Thank you for choosing the SANUPS A11J. SAVE THESE INSTRUCTIONS This manual contains important instructions for A11J that should be followed during installation and maintenance of the UPS and batteries to protect the safety of the customer and the service technician .
Page 3
Notes about UPS Models This manual is for the UPS model authorized with UL standard shown in the following table. Confirm your UPS model before using the UPS. Capacity Type Model* 5 kVA A11J502A002TU A11J502U002T * In this instruction manual, the name of UPS is described as Model “A11J502U002T” depending on the item explained. §8.
Before Use § The following shows the procedures to use the UPS. Be sure to follow the procedures described in this instruction manual to ensure safe and proper use of the UPS. Check the safety precautions ⇒ pages 2 to 5 Check the operating precautions ⇒...
PRECAUTIONS (IMPORTANT SAFERY INSTCUTIONS) This manual contains important instructions for operating and maintaining the A11J Series and the batteries to protect the safety of the customers and the service technician. Before installing, operating, performing maintenance or inspecting the UPS, be sure to read this manual and accompanying documents carefully to obtain a clear understanding of the information related to its operation, safety and important precautions.
Page 6
Safety Precautions 1. Relocation, Transportation and Moving Precautions CAUTION ! Be careful to avoid falling or dropping the UPS during relocation, transportation, as bodily injury could result. Be careful to avoid back strain when handling the UPS. To avoid bodily injury or a malfunction caused by dropping the UPS, do not tilt the UPS more than 10 degrees to either side when moving it vertically.
Safety Precautions 4. Operating Precautions WARNING ! Immediately shut down the UPS if it malfunctions, or if an unusual odor or noise is observed. Failure to do so may result in a fire. To avoid electric shock, do not open the cover of the UPS. Do not detach the cover of the options, except when you use some options.
SANYO DENKI. Do not use batteries after their service life has expired. Doing so may result in fuming or fire. Additionally, the battery backup function may fail to operate with such batteries, so that power will not be supplied to the load when a power outage occurs.
Operating Precautions § § (1) Input Power Supply and Power Supply Capacity The following table shows the ratings for the AC input power of this UPS. For the voltage and frequency variation ranges, see §14.4 “Specifications.” AC Input Input Input Branch Name AC Input Voltage Rating Circuit Breaker...
Conducting an insulation test with the UPS connected may damage electronic components such as the built-in arrester. (6) The UPS can be mounted on a rack (L-shaped support rails are required). For the information of the needed parts, how to install and more, contact your supplier or SANYO DENKI representative.
*1. Rack Mounting Brackets are used for installation on a rack. However the L-shaped support rails are required to install on a rack. For the information of the needed parts how to install on a rack and more, contact your supplier or SANYO DENKI representative.
⑫ Option card slot OPTION CARD For inserting an option card Notes *1. For information on various optional equipment, contact your supplier or SANYO DENKI representative. *2. In this manual, breakers and switches are displayed enclosed in like MAIN MCCB .
Part Names § ② UNINTERRUPTIBLE POWER SUPPLY ① ③ ⑤ ⑥ ⑩ ⑧ ⑦ ⑨ ④ Name Label Color Function When input power is normal ① Input LED Green INPUT Blinking When input power is abnormal ② Backup LED Green When the battery is operating BACKUP ③...
Part Names § ④ ① ② ③ ⑤ Name Label Color Function When input power is normal ① Input LED Green INPUT Blinking When input power is abnormal When supplying power by inverter operation ② Output LED Green OUTPUT Blinking When supplying power by bypass operation ③...
8 CTS 9 RI Fixing Screw (inch) CARD I/F ② Connect the connection cable of an optional Sanyo LAN interface card. When connecting a LAN interface card, set the interface to (work station). For the Card interface connector LCD Panel Operating interface setting procedure, see §3.5 “Setting PC Interface”...
Page 16
Part Names Name Function SIGNAL I/F Outputs status information of the UPS such as a power outage or voltage drop. ③ Contact signal External Transmission Signals and Shutdown Input Signals interface connector Pin No. and Signal Name Explanation Status when Operating This signal is output when there is a power outage or 1-8: ON...
