) Connection examples DVM indoor unit synchronization N : N : 1 Synchronous control COM1(F1/F2) Outdoor unit COM2 (F3/F4) Wired R/C Remote controller for indoor units (MWR-TH01, WS00, SH00) cannot be connected to the same COM2 communication line with the ERV remote controller.
  • Page 571 05-1_control systems(002~045) 3/15/08 4:09 Page 39 DVM indoor unit synchronization N : N : 2 Synchronous control COM1(F1/F2) Outdoor unit COM2 (F3/F4) Slave Wired R/C Master Remote controller for indoor units (MWR-TH01, WS00, SH00) cannot be connected to the same COM2 communication line with the ERV remote controller.
  • Page 572 05-1_control systems(002~045) 3/15/08 4:09 Page 40 Control Systems Individual control system 1-4. 7-day scheduler (MWR-BS00) 1) Features Weekly operation schedule setup • Air conditioner On/Off schedule setting • Max. 124 schedule operation settings • Automatic schedule operation repeat • Current time and day display 2) Dimensional drawing Unit : mm V-40...
  • Page 573 05-1_control systems(002~045) 3/15/08 4:09 Page 41 3) Description of buttons and functions Name Description Displays the current time in the monitoring mode, while displaying schedule time in the Digital time display scheduling mode. Display mode For the scheduling set mode, is displayed.
  • Page 574 05-1_control systems(002~045) 3/15/08 4:09 Page 42 Control Systems Individual control system 1-4. 7-day scheduler (MWR-BS00) 3) Description of buttons and functions PCB description Name Description Connection to a wired remote controller (MWR-TH01) Communication wiring terminal (F3/F4). Connection to a wired remote controller (MWR-TH01) Power wiring terminal (12VDC) (V1/V2).
  • Page 575 05-1_control systems(002~045) 3/15/08 4:09 Page 43 Wiring Wired remote controller: MWR-TH01 Centralized controller: MCM-A202A F3/F4 R1/R2 F3-R1 F4-R2 7-day 7-day scheduler scheduler R1 R2 C1 C2 Extra power supply 12V DC/300mA ❈ SW4 ON ❈ SW2 OFF Centralized controller Wired remote controller Operation checking Display after applying the power ➊...
  • Page 576 05-1_control systems(002~045) 3/15/08 4:09 Page 44 Control Systems Individual control system 1-4. 7-day scheduler (MWR-BS00) 6) Connection examples Connected to the wired remote controller F1/F2 Indoor unit Outdoor unit F3/F4 Wired R/C 7-day scheduler Wired R/C 7-day scheduler Control Apply schedule operation to all indoor units connected to the wired remote controller. Connected to the centralized controller R1/R2 F1/F2...
  • Page 577 05-1_control systems(002~045) 3/15/08 4:09 Page 45 Centralized control system 2-1. Interface module-------------------------------------------------------- 2-2. Centralized controller (MCM-A202A) -------------------------------- 2-3. Function controller (MCM-A100) ------------------------------------ 2-4. Operation mode selection switch (MCM-C200) ------------------ 2-5. S-NET II Plus (MST-S1P) -------------------------------------------- V-45...
  • Page 578 05-2_control systems(046~081) 3/6/08 14:02 Page 46 Control Systems Centralized control system 2-1. Interface module 1) MIM-B04A (1) Features F1 F2 • Communication device interfacing indoor/outdoor units with external control system • Mainly used for upper system like centralized controllers/functions controllers/DMS •...
  • Page 579 05-2_control systems(046~081) 3/6/08 14:02 Page 47 (3) Explanation of part names F1 F2 Name Description Communication checking 7-Segment Displays the communication state Software update connector Using this connector, I/M software can be updated. Option setting switches Set additional function Address setting switch Set I/M address Communication connector (I/M ↔...
  • Page 580 05-2_control systems(046~081) 3/6/08 14:02 Page 48 Control Systems Centralized control system 2-1. Interface module (4) Installation WIRING ➊ Connection between interface module and outdoor unit (example : DVM PLUS) DC 12V F1 F2 F1/F2 ❷ Connection between interface module and centralized controller F1 F2 R1/R2 Specification...
  • Page 581 05-2_control systems(046~081) 3/6/08 14:02 Page 49 Operation display ➊ When I/M is connected to F1/F2 (Outdoor unit) ❈ Display all indoor unit ➔ ➔ ➔ main addresses alternatively at the left segment (for all indoor units with K2 to OFF) Power input Outdoor unit During tracking...
  • Page 582 05-2_control systems(046~081) 3/6/08 14:02 Page 50 Control Systems Centralized control system 2-1. Interface module 2) MIM-B13A (1) Features • Communication device interfacing indoor/outdoor units with external control system • Mainly used for upper system like centralized controllers / functions controllers / DMS •...
  • Page 583 05-2_control systems(046~081) 3/6/08 14:02 Page 51 (3) Explanation of part names Name Description Communication checking 7-Segment Displays communication state Software update connector Using this connector, I/M software can be updated Address setting switch Set I/M address Connection CH 0 : I/M ↔ Centralized controller Connect to centralized controller R1/R2 Connection I/M ↔...
  • Page 584 OF1 OF2 Setting the power setting switch • DC 12V, DC 5V together : All switches must be OFF (For DVM PLUS II, DVM PLUS III) • DC 12V only : All switches must be ON (For FJM, CAC, mini DVM)
  • Page 585 05-2_control systems(046~081) 3/6/08 14:02 Page 53 ❷ Connection between interface module and centralized controller Specification • Power (V1/V2) : DC 12V /150mA , DC 5V /50mA • Communication line - F1/F2 (Connect to outdoor unit) : RS-485 (No-polarity), VCTF (0.75~1.5mm - R1/R2 (Connect to centralized controller) : RS-485 (No-polarity), VCTF (0.75~1.5mm •...
  • Page 586 05-2_control systems(046~081) 3/6/08 14:02 Page 54 Control Systems Centralized control system Operation display ➊ When interface module is connected to F1/F2 (Outdoor unit) ➔ ➔ ➔ ➔ Software version after Before outdoor unit Outdoor unit detection During tracking Tracking completed power input (2.0) detection ❈...
  • Page 587 05-2_control systems(046~081) 3/6/08 14:02 Page 55 2-2. Centralized controller (MCM-A202A) 1) Features • Maximum 16-group controller (Max. 256 Indoor units) • Whole/Individual indoor unit control (On/Off) • Restriction on the use of wireless/wired remote controllers • Cooling and heating mode control •...
  • Page 588 05-2_control systems(046~081) 3/6/08 14:02 Page 56 Control Systems Centralized control system 2-2. Centralized controller (MCM-A202A) 3) Buttons and display COOL AUTO HEAT Name Description It lights on when more than one indoor unit operates. Indoor unit operation LED It flickers during indoor unit tracking process after power reset. Press All ON button to turn on all the indoor units.
  • Page 589 05-2_control systems(046~081) 3/6/08 14:02 Page 57 4) Communication wiring length Maximum communication wiring length is 1000m between the centralized controller to the most remote interface module. ① + ➁ + ➂ + ➃ < 1000m 5) Precaution on wiring with interface modules Each connection between the centralized controller and the interface modules must be made using the separate communication wires to prevent crosstalk.
  • Page 590 05-2_control systems(046~081) 3/6/08 14:02 Page 58 Control Systems Centralized control system 2-2. Centralized controller (MCM-A202A) 6) Rotary & Option switch DIP SW Description Restriction setting on wired/wireless remote control use Wired/Wireless remote control use is allowed all the time. Level 0 Wired/Wireless remote control use is allowed only if indoor unit is ON by the centralized controller.
  • Page 591 05-2_control systems(046~081) 3/6/08 14:02 Page 59 7) Option switch K1, K2 – Remote control use LEVEL 0 • ‘Allowed’ remote controller LEVEL 1 • Turned on by Centralized controller – ‘Allowed’ • Turned off by Centralized controller – ‘Prohibited’ LEVEL 2 •...
