UPS Characteristics
§
1
4
.
4
S
1
4
.
4
S
Item
Type
Model
Output capacity
Cooling system
Input terminals
Number of phases
Voltage
Frequency
Power requirements
Input power factor
Output terminals
Number of phases
Voltage
Voltage accuracy
Frequency
Frequency accuracy
Voltage waveform
Distortion factor of
voltage waveform
Rapid load
Transient
Power outage,
voltage
variation
Rapid input
voltage change
Load power factor
Overcurrent protection
Overload
capability
Type
Quantity
Rated capacity
Backup time
Expected service life
Generated heat
Input leakage current
Operating environment
Acoustic noise
*1. Input voltage range of normal operation will be changed with connected load capacity.
When the load factor is less than 70%, voltage range will be –40% to +15%. When the load factor is 70% or above,
the voltage range will be –20% to +15%.
*2. The allowable range for the input frequency is ±8% when auto-detect is set and 40 Hz to 120 Hz when a fixed setting is
set. When the input frequency recovers from being outside the allowable range, the range is ±8% regardless of which
setting is set. The inverter will not start if the input frequency is not within the range of the values (±1%, ±3, or
±5%) set for the frequency synchronization compliance range.
*3. When the distortion factor of the input voltage waveform is less than 1%.
*4. When the auto-detect setting is set, you can select a frequency compliance range from ±1%, ±3%, and ±5%.
When a fixed frequency is set, the output frequency is fixed to the set frequency (50 Hz or 60 Hz) regardless of the
input frequency.
*5. The inverter is capable of operation synchronized with AC input frequency and switchover operation without
interruption provided that the AC input frequency is within the rated frequency range, and the AC input voltage is
within the rated voltage range.
*6. Some of the specifications for a UPS with long backup times differ from the specifications listed in the table above.
See the extension battery specifications instruction manual.
*7. The UPS contains batteries. The battery service life will be foreshortened if the UPS is used in an environment
where the ambient temperature exceeds 30°C (86°F).
45
p
e
c
i
f
i
c
a
t
i
o
n
s
p
e
c
i
f
i
c
a
t
i
o
n
s
Standard or Performance
Forced air cooling
Field Wiring Type Terminal block
Single-phase, 2-wire
200 V, 208 V, 220 V, 230 V, 240 V
Field Wiring Type Terminal block
Single-phase, 2-wire
200 V, 208 V, 220 V, 230 V, 240 V
Within rated voltage ±2%
Within rated accuracy ±1%, 3%, or 5%
Linear load: 3% or less
When rectifier load: 8% or less
change
Within rated voltage ±5 %
recovery
Auto switch to bypass circuit at 110% or more
Inverter
110% (1 minute) / 118%(instantaneously)
Bypass
200% (30 seconds) / 800% (2 cycles)
Small-sized valve regulated lead-acid battery
5 minutes when load power factor 0.8,
4 minutes when load power factor 0.9
Ambient temperature: 0 to 40°C (32 to 104°F)
Relative humidity: 20 to 90%
A11J502A002TU
A11J502U002T
5 kVA/4.5 kW
50 Hz or 60 Hz
5.5 kVA
0.95 or more
50 Hz or 60 Hz
Sine wave
0.9 (lag)
16 (12 V / 1)
5 Ah / Battery
5 years
339 W
4 mA or less
45 dB or less
Notes
Selectable, rated voltage same as output voltage
At shipment: 200 V
Auto-detect, fixed setting selectable,
at shipment: auto-detect
Max. capacity during battery recovery charging
During rated input voltage
At shipment: 200 V
Same as input frequency (auto-select)
1%, 3%, and 5% selectable, at shipment: 3% *4
When UPS free running operation: Within ±0.5%
During rated output
0% ⇔ 100% at transient or output switch
During rated output
±10% variation
Variation range 0.7 (lag) to 1.0
With auto return function
Series of 16
20 minute-rate
At 25 C (77 F) ambient temperature, initial
value
At 25 C ambient temperature
During rated output
No condensation
1 m (approx. 40 inches) from front of UPS,
A characteristics
*1
*2
*3
*5
*6
*7