Page 17
Part Names Name Function REMOTE/EPO Use these terminals for controlling the UPS with a non-voltage contact from an external ⑤ device. External control terminals REMOTE/EPO Terminal Names External Appearance 6 COM terminals 5 EPO 4 COM 3 Remote OFF REMOTE 2 COM terminals 1 Remote ON...
Installation and Wiring § Install the UPS in the installation location, attach the LCD panel, and perform the wiring work. When installing and wiring the UPS, carefully follow the instructions in this instruction manual. § Installation work should be performed only by technically qualified personnel. When installing the UPS, carefully follow the instructions in this Instruction Manual.
Installation and Wiring § Place the UPS horizontally in the installation location so that the Unit Control Panel on the front of the UPS is on the right side. Do not place objects on top of the UPS. Doing so may damage the UPS. Unit Control Panel Unit Control Panel §...
Installation and Wiring § ① Prepare the LCD panel, LCD panel connection cable, and two screws C for securing the LCD panel (only when securing the LCD panel), that are supplied with the UPS. Screw C: For securing LCD panel M3×6 LCD Panel Connection Cable LCD Panel...
Page 21
Installation and Wiring ⑤ Insert one end of the LCD panel connection cable into the connector at the position shown in the diagram. ⑥ Check that the forced bypass switch Forced Bypass above the connector is set to the “Inverter” side. ⑦...
Installation and Wiring § Wiring work should be performed by technically qualified personnel. When wiring the UPS, carefully follow the instructions in this instruction manual. Incorrect wiring may result in electric shock and/or fire. There is the danger of electric shock so wear insulated gloves as a preventive !...
Page 23
Installation and Wiring ⑥ Connect the ground to the “ ” terminal of the terminal block. Use D class grounding for the ground. ⑦ Connect the utility power supply to the “INPUT L and N” input terminals. ⑧ Connect the customer’s load devices to the “OUPUT L and N“ output terminals.* *Note A breaker for a branch circuit protection of output is needed between the UPS and the customer’s load.
For details on wiring and settings, see §12. “Using Power Management Software” or the instruction manual of the optional equipment. For details on optional equipment, contact your supplier or SANYO DENKI. REMOTE/EPO Terminal Connection Method Connect and use, for example, a switch or a contact of the customer’s system that matches the terminal specifications.
Preparation Before Operation § § ① Check the settings in the setting menu of the UPS. LCD Panel Operating Manual See §3. “Setting UPS” of the , and check the settings. The factory default settings of the UPS are indicated by the “*” mark in the Default Setting column of the “List of Settings.”...
Green: Green: Off Red: Off Blinking ↓ Green: Blinking Lit* SANYO DENKI Green: Off SANUPS A11J Red: Off After approx. 5 sec. - STANDBY - ① Set this to “ON” Vi=*** Fi=*** * Note Green: Off If “Green INPUT” does not change from blinking to always on, the UPS cannot be charged.
Green: Off Red: Off Blinking ↓ Green: Blinking SANYO DENKI Green: Off SANUPS A11J Red: Off After approx. 5 sec. - STANDBY - Vi=*** Fi=*** ① Set this to “ON” Green: Off Check that “Green INPUT” has changed from blinking to always on, and then proceed to step ②.
Page 29
Are “Red ALARM” and “Red WARNING” on? Contact your supplier or SANYO DENKI. Contact your supplier or SANYO DENKI when “Red ALARM” and “Red WARNING” are on or when the UPS does not operate properly even if you perform the corresponding countermeasure above.
Green: Green: Off Red: Off Blinking ↓ Green: Blinking SANYO DENKI Green: Off SANUPS A11J Red: Off After approx. 5 sec. - STANDBY - ① Set this to “ON” Vi=*** Fi=*** Check that “INPUT (Green)” has Green: Off changed from blinking to always on, and then proceed to step ②.
Page 31
Operating Procedures After checking the startup of the UPS in step ④, turn ON the power of the load devices. Notes on UPS startup *1. If the “CONTROL NG” is displayed, the UPS cannot be started because, for example, there is an input power supply error.
Operating Procedures § Follow the procedure below to shut down the UPS. Be sure to shut down the load devices prior to shutting down the UPS. ① Press any key on the LCD panel to display the screen. ② Press ③...