  • Page 592 05-2_control systems(046~081) 3/6/08 14:02 Page 60 Control Systems Centralized control system 2-2. Centralized controller (MCM-A202A) 8) Option switch K3 – Tracking mode setting Main:0 Main:1 Main:2 RMC:3 RMC:4 RMC:5 Group mode – Indoor unit control/monitoring with the RMC address Room mode - Indoor unit control/monitoring with the Main address Interface with DMS and S-NET mini –...
  • Page 593 05-2_control systems(046~081) 3/6/08 14:02 Page 61 9) Option switch K4 – Upper-layer device compatibility (1) Upper- layer controller interface Upper-layer devices can be chosen for interface with the centralized controller based on the option switch K4 setting. Main:0 Main:1 Main:2 RMC:3 RMC:4 RMC:5...
  • Page 594 05-2_control systems(046~081) 3/6/08 14:02 Page 62 Control Systems Centralized control system 2-2. Centralized controller (MCM-A202A) 10) Various LED display After power reset to the centralized controller, it carries out indoor unit tracking process through the interface modules. Main:0 Main:1 Main:2 I/M 0 RMC:0 RMC:1...
  • Page 595 11) Compatibility with interface module • MIM-B04A : DVM, DVM PLUS, mini DVM(R407), CAC • MIM-B13A : DVM PLUS II, DVM PLUS III, HR II, mini DVM(R410A), FJM, ERV ❈ Old versions MIM-B13, MIM-B04, MIM-B00 are also supported to MCM-A202A.
  • Page 596 05-2_control systems(046~081) 3/6/08 14:02 Page 64 Control Systems Centralized control system 2-2. Centralized controller (MCM-A202A) Operation sequence ❇ IDU : Indoor unit IDU1, 2, 3 Stop mode after power reset Cooling mode set with centralized controller IDU1 ON with centralized controller IDU1 operating in 24ºC Cooling IDU1 set to 28ºC Heating with wired remote controller IDU1 operating in 28ºC Heating...
  • Page 597 05-2_control systems(046~081) 3/6/08 14:02 Page 65 2-3. Function controller (MCM-A100) 1) Features • Indoor unit control/monitoring of up to 16 groups (Max. 256 indoor units) • On/Off control • Operation mode, temperature setting, airflow direction, fan speed • Error display (Indoor & Outdoor units) •...
  • Page 598 05-2_control systems(046~081) 3/6/08 14:02 Page 66 Control Systems Centralized control system 2-3. Function controller (MCM-A100) 3) Explanation of part names Name Description Error indicator It is displayed when errors occurred in indoor/outdoor units. Defrost indicator Certain indoor unit enters Defrosting operation mode. Operation mode indicator Indoor unit operation mode.
  • Page 599 05-2_control systems(046~081) 3/6/08 14:02 Page 67 4) Connection with centralized controller Centralized controller Power supply 9VDC~12VDC 100mA Function controller 5) Option & Rotary switch Function DIP SW Dip switch – No function Cooling Cooling and Heating No function No function ºC ºF No function...
  • Page 600 05-2_control systems(046~081) 3/6/08 14:02 Page 68 Control Systems Centralized control system 2-3. Function controller (MCM-A100) 7) Connection diagram DVM PLUS III / HR III MIM-B13A MCM-A100 MCM-A202A K4 ON DVM PLUS II / HR II MIM-B13A DVM PLUS MIM-B04A DVM / DVM HR...
  • Page 601 05-2_control systems(046~081) 3/6/08 14:02 Page 69 8) Precaution on wiring with interface modules ➊ Multiple centralized controllers cannot be connected to one functional controller. ❷ Centralized controller address must be matched to function controller address. If not matched, function controller does not complete initial tracking process. ❸...
  • Page 602 05-2_control systems(046~081) 3/6/08 14:02 Page 70 Control Systems Centralized control system 2-3. Function controller (MCM-A100) 9) Error display Display Description Note Centralized controller ↔ Function controller communication error Er ➔ EA (no response from the centralized controller) No data from indoor units to centralized controller. (Normal communication Communication error Er ➔...
  • Page 603 05-2_control systems(046~081) 3/6/08 14:02 Page 71 2-4. Operation mode selection switch (MCM-C200) 1) Features Operation mode selection switch Outdoor unit operation mode selection (Cooling, Heating or Auto) Mixed operation mode protection 2) Dimensional drawing Unit : mm V-71...
  • Page 604 05-2_control systems(046~081) 3/6/08 14:02 Page 72 Control Systems Centralized control system 2-4. Operation mode selection switch (MCM-C200) 3) Installation AUTO HEAT OPT 1 HEAT WHITE AUTO AUTO BLUE COOL Outdoor COOL Uint ➊ Connect MCM-C200 to Outdoor unit 1:1 ❷ After setting the operation mode of MCM-C200, press K3 button to make outdoor unit reset (If compressor is activating, outdoor unit will be reset automatically) ❈...
  • Page 605 05-2_control systems(046~081) 3/6/08 14:02 Page 73 2-5. S-NET II Plus (MST-S1P) 1) System overview (1) Overview • S-NET II Plus Central management PC program specifically designed to manage system air conditioners • Applicable sites System air conditioners installed on sites such as universities and residential and commercial complexes. It is possible to control and monitor max.
  • Page 606 05-2_control systems(046~081) 3/6/08 14:02 Page 74 Control Systems Centralized control system 2-5. S-NET II Plus (MST-S1P) (3) Product specification Item Model Details Pentium III 500MHz or above Memory More than 512MB Network 10/100M Ethernet Windows NT, Window 2000, Windows XP ❈...
  • Page 607 05-2_control systems(046~081) 3/6/08 14:02 Page 75 Centralized controller comm. line connection • Centralized controller C1, C2 comm. line connection (Check polarity of the comm. line for connection) C2 C1 V2 V1 When making a connection, check the polarity of the comm.line. C2 C1 V2 V1 T X + ➝...
  • Page 608 05-2_control systems(046~081) 3/6/08 14:02 Page 76 Control Systems Centralized control system 2-5. S-NET II Plus (MST-S1P) (2) S-NET II Plus function description isplay Main screen ➊ Control/Monitoring screen II Plus. Able to monitor and control the status of indoor units connected to S-NET Menu Control / Monitoring window Control tree...
  • Page 609 05-2_control systems(046~081) 3/6/08 14:02 Page 77 256-room control : Select 256 group control at the control tree When indoor unit is turned ON When indoor unit is OFF Indoor unit that does not exist (in gray) Description 256-group name Indoor unit ON/OFF button 16-group name Zone control •...
  • Page 610 05-2_control systems(046~081) 3/6/08 14:02 Page 78 Control Systems Centralized control system 2-5. S-NET II Plus (MST-S1P) • How to change a zone name Changing a zone name in the zone setup window. Changing a zone name at the control tree. •...
  • Page 611 05-2_control systems(046~081) 3/6/08 14:02 Page 79 Schedule control • Daily schedule : set up for schedule operation repeating everyday. • Weekly schedule : set up for schedule operation repeating every week. • 1-day schedule : set up for schedule operation for one day only. •...
  • Page 612 05-2_control systems(046~081) 3/6/08 14:02 Page 80 Control Systems Centralized control system 2-5. S-NET II Plus (MST-S1P) • Rename a schedule Rename a schedule in the schedule Rename a schedule at the control tree. setup window. • Delete a schedule Delete the existing schedule For schedule time setup, select a schedule group at the control tree to see the schedule setting.
  • Page 613 05-2_control systems(046~081) 3/6/08 14:02 Page 81 3) Installation (1) Overview • Before installing S-NET II Plus program, carry out a virus inspection in the PC. • Program installation • Programs to be installed in the PC during program Installation ➔ Microsoft .Net Framework 1.1 (2) S-NET authorization process...
