Operating Procedures
§
8
.
2
U
P
8
.
2
U
P
Follow the procedure below to shut down the UPS.
Be sure to shut down the load devices prior to shutting down the UPS.
① Press any key on the LCD panel to display the screen.
② Press
STATUS
④ Check that the LCD display and LEDs are in the states shown in the diagram below.
- STANDBY
