ABB -i-Bus-KNX Millenium Technical Reference Manual page 37

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Parameters for "Set values manual"
Area for manual set value setting
max. manual lowering during heating mode
(0 - 15 K)
Resetting of the manual adjustment for
receipt of a basic set value
Resetting of the manuel adjustment for
change of operation mode
Reset onsite operation via options object
Parameters for "Set values cooling"
Base setpoint cooling (°C)
Setpoint standby cooling, setting dependent
(K)
Setpoint temperature ECO cooling, setting
dependent (K)
Setpoint heat protection (°C)
KNX Technical Reference Manual | 1473-1-7819
Settings
deactivated
+/-1 K
+/-2 K
+/-3 K
+/-4 K
+/-5 K
+/-6 K
+/-7 K
+/-8 K
+/-9 K
+/-10 K
+/-11 K
+/-12 K
+/-13 K
+/-14 K
+/-15 K
0 ... 15 K
• deactivated
• activated
• deactivated
• only ECO mode adjustment for change
from ECO mode
• activated
• deactivated
• with every value
• with value 0
• with value 1
Settings
10 ... 40
0 ... 15
0 ... 15
10 ... 45
Description of applications /
Comments
Only available when parameter "Area for
manual set value setting" is set on "+/-
1 K ... +/-15 K".
Comments
objects
— 37 —