  • Page 614 05-3_control systems(082~141) 3/6/08 14:03 Page 82 Control Systems V-82...
  • Page 615 05-3_control systems(082~141) 3/6/08 14:03 Page 83 Integrated management system 3-1. DMS (Data Management Server) ------------------------------------ 3-2. S-NET3 (MST-P3P) ---------------------------------------------------- 3-3. S-NET mini (MST-S3W) ---------------------------------------------- V-83...
  • Page 616 05-3_control systems(082~141) 3/6/08 14:03 Page 84 Control Systems Integrated management system 3-1. DMS (Data Management Server) 1) MIM-D00 (1) General description • Built-in web server - PC-independent management - Internet access control • 16 centralized controllers supported • Up to 256 indoor units can be controlled individually or in groups •...
  • Page 617 05-3_control systems(082~141) 3/6/08 14:03 Page 85 (2) Features Easy control & Monitoring • Operation control and monitoring of up to 256 indoor units individually or in groups. • Operation mode, temperature setting, airflow direction and fan speed. • Restriction on use of wireless/wired remote controllers. Web server function •...
  • Page 618 05-3_control systems(082~141) 3/6/08 14:03 Page 86 Control Systems Integrated management system 3-1. DMS (Data Management Server) (4) Dimensional drawing Unit : mm (5) Buttons and connectors 11 12 Name Description Option switch Option switch for specification on external input to DMS Power terminal Power supply to DMS.
  • Page 619 05-3_control systems(082~141) 3/6/08 14:03 Page 87 (6) External input/output ports and option switch Option switch SW03 External input/output ports DI-2 DI-1D0-2 D0-1 Name Description All indoor units are controlled by no-powered external input (leveled/pulsed) Digital input DI-1 according to the option switch setting. Load : 12VDC/5mA All wired/wireless remote controllers for indoor units are permitted/prohibited by no-powered external input (leveled/pulsed) according to the option switch...
  • Page 620 05-3_control systems(082~141) 3/6/08 14:03 Page 88 Control Systems Integrated management system 3-1. DMS (Data Management Server) (7) Option switch DIP switch (SW03) : Use only for external contact signal control. DIP switch no. Pattern Control details Contact input No function (Default setting) Not applied 1.
  • Page 621 05-3_control systems(082~141) 3/6/08 14:03 Page 89 Pattern 3 External contact DI-2 (Level-triggered) DI-1 External contact (Level-triggered) Option switch External contact input to DI-1 Short contact : Starts all indoor unit operation. Open contact : Stops all indoor unit operation. External contact input to DI-2 Short contact : Disables the use of all wired/wireless remote controllers.
  • Page 622 Centralized controller MCM-A202A Interface module MIM-B04A, MIM-B13A MIM-B12 Max. 8 watt-hour meters are supported for 1 SiM. Watt-hour meter Specified Korean products DVM PLUS III, DVM PLUS II, Outdoor unit DVM PLUS, DVM, HR system, V-90...
  • Page 623 05-3_control systems(082~141) 3/6/08 14:04 Page 91 (9) Maximum number of interface Device Maximum Model Upper-layer device Unlimited S-NET3, S-NET i, S-NET mini, Web-Client Centralized controller MCM-A202A MIM-B04A, MIM-B13A Interface module (for one centralized controller) MIM-B12 Watt-hour meter 8 watt-hour meters for one SiM In case of exceeding 256 indoor units, DMS Indoor unit ignores them after initial tracking process.
  • Page 624 05-3_control systems(082~141) 3/6/08 14:04 Page 92 Control Systems Integrated management system 3-1. DMS (Data Management Server) (11) Access to DMS ➊ Use the cross-type LAN cable to make direct connection with an operating PC and the DMS. Direct LAN cable Cross LAN cable Pin assignment of the LAN cable 1.
  • Page 625 05-3_control systems(082~141) 3/6/08 14:04 Page 93 (12) Initial screen display Main menu Basic monitoring and control for indoor units Error history reference Schedule function Time section setting for different electricity-billing rates Watt-hour meter mapping to connected indoor/outdoor units Power distribution/ratio result query DMS configuration for proper operation Registration of installed devices Access ID and password management...
  • Page 626 05-3_control systems(082~141) 3/6/08 14:04 Page 94 Control Systems Integrated management system 3-1. DMS (Data Management Server) Main control panel Function Description ON/OFF control ON/OFF control of indoor units. Room temperature Current room temperature of the selected indoor unit. Temperature setting with UP/DOWN arrows. Set temperature Cooing mode : 18 ºC ~ 30 ºC Heating mode : 16ºC ~ 30 ºC...
  • Page 627 05-3_control systems(082~141) 3/6/08 14:04 Page 95 Schedule Selected schedule cannot be modified without stopping application. Select synchronous ERV operation mode with indoor units Set the dates when schedule control is skipped. Press to remove the relevant indoor units from the selection table. Press to select indoor units which schedule control is applied to.
  • Page 628 05-3_control systems(082~141) 3/6/08 14:04 Page 96 Control Systems Integrated management system 3-1. DMS (Data Management Server) Setup for power distribution This setting is mostly used for the case that electricity billing rates differ in time section of day. S-NET3 must be used together to support time section setting for power distribution. Segmented tables for different rate sections are seen on the S-NET3 screen to enter time-dependent billing rates.
  • Page 629 05-3_control systems(082~141) 3/6/08 14:04 Page 97 WHM address assignment WHM address is assigned to constant value for each terminal of SiM interface like below. SiM address can be set from 0 to 7. DMS recognizes SiM of which address is added by 16 to differentiate it from those of centralized controllers.
  • Page 630 05-3_control systems(082~141) 3/6/08 14:04 Page 98 Control Systems Integrated management system 3-1. DMS (Data Management Server) WHM address assignment Mapping example 1. Watt-hour meter mapping with common power supply C1-C2 Wiring Centralized controller Address 0 SiM Address 0 Watt-hour meter I/M Address 1 Main 0 Main 1...
  • Page 631 05-3_control systems(082~141) 3/6/08 14:04 Page 99 Mapping example 2. Watt-hour meter mapping with separate power supply C1-C2 Wiring Centralized controller Address 0 SiM Address 0 Watt-hour meter Watt-hour meter Main 0 Main 1 Main 2 I/M Address 1 Watt-hour meter Main 0 Main 1 Main 2...
  • Page 632 05-3_control systems(082~141) 3/6/08 14:04 Page 100 Control Systems Integrated management system 3-1. DMS (Data Management Server) Result of power distribution Power distribution result can be queried based on dates for all indoor units. Even operation time and power consumption of individual indoor units can be queried for the specific date. All the distribution result is saved in the Microsoft Excel format by simple button press.
  • Page 633 05-3_control systems(082~141) 3/6/08 14:04 Page 101 System environment All the configurations are made in the system environment. Those include network configuration, Master/Slave setting, current time setting, S-NET3 password, priority setting, Language selection, error mailing service and DMS naming. ➊ Network configuration IP Address : Networking DMS IP Gateway : Gateway or router IP which each subgroup is networked with.
  • Page 634 05-3_control systems(082~141) 3/6/08 14:04 Page 102 Control Systems Integrated management system 3-1. DMS (Data Management Server) Slave DMS 1 192.168.0.2 Slave DMS 2 192.168.0.2 Master DMS 3 ❸ System time Set the current time for power distribution or schedule control. ❹...
  • Page 635 05-3_control systems(082~141) 3/6/08 14:04 Page 103 Controller Function (When priority is applied) S-NET3 S-NET3 always can set DMS configuration (Top priority). S-NET i Once DMS is configured by S-NET3, S-NET i can’t make changes to the configurations. S-NET mini Once DMS is configured by S-NET3, S-NET mini can’t make changes to the configurations. Once DMS is configured by S-NET3, S-NET i or S-NET mini, DMS cannot be configured Web client by web clients.