Operating Procedures § You can use the control panel on the right side of the front of the UPS to start up and shut down the UPS. Startup Operation ① Set MAIN MCCB on the front of the UPS to “ON.” ②...
Service technician * What are service technicians? This term is used to indicate service technicians from SANYO DENKI or entrusted by SANYO DENKI with knowledge of this UPS. Maintenance work must not be performed by other than a qualified service technician.
Inspection and Maintenance § Be sure not to inspect the inside of the UPS. Doing so may result in an electric shock, burn, injury, smoke, or fire. Do not touch the fan on the back of the UPS when cleaning the UPS or !...
Inspection and Maintenance § § Test the batteries. You can do this without stopping the load devices connected to the UPS. When the UPS is shipped from the factory, it is set up to perform an automatic battery test once every 180 days.
The buzzer will sound again each time you start the UPS. This will continue until you replace the batteries. Note If any other trouble occurs or you think there is a malfunction, contact your supplier or SANYO DENKI.
See §3.11 “Setting UPS Operation at OFF” in the Blinking Operating Manual and check the setting value. The default setting is “OFF.” Red ALARM: Lit Nothing is The UPS has malfunctioned. All other LEDs indicated. Contact your supplier or SANYO DENKI. are off.
Page 39
All: Off - See §8.1 “UPS Startup” and check the correct operating procedure. Cannot operate the unit The UPS has malfunctioned. Contact your supplier or SANYO Red ALARM: Lit - control panel. DENKI. on the unit control panel set to “ON”? If it is set to MAIN MCCB “OFF,”...
Page 40
Contact your supplier or SANYO DENKI. Note If the UPS does not operate normally even if you perform the countermeasures above, or if any other trouble occurs or you think there is a malfunction, contact your supplier or SANYO DENKI.
Using Power Management Software § What is power management software “SANUPS SOFTWARE STANDALONE” (supplied CD-ROM)? This software is for managing the power supply with a computer by communicating between the UPS and computer (personal computer, workstation, etc.). Install and use the power management software on your computer. Installation Guide and User Guide For more information, see the in the “PDF”...
Page 43
When using SANUPS SOFTWARE STANDALONE, note the following points for the items displayed on the main screen. User Guide For details on the main screen, see §6.1 “Main Screen” in the of SANUPS SOFTWARE STANDALONE. Main Screen of SANUPS SOFTWARE STANDALONE A11J*** 200V 200V Battery Charge Indication 5min.
Using Operating System Standard UPS Service § § The standard UPS service of the operating system can be used to perform an automatic shutdown when a power outage occurs. Connect the PC I/F connector of the UPS and the serial connector of the computer with the supplied communication cable. When using the standard UPS service of the operating system, set the interface to “Standalone.”...
Page 45
Using Operating System Standard UPS Service ④ Click the “Configure...” button. Click Configure... ⑤ Make the settings shown in the following figure, and then click the “OK” button. When you return to the screen in step ①, click “Apply”. Item Description A Enable all notifications Check this if you want to display all warning messages related to power failures.
At the same time, “Red ALARM” lights and the buzzer sounds. The power supply route is the same as for an overload. Output from the UPS will stop if a power outage occurs during bypass operation due to a UPS failure. Contact your supplier or SANYO DENKI.
Continuous tone ① * ② **・・・・・・**・・・・・・ Press to stop the buzzer. Continuous tone ③ ********・・・・・・ ④ ****・・・・・・****・・・・・・ ⑤ *****・・・・・・*****・・・・・ ⑥ *******・・・・・・*******・・・・・ See §10. "Buzzer Sounds” and perform the corresponding countermeasure. If the UPS has malfunctioned, contact your supplier or SANYO DENKI.
UPS Characteristics § Item Standard or Performance Notes Type A11J502A002TU Model A11J502U002T Output capacity 5 kVA/4.5 kW Cooling system Forced air cooling Input terminals Field Wiring Type Terminal block Number of phases Single-phase, 2-wire Selectable, rated voltage same as output voltage Voltage 200 V, 208 V, 220 V, 230 V, 240 V At shipment: 200 V...
This warranty is void in the event of any modifications or changes to the product supplied by SANYO DENKI. This warranty is void in the event of any improper use of the product supplied by SANYO DENKI, or failure to use the product as specified in this Instruction Manual.