  • Page 636 05-3_control systems(082~141) 3/6/08 14:04 Page 104 Control Systems Integrated management system 3-1. DMS (Data Management Server) Power distribution • Where does power consumption occur? Air-conditioning system Outdoor unit fan Compressor Outdoor unit PCB Indoor unit PCB Indoor unit fan System power consumption includes : 1.
  • Page 637 05-3_control systems(082~141) 3/6/08 14:04 Page 105 ➊ DMS power distribution theory All the system information of power and indoor/outdoor operation is always monitored by the DMS for power distribution calculation. IDU : Indoor unit Through SiM units IDU B IDU A Measured power consumption IDU C...
  • Page 638 05-3_control systems(082~141) 3/6/08 14:04 Page 106 Control Systems Integrated management system 3-1. DMS (Data Management Server) ❺ What if the room temperature begins to reach the set temperature? If the room temperature begins to reach the set temperature, the indoor unit does not have to extract the full refrigerant amount to keep the set condition.
  • Page 639 05-3_control systems(082~141) 3/6/08 14:04 Page 107 DMS tracking mode for power distribution Under the Room tracking mode, power distribution is carried out which is based on the MAIN-address of indoor units under centralized controllers and interface modules. Since all the indoor units under one interface module have different MAIN addresses, no confusion is made for proper power distribution.
  • Page 640 05-3_control systems(082~141) 3/6/08 14:04 Page 108 Control Systems Integrated management system 3-1. DMS (Data Management Server) Power distribution equation C1-C2 wiring Centralized controller Power supply Power supply Interface module When configuring the DMS and the whole system, mapping of watt-hour meters for indoor/outdoor units must be precisely assigned for correct power distribution.
  • Page 641 05-3_control systems(082~141) 3/6/08 14:04 Page 109 Example Suppose capacity values accumulated at 24:00 during one whole day is as follows. Strong cooling Week cooling Fan mode Stop 360kWh consumed (outdoor + indoor) Main capacity =105 Main capacity = 60 Main capacity = 0 Main capacity = 0 Fan capacity = 20 Fan capacity = 20...
  • Page 642 05-3_control systems(082~141) 3/6/08 14:04 Page 110 Control Systems Integrated management system 3-1. DMS (Data Management Server) Installation example (Allowed) C1-C2 wiring Centralized controller Power supply Power supply Interface module Mapping watt-hour meters to indoor/outdoor units 1. Watt-hour meter A is mapped to all indoor/outdoor units in G1. 2.
  • Page 643 05-3_control systems(082~141) 3/6/08 14:04 Page 111 Installation example (Not allowed) C1-C2 wiring Centralized controller Power supply Power supply Interface module All indoor units in one outdoor unit must have the same power source. Installation above cannot be available for the reason that one indoor unit in G1 has different power source from the other indoor units.
  • Page 644 05-3_control systems(082~141) 3/6/08 14:04 Page 112 Control Systems Integrated management system 3-2. S-NET3 (MST-P3P) 1) System overview (1) Overview S-NET3 PC program designed to manage system air conditioners in a large site. Applicable sites DMS installed sites such as university and residential and commercial complex that allow max. 16 DMS connections to control and monitor max.
  • Page 645 05-3_control systems(082~141) 3/6/08 14:04 Page 113 2) Function (1) S-NET3 function description View the management structure Control and monitor the indoor units (max. 4,096 units). Check and refer the state of various devices such as indoor/outdoor View the installation structure units, centralized controller, and I/M.
  • Page 646 05-3_control systems(082~141) 3/6/08 14:04 Page 114 Control Systems Integrated management system 3-2. S-NET3 (MST-P3P) (2) Detailed S-NET3 function description Monitoring Monitor the operation status of max.16 DMS units, and max. 4,096 indoor units. • Monitor the status of indoor/outdoor units, controllers connected to S-NET3. •...
  • Page 647 05-3_control systems(082~141) 3/6/08 14:04 Page 115 ontrol and environment setting ➊ User functions Manage a range of functions accessible to different types of users such as general user, administrator, installer. User Administrator Installer View the total indoor unit Structure editing The list of installed devices Whole indoor unit stop Indoor unit/ERV control/Monitoring...
  • Page 648 05-3_control systems(082~141) 3/6/08 14:04 Page 116 Control Systems Integrated management system 3-2. S-NET3 (MST-P3P) isplay Login Select Select Select user administrator installer Password input Login button Main screen View total View the total List of logout indoor units installed devices Full screen Edit Total indoor...
  • Page 649 05-3_control systems(082~141) 3/6/08 14:04 Page 117 ➊ Control/Monitoring screen Able to monitor the operation status of indoor units connected to S-NET3. When DMS is selected, display indoor units connected to DMS. Monitor indoor unit operation status When centralized controller is selected, display indoor units connected to centralized controller.
  • Page 650 05-3_control systems(082~141) 3/6/08 14:04 Page 118 Control Systems Integrated management system 3-2. S-NET3 (MST-P3P) ❷ View installation structure • Select the installation structure tab then select DMS connected to S-NET3; it is possible to see the program version, status of the selected DMS, the program version and communication status of centralized controller.
  • Page 651 05-3_control systems(082~141) 3/6/08 14:04 Page 119 ❸ Control • Control indoor unit/ERV through the control window that appears on the screen. • Control total indoor units, the operation mode of indoor units, multiple selection, temperature, fan speed, and fan direction. Upper/Lower set temperature limit.
  • Page 652 05-3_control systems(082~141) 3/6/08 14:04 Page 120 Control Systems Integrated management system 3-2. S-NET3 (MST-P3P) Schedule control ➊ Schedule setting Able to set a schedule to control indoor units and ERVs. (creating, modifying, deleting). • Able to set weekly, daily, one day schedule. •...
  • Page 653 05-3_control systems(082~141) 3/6/08 14:04 Page 121 The 3 step (schedule operation setting) • Set up time by dragging on the time table. Set the schedule with the control panel on the right. • (operation mode. temperature setting, fan speed, fan direction, remote control use). •...
  • Page 654 05-3_control systems(082~141) 3/6/08 14:04 Page 122 Control Systems Integrated management system 3-2. S-NET3 (MST-P3P) ❷ Schedule modification • Click the set schedule display window twice to display the modification panel. Then it is possible to modify various functions such as schedule time, operation mode and temperature setting.
  • Page 655 05-3_control systems(082~141) 3/6/08 14:04 Page 123 ❸ Power management structure editing • Just as the structural editing at the monitoring, power management can be restructured to ensure greater convenience for administrators. Once the power management structure is edited, power consumption report and usage can be •...
  • Page 656 05-3_control systems(082~141) 3/6/08 14:04 Page 124 Control Systems Integrated management system 3-2. S-NET3 (MST-P3P) Statistics and analysis ➊ Indoor unit status Able to see the operation status of selected indoor units and indoor temperature for the present • and the past. •...
  • Page 657 05-3_control systems(082~141) 3/6/08 14:04 Page 125 System management ➊ Environment setting Set the environment of S-NET3. • • Set administrator password, language, temperature unit, default value for indoor unit, etc. • Determine if peak power will be displayed or not in the menu setting (Korean market only). Language setting Temperature unit setting (°C/°F) Whether or not peak power will...
  • Page 658 05-3_control systems(082~141) 3/6/08 14:04 Page 126 Control Systems Integrated management system 3-2. S-NET3 (MST-P3P) ❸ View event log • Able to check various information such as indoor/outdoor units connected to S-NET3, control device error/warning, information details by date. Query period setting Set the list of events Event display...
  • Page 659 05-3_control systems(082~141) 3/6/08 14:04 Page 127 ❺ DMS backup and restoration Able to backup and restore the DMS data connected to S-NET3. • • Backup refers to activities of storing data in the data folder in PC. Select all DMSs Backup Restoration Indicate a...
  • Page 660 05-3_control systems(082~141) 3/6/08 14:04 Page 128 Control Systems Integrated management system 3-2. S-NET3 (MST-P3P) 3) Installation (1) S-NET3 installation • Carry out a virus inspection in the PC before setting up a S-NET3 program. • Install S-NET3. • Programs to be installed in the PC during a program setup - Microsoft .Net Framework 2.0 - Microsoft SQL Server Desktop Engine Installation CD...
  • Page 661 05-3_control systems(082~141) 3/6/08 14:04 Page 129 (3) S-NET3 log information Contents E9000 Connection impossible E9001 Connection denied E9002 Connection finished E9010 WINK denied E9011 DMS password authentication failure E9012 Serial exchange failure E9100 General error on instruction transmission E9150 Attempt to transmit to a DMS not in connection E9151 Attempt to transmit to a DMS not registered E9200...
  • Page 662 • • Zone control Wired/Wireless remote control restriction • Applied to DVM, DVM PLUS, DVM PLUS II, DVM PLUS III, HR system, FJM, CAC • Power supply 12VDC, 3.0A Maximum communication length RS485 : Maximum 1km from the end to the other end...
  • Page 663 05-3_control systems(082~141) 3/6/08 14:04 Page 131 3) Main panel Power LED LAN LED Data LED Error LED Power switch – Press the S-NET mini to turn ON Menu switch – It shows the main menu window to users. Lock switch – Undesirable key press protection Keyboard switch –...
  • Page 664 05-3_control systems(082~141) 3/6/08 14:04 Page 132 Control Systems Integrated management system 3-3. S-NET mini (MST-S3W) 5) Option switch • DIP switch (SW1) : Use only for external contact signal control. DIP switch no. Pattern Control details Contact input No function (Default setting) Not applied 1.
  • Page 665 05-3_control systems(082~141) 3/6/08 14:04 Page 133 Pattern 3 External contact DI-2 (level-triggered) DI-1 External contact (level-triggered) Option switch External contact input to DI-1 Short contact : Starts all indoor unit operation. Open contact : Stops all indoor unit operation. External contact input to DI-2 Short contact : Disables the use of all wired/wireless remote controllers.
  • Page 666 05-3_control systems(082~141) 3/6/08 14:04 Page 134 Control Systems Integrated management system 3-3. S-NET mini (MST-S3W) 6) Flexible communication connection Ethernet connection to up to 4 DMSs Up to 256 indoor units of 4 DMSs can be controlled Ethernet RS485 connection to up to 16 centralized controllers (C1-C2 connection) Up to 256 indoor units are controlled through the centralized controllers.
  • Page 667 05-3_control systems(082~141) 3/6/08 14:04 Page 135 7) Menu (1) Main menu Name Description • Operation control and monitoring ( up to 256 indoor units) • Operation mode, temperature setting, airflow direction and fan speed • Temperature limit setting • Multiple control of indoor units Control and monitoring •...
  • Page 668 05-3_control systems(082~141) 3/6/08 14:04 Page 136 Control Systems Integrated management system 3-3. S-NET mini (MST-S3W) (2) Control and monitoring Description ON/OFF control Room temperature display Set temperature display Temperature Up/Down control Operation mode selection Fan speed selection Airflow direction selection Temperature limit setting enable/disable Temperature limit setting Schedule monitoring...
  • Page 669 05-3_control systems(082~141) 3/6/08 14:04 Page 137 Full display Description State display of indoor units Blue : Operation Gray : Stop Red : Indoor unit error Pink : Network error White : Not registered indoor unit R : Remote control restriction C : Temperature limit Indoor unit ON/OFF control Selected indoor unit name display...
  • Page 670 05-3_control systems(082~141) 3/6/08 14:04 Page 138 Control Systems Integrated management system 3-3. S-NET mini (MST-S3W) Schedule setting Making new schedule Schedule edition 1. Weekly/Daily schedule setting 1. On/Off time setting 2. Temperature/Mode setting 3. Wireless/Wired remote control restriction Today’s schedule monitoring Zone control Making new zone Zone initialization (automatic back-up)
  • Page 671 05-3_control systems(082~141) 3/6/08 14:04 Page 139 Security setting Default password : 1234 Password Enable/Disable Changing password System tracking Lower-layer device selection Device connection display (Centralized controller or interface module) Indoor unit address display Installation information System installation display Detailed indoor unit monitoring V-139...
  • Page 672 05-3_control systems(082~141) 3/6/08 14:04 Page 140 Control Systems Integrated management system 3-3. S-NET mini (MST-S3W) Hardware configuration Current date/time setting Static or dynamic IP setting System management Interface configuration 1. Ethernet connection to DMS 2. RS485 connection to centralized controller or interface module V-140...
  • Page 673 05-3_control systems(082~141) 3/6/08 14:04 Page 141 (3) Restriction on temperature setting Restriction on temperature setting is accomplished by incessant monitoring of indoor unit temperature setting through S-NET mini - device communication. If the temperature is not within the set limit, S-NET mini tries to set temperature repetitively to keep it within the range.
  • Page 674 05-4~6_control systems(142~171 3/6/08 14:09 Page 142 Control Systems V-142...
  • Page 675 05-4~6_control systems(142~171 3/6/08 14:09 Page 143 Power distribution system 4-1. SiM (WHM interface module) (MIM-B12) -------------------------- 4-2. Power distribution unit (MCM-B102) -------------------------------- V-143...
  • Page 676 05-4~6_control systems(142~171 3/6/08 14:09 Page 144 Control Systems Power distribution system 4-1. SiM (WHM interface module) (MIM-B12) 1) Features • Watt-hour meter interface unit • 8-channel real-time watt-hour consumption display • Automatic watt-hour meter tracking • Current communication state indication Power supply 9VDC ~ 12VDC, 500mA Maximum communication length...
  • Page 677 05-4~6_control systems(142~171 3/6/08 14:09 Page 145 3) Display and setting Name Description Address setting switch SiM address setting for DMS registration. Option switch No function. LED display Power supply, DMS communication and watt-hour communication display. Push buttons are used to display power consumption for the different Push button switch watt-hour meters, reset SiM software and carry out self-diagnosis for communication channels.
  • Page 678 05-4~6_control systems(142~171 3/6/08 14:09 Page 146 Control Systems Power distribution system 4-1. SiM (WHM interface module) (MIM-B12) 4) RS485 connection with DMS and watt-hour meters CH1 : Address 1 CH3 : Address 3 CH2 : Address 2 CH4 : Address 4 CH6 : Address 2 CH8 : Address 8 CH5 : Address 5...
  • Page 679 05-4~6_control systems(142~171 3/6/08 14:09 Page 147 6) Push button switch Button Function Next channel selection Previous channel selection Reset Channel loop-back test (Self-diagnosis) Reserved Reserved • If switch K4 is pressed, the SiM enters self-diagnosis test mode to check the hardware interface of each channel with loop-back test.
  • Page 680 05-4~6_control systems(142~171 3/6/08 14:09 Page 148 Control Systems Power distribution system 4-2. Power distribution unit (MCM-B102) 1) Features Mode Room Total Watt-hour distribution for max. 48 indoor units linked to 1 outdoor unit. • Supports max. 48 indoor units. • Displays total watt-hour consumption. •...
  • Page 681 05-4~6_control systems(142~171 3/6/08 14:09 Page 149 2) Button and display Mode Room Total Mode FAN WHM PDU DVM Error Room Total Name Description Press button to change a room number. Search button for each room The changed room number coincides with the main address of the indoor unit. Select Auto to change room number automatically, or select Manual to Auto / Manual mode button change a room number by button ➀.
  • Page 682 05-4~6_control systems(142~171 3/6/08 14:09 Page 150 Control Systems Power distribution system 4-2. Power distribution unit (MCM-B102) 3) Dimensional drawing (1) The external dimensions of the power distribution unit Unit : mm 56.5 126.2 (2) PCB’s composition of the power distribution unit SET NET Mode Mode...
  • Page 683 05-4~6_control systems(142~171 3/6/08 14:09 Page 151 4) Installation (1) Power distribution unit installation diagram R S T N Power line Comm. line 220V Mode Room Total Watt-hour meter comm. line Indoor/Outdoor comm. line 3-phase 4-line 380V~415V If possible, locate the power distribution unit in a place easy to connect with the watt-hour meter. (switch box ) (2) Power, comm.
  • Page 684 05-4~6_control systems(142~171 3/6/08 14:09 Page 152 Control Systems Power distribution system 4-2. Power distribution unit (MCM-B102) 4) Installation (3) Power distribution unit comm. timing flowchart Input power Screen display Power distribution unit ↔ Mode Indoor/Outdoor units comm. Room Power distribution unit ↔ Total Watt-hour meter Comm.
  • Page 685 05-4~6_control systems(142~171 3/6/08 14:09 Page 153 4-2. Power distribution unit (MCM-B102) 5) Function (1) Power distribution unit setup menu description Administrator’s password setup (default value “0000000”). Power distribution unit address setup (Applicable if there is more than one power distribution unit). Select a watt-hour meter manufacturer to be connected with the power distribution unit (1).
  • Page 686 05-4~6_control systems(142~171 3/6/08 14:09 Page 154 Control Systems Power distribution system (1) Watt-hour meter manufacturer connected with the power distribution unit. Setup value Omni Micronix China HANSUK Watt-meter Industrial Reserved Reserved RS485 RS485 Londian TECH Systems (2) Difference between auto/manual mode for indoor FAN power consumption. •...
  • Page 687 05-4~6_control systems(142~171 3/6/08 14:09 Page 155 External contact control system 5-1. Key-tag interface module (MIM-B02) ------------------------------ 5-2. External contact interface module (MIM-B14) ---------------------- V-155...
  • Page 688 05-4~6_control systems(142~171 3/6/08 14:09 Page 156 Control Systems External contact control system 5-1. Key-tag interface module (MIM-B02) 1) Features Interlock DVM air-conditioner with external controller Key-tag interface module is mainly used for accommodation facilities to control indoor units by using the contact of a card-key holder. - Indoor unit On/Off control by the external contact (Usable equipment : Card-key, Timer, Sensor) - Max.16 indoor units can be controlled.
  • Page 689 05-4~6_control systems(142~171 3/6/08 14:09 Page 157 3) Explanation of part names Name Description Display indoor units’ Main addresses when Key-tag I/M communicates with Communication checking 7-Segment outdoor unit normally. Communication connector Connect to outdoor unit (Indoor unit)F1/F2. (Key-tag I/M ↔ Outdoor unit) Option switch Indoor unit operation patterns can be set.
  • Page 690 05-4~6_control systems(142~171 3/6/08 14:09 Page 158 Control Systems External contact control system 5-1. Key-tag interface module (MIM-B02) 4) Additional functions Option switch setting These can set indoor unit operation patterns when the external contact is input. DIP SW State Note Description When the I/M contact is Close, indoor unit turns OFF (When the contact is Close, remote controller can’t be used).
  • Page 691 05-4~6_control systems(142~171 3/6/08 14:09 Page 159 Control timing example (1) Option switch K3 • ON : The external contact control indoor unit OFF only. • OFF : The external contact control indoor unit ON and OFF. Case 1 : K3=ON K1=OFF ➔...
  • Page 692 05-4~6_control systems(142~171 3/6/08 14:09 Page 160 Control Systems External contact control system 5-1. Key-tag interface module (MIM-B02) 4) Additional functions Control timing example (2) Option switch K4 • ON : After power reset, ignore initial I/M contact state. And start to control indoor unit by next contact state. •...
  • Page 693 05-4~6_control systems(142~171 3/6/08 14:09 Page 161 5) Installation External contact line wiring F1/F2 F1/F2 Main:0 Main:1 Variable equipment can be connected. Ex)Sensor, Card-key, Timer Ex) If you want to control the indoor unit of Main address “0”. Connect the contact lines to key-tag I/M terminals labeled “0” and “GND”. ❈...
  • Page 694 05-4~6_control systems(142~171 3/6/08 14:09 Page 162 Control Systems External contact control system 5-2. External contact interface module (MIM-B14) 1) Features Interlock DVM air-conditioner with external controller - Indoor unit On/Off control by the external contact (Usable equipment :Card-key,Timer,Sensor) - Output the indoor unit thermo ON/OFF state - Output the indoor unit error state 2) Dimensional drawing Unit : mm...
  • Page 695 05-4~6_control systems(142~171 3/6/08 14:09 Page 163 4) Installation External contact line wiring Indoor unit thermo Error signal ON/OFF signal output No-power contact signal input Ex)Sensor, Card-key, Timer 220VAC, 3A Indoor unit PCB CN83 Connect wire CN81 K9 K10 K11 K12 •...
  • Page 696 05-4~6_control systems(142~171 3/6/08 14:09 Page 164 Control Systems V-164...
  • Page 697 05-4~6_control systems(142~171 3/6/08 14:09 Page 165 Building management system 6-1. Lonworks interface module (MIM-B07) ---------------------------- V- 166 V-165...
  • Page 698 05-4~6_control systems(142~171 3/6/08 14:09 Page 166 Control Systems Building management system 6-1. Lonworks interface module (MIM-B07) 1) Features Lonworks I/M is mainly used to control the air-conditioning system with the open protocol for easy interface to unknown third-party companies. 2) Dimensional drawing Unit : mm V-166...
  • Page 699 05-4~6_control systems(142~171 3/6/08 14:09 Page 167 3) Explanation of part names Name Description Service button Press the button to bind with other I/Ms. Address setting switch Set Lonworks I/M address (Range : 0~3). Connection I/M ↔ Outdoor unit Connect to outdoor unit (Indoor unit) F1/F2. Operation State Description...
  • Page 700 05-4~6_control systems(142~171 3/6/08 14:09 Page 168 Control Systems Building management system 6-1. Lonworks interface module (MIM-B07) 4) Function Control and monitoring Function Description On/Off Operation on/off Set operation mode Auto/Cool /Heat /Fan Control Cooling mode :18~30°C, Set temperature Heating mode :16~30°C Set fan speed Auto /Low/Middle /High On/Off...
  • Page 701 05-4~6_control systems(142~171 3/6/08 14:09 Page 169 (1) nviIndoorMode SNVT_hvac_mode Operation DVM operation mode HVAC_OFF Last operation mode HVAC_Auto Auto mode HVAC_COOL Cooling mode HVAC_HEAT Heating mode HVAC_FAN_ONLY Fan mode (2) Setting temperature range : Cooling mode 18 ~ 30°C, Heating mode 16 ~ 30°C (3) nviFanSpeed State Value...
  • Page 702 05-4~6_control systems(142~171 3/6/08 14:09 Page 170 Control Systems Building management system 6-1. Lonworks interface module (MIM-B07) 5) Installation WIRING ➊ Connection between Lonworks interface module and outdoor unit. (example : DVM PLUS II) DC12V F1/F2 ❷ Connection between Lonworks interface module and Lonwork MMI F1/F2 F1/F2 F3/F4...
  • Page 703 05-4~6_control systems(142~171 3/6/08 14:09 Page 171 V-171...
  • Page 704 06_Installation(02~45) 3/15/08 4:34 Page 2 DVM PLUS III VI-2...
  • Page 705 3/15/08 4:34 Page 3 Installation DVM PLUS III / DVM PLUS III HR ..MCU installations ....VI-3...
  • Page 706 06_Installation(02~45) 3/15/08 4:34 Page 4 Installation VI-4...
  • Page 707 06_Installation(02~45) 3/15/08 4:34 Page 5 DVM PLUS III, DVM PLUS III HR 1-1. Changes from DVM PLUS III concerned with installation -------- 1-2. Outdoor unit combinations-------------------------------------------- 1-3. Space requirements (Service space)-------------------------------- 1-4. Placing the outdoor units ---------------------------------------------- 1-5. Electric specifications -------------------------------------------------- 1-6.
  • Page 708 3/15/08 4:34 Page 6 Installation DVM PLUS III, DVM PLUS III HR 1-1. Changes from DVM PLUS III concerned with installation DVM PLUS III, DVM PLUS III HR DVM PLUS II, DVM HR II 8 HP, 10 HP, 12 HP...
  • Page 709 06_Installation(02~45) 3/15/08 4:34 Page 7 DVM PLUS III, DVM PLUS III HR DVM PLUS II, DVM HR II 200~300mm Oil trap Less than 1m 2m or more No vertical trap No vertical trap • When the piping length between the outdoor units is 2m or more, a vertical trap has to be installed like above diagram.
  • Page 710 06_Installation(02~45) 3/15/08 4:34 Page 8 Installation DVM PLUS III, DVM PLUS III HR 1-2. Outdoor unit combinations 1) Basic models Total capacities of the Maximum number of Classification Capacity (HP) Model connectable indoor units (kW) connectable indoor units RVXVHT080GE / RVXVRT080GE 11.2 ~ 29.1...
  • Page 711 06_Installation(02~45) 3/15/08 4:34 Page 9 3) Compact combinations Total capacities Basic model Maximum number of the of connectable Classification Capacity (HP) RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVHT160GE connectable indoor units RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE RVXVRT160GE indoor units (kW) 25.2~65.5 28.0~72.8 30.8~80.1 33.6~87.4 36.4~94.6 39.2~101.9...
  • Page 712 06_Installation(02~45) 3/15/08 4:34 Page 10 Installation DVM PLUS III, DVM PLUS III HR 1-3. Space requirements (Service space) 1) Single installation (Unit: mm) Wall height unrestricted 300 or more(S2) 300 or more 10 or Front more 500 or more(S1) 200 or more...
  • Page 713 06_Installation(02~45) 3/15/08 4:34 Page 11 1-4. Placing the outdoor units 1) Anchor bolts position (Unit: mm) Model RVXVHT080/100/120GE RVXVRT080/100/120GE RVXVHT140/160GE 1200 1058 RVXVRT140/160GE Anchor bolt(4-ø15) 2) Removing fasteners of compressor’s leg (Only applied to 14/16HP, RVXVHT140/160GE, RVXVRT140/160GE) (1) Open the front cabinet near the bottom. The compressors are fastened with nuts at 6 places(14/16HP).
  • Page 714 06_Installation(02~45) 3/15/08 4:34 Page 12 Installation DVM PLUS III, DVM PLUS III HR 1-5. Electric specifications 1) Basic models Classification Capacity (HP) Model MCCB (A) RVXVHT080GE / RVXVRT080GE 25A, 30mA 0.1 Second or less RVXVHT100GE / RVXVRT100GE 30A, 30mA 0.1 Second or less...
  • Page 715 06_Installation(02~45) 3/15/08 4:34 Page 13 3) Compact combinations Basic model Capacity MCCB Classification RVXVHT080GE RVXVHT100GE RVXVHT120GE RVXVHT140GE RVXVHT160GE (HP) RVXVRT080GE RVXVRT100GE RVXVRT120GE RVXVRT140GE RVXVRT160GE 50A, 30mA 0.1 Second or less 60A, 100mA 0.1 Second or less 60A, 100mA 0.1 Second or less 75A, 100mA 0.1 Second or less 75A, 100mA 0.1 Second or less 75A, 100mA 0.1 Second or less...
  • Page 716 06_Installation(02~45) 3/15/08 4:34 Page 14 Installation DVM PLUS III, DVM PLUS III HR 1-6. Wiring works 1) External connection diagram of DVM PLUS III (1) 3 phase 4 wires 3 phase 4wires (380~415V) Main unit Sub unit 1 Sub unit 2...
  • Page 717 06_Installation(02~45) 3/15/08 4:34 Page 15 2) External connection diagram of DVM PLUS III HR (1) 3 phase 4 wires 3 phase 4wires (380~415V) Main unit Sub unit 1 Sub unit 2 Main unit Sub unit MCCB OF1 OF2 OF1 OF2...
  • Page 718 06_Installation(02~45) 3/15/08 4:34 Page 16 Installation DVM PLUS III, DVM PLUS III HR 1-6. Wiring works 3) Caution of wiring work Example) 3 phase 3 wires Connecting 3 phase 380~415V 1 Phase To sub unit 220~240V 1 phase (220~240V) and communication cable...
  • Page 719 06_Installation(02~45) 3/15/08 4:34 Page 17 1-7. Refrigerant piping works 1) Notice & Cautions Cautions Correct piping work Wrong piping work The refrigerant piping should be the same level or lower than connecting position of piping to outdoor units. Piping work should be run with side direction for better uniform distribution of refrigerant and oil like next diagram.
  • Page 720 06_Installation(02~45) 3/15/08 4:34 Page 18 Installation Introduction 1-7. Refrigerant piping works 2) Example of piping layouts (DVM PLUS III, DVM PLUS III HR) DVM PLUS III Example of piping layouts for DVM PLUS III Using Y-joint Using Header joint VI-18...
  • Page 721 06_Installation(02~45) 3/15/08 4:34 Page 19 DVM PLUS III HR Example of piping layouts MCU-4EAE1 MCU-4EAE1 EEV bypass valve (Close) EEV bypass valve (Open) Using Y-joint CU-4EAEV1 (EEV included) MCU-4EAE1 MCU-4EAE1 MCU-4EAE1 MCU-4EAE1 MCU-6EAE1 VI-19...
  • Page 722 06_Installation(02~45) 3/15/08 4:34 Page 20 Installation DVM PLUS III, DVM PLUS III HR 1-7. Refrigerant piping works 3) Piping examples DVM PLUS III Branch with Y-joint Branch with Y and Header joint Branch with Header joint One outdoor unit installed...
  • Page 723 06_Installation(02~45) 3/15/08 4:34 Page 21 DVM PLUS III HR Branch with Y-joint Using MCU only MCU-4EAE1 Using Y- joint CU-4EAEV1 and MCU (EEV included) EEV bypass valve EEV bypass valve EEV bypass valve EEV bypass valve (Close) (Close) (Close) (Close)
  • Page 724 06_Installation(02~45) 3/15/08 4:34 Page 22 Installation DVM PLUS III, DVM PLUS III HR 1-7. Refrigerant piping works 4) Pipe selection Branch joint : (D), (E), (F) Outdoor unit connection pipe size : (A1), (A2), (A3) ■ Branch joint of outdoor unit’s multi connection (D)
  • Page 725 06_Installation(02~45) 3/15/08 4:34 Page 23 Main pipe 1 size increment When the equivalent pipe length from outdoor unit to the farthest indoor unit is over than 90m, the main pipe (both liquid and gas pipe) has to be increased with 1 size like below table.
  • Page 726 06_Installation(02~45) 3/15/08 4:34 Page 24 Installation DVM PLUS III, DVM PLUS III HR 1-7. Refrigerant piping works 4) Pipe selection DVM PLUS III Additional refrigerant charging ■ Additional refrigerant has to be charged according to the length and size of EX) Additional refrigerant charging liquid pipe.
  • Page 727 06_Installation(02~45) 3/15/08 4:34 Page 25 DVM PLUS III HR Branch joint : (D), (E), (F) Outdoor unit connection pipe size : (A1), (A2), (A3) ■ Branch joint of outdoor unit’s multi connection (D) 12Hp 14Hp 16Hp A1 : Select the pipes according to the outdoor unit capacity with following table.
  • Page 728 06_Installation(02~45) 3/15/08 4:34 Page 26 Installation DVM PLUS III, DVM PLUS III HR 1-7. Refrigerant piping works 4) Pipe selection DVM PLUS III HR Main pipe 1 size increment When the equivalent pipe length from outdoor unit to the farthest indoor unit is over than 90m, the main pipe (both liquid and gas pipe) has to be increased with 1 size like below table.
  • Page 729 06_Installation(02~45) 3/15/08 4:34 Page 27 Additional refrigerant charging ■ Additional refrigerant is charged according to the length and size of liquid pipe. EX) Additional refrigerant charging Basic model Factory charging(kg) Liquid pipe size Additional refrigerant charging (O.D. mm) (kg/m) RVXVRT080GE ø6.35 0.02 RVXVRT100GE...
  • Page 730 06_Installation(02~45) 3/15/08 4:34 Page 28 Installation DVM PLUS III, DVM PLUS III HR 1-8. Option switches & function keys 1) Option switches Switch Setting Function Remarks Setting total quantity of Installed indoor units Main unit required only SW01/SW02 SW01 : The tens digit, SW02 : The units digit...
  • Page 731 06_Installation(02~45) 3/15/08 4:34 Page 29 Switch Setting Function Remarks Since supplying power, first oil return operation happens after 5hrs and then 7 hrs. Since supplying power, first oil return operation happens after 2hrs and then 2 hrs. Standard Defrost period setting Shorten defrost period by 20% approximately SW06 Standard fan step...
  • Page 732 06_Installation(02~45) 3/15/08 4:34 Page 30 Installation DVM PLUS III, DVM PLUS III HR 1-8. Option switches & function keys 2) Function keys Key function Display LED Push 1 time Refrigerant charging in heating operation “K” “1” “BLANK” “BLANK” Push 2...
  • Page 733 06_Installation(02~45) 3/15/08 4:34 Page 31 ❈ Note : LED display alphabet SEG 1 SEG 2 SEG 3 SEG 4 Display LED Key function SEG 1 SEG 2, 3, 4 Ex) 16 HP ➞ Off, 1, 6 Push 1 time Outdoor capacity Ex) Loading 13 sec ➞...
  • Page 734 06_Installation(02~45) 3/15/08 4:34 Page 32 Installation DVM PLUS III, DVM PLUS III HR 1-9. Error codes ① ② ③ ➃ ① Display alphabet at Description It displays from error 101 to error 700. It displays from error 701 to error 800.
  • Page 735 06_Installation(02~45) 3/15/08 4:34 Page 33 Error code Description Communication error between indoor and outdoor unit E-201 (Tracking failure or the setting quantity of indoor unit on outdoor unit’s PCB differs from the quantity of installed indoor unit.) E-202 Communication error between indoor and outdoor unit. (After tracking is completed, and then no response from indoor unit) E-203 Communication error between main and sub outdoor unit E-204...
  • Page 736 06_Installation(02~45) 3/15/08 4:34 Page 34 Installation DVM PLUS III, DVM PLUS III HR 1-9. Error codes Error code Description E-407 Compressor stop by high pressure’s protection control. E-410 Compressor stop by low pressure’s protection control. E-413 Protection control by sump sensor.
  • Page 737 06_Installation(02~45) 3/15/08 4:34 Page 35 MCU installations 2-1. Basic models ---------------------------------------------------------- 2-2. Refrigerant piping works ---------------------------------------------- 2-3. Wiring connections ---------------------------------------------------- 2-4. Option switches -------------------------------------------------------- 2-5. Setting of MCU’s switches-------------------------------------------- VI-35...
  • Page 738 06_Installation(02~45) 3/15/08 4:34 Page 36 Installation MCU installations 2-1. Basic models 1) MCU-4EAE1, MCU-6EAE1 Description Model Indoor unit’s Quantity of connectable indoor units Total capacity capacity per MCU’s port MCU-4EAE1 Up to 4 units 2.2~14.0kW Up to 44.8kW (16HP) Not included MCU-6EAE1 Up to 6 units ❈...
  • Page 739 06_Installation(02~45) 3/15/08 4:34 Page 37 MCU-4EAE1, MCU-6EAE1 (EEV not included) Wall mounted and ceiling model Slim 1 way cassette model Wall mounted model MCU-4EAEV1 (EEV included) Wall mounted model Slim 1 way cassette model EEV Bypass valve open Wall mounted model EEV Bypass valve close EEV Bypass valve EEV Bypass valve...
  • Page 740 06_Installation(02~45) 3/15/08 4:34 Page 38 Installation MCU installations 2-2. Refrigerant piping works • Regarding piping work between the outdoor unit and MCU kits, selection of the branch joints and the piping work between branch joints and the indoor unit, see the installation manual for the outdoor unit and other technical documents. 1) General refrigerant piping work with MCU VI-38...
  • Page 741 06_Installation(02~45) 3/15/08 4:34 Page 39 2) Connection of refrigerant pipes (Indoor/Outdoor) From outdoor unit Gas pipe connection (Flange) High pressure gas pipe connection (Brazing) Liquid pipe connection (Flare) To indoor unit Liquid pipe to indoor unit Gas pipe to indoor unit 3) Connection size of refrigerant pipes 5/8”(15.88mm) : Gas pipe connection (Indoor unit) 3/8”(9.52mm) : Liquid pipe connection (Indoor unit)
  • Page 742 06_Installation(02~45) 3/15/08 4:34 Page 40 Installation MCU installations 2-2. Refrigerant piping works 5) Piping layouts Example of piping layouts MCU-4EAE1 MCU-4EAE1 EEV bypass valve (Close) Using Y-joint EEV bypass valve (Open) CU-4EAEV1 (EEV included) MCU-4EAE1 MCU-4EAE1 MCU-4EAE1 MCU-4EAE1 MCU-6EAE1 VI-40...
  • Page 743: Wiring Connections

    06_Installation(02~45) 3/15/08 4:34 Page 41 2-3. Wiring connections Connection of the power cable (3 phase 4 wires) Switch board Outdoor unit Indoor unit 1phase 3phase 2 wires 4wires 220~240V 380- 415V~ MCCB MCCB Pull box Earth Earth Wired remote Indoor controller communication cable Connection of the power cable (3 phase 3 wires and 1 phase 2 wires)
  • Page 744 06_Installation(02~45) 3/15/08 4:34 Page 42 Installation MCU installations 2-3. Wiring connections CASE 1 Indoor Indoor Outdoor MCCB unit unit unit 220-240V CASE 2 Indoor Indoor Indoor Outdoor MCCB unit unit unit unit 220-240V ❈ : Supply the 220-240V power to L, N of MCU separately with outdoor unit. Indoor Unit Indoor Unit ❈...
  • Page 745 06_Installation(02~45) 3/15/08 4:34 Page 43 2-4. Option switches Indoor unit’s activating dip switch Rotary switch for indoor unit address Rotary switch for MCU address ➀ Set the rotary switch for the indoor unit ADDRESS on the MCU PCB same as the ADDRESS of connected indoor unit.
  • Page 746 06_Installation(02~45) 3/15/08 4:34 Page 44 Installation MCU installations 2-5. Setting of MCU’s switches Indoor unit’s activating dip switch Rotary switch for MCU address Rotary switch for indoor unit address Indoor unit’s activating dip switch Main address of indoor unit (On : Use, Off : Not use) ❈...
  • Page 747 06_Installation(02~45) 3/15/08 4:34 Page 45 Key operation ❈ Note : LED display alphabet Display MCU Display indoor SEG 1 SEG 2 SEG 3 SEG 4 status unit's address Display segment Display contents Remarks (Pushed time) Blank Ex) MCU address 0 Blank Ex) MCU address 1 MCU address...
  • Page 748 1/8/08 3:30 PM Page 1 2008.00 DB98-00000A(1) Samsung System Appliance Division Air Conditioning Research & Development System Group 1 416 Maetan-3Dong, Yeongtong-Gu, Suwon City Kyungki-Do, Korea 442-742 TEL : 82-31-200-8226 FAX : 82-31-200-7999 Internet Website : www.dvmsystem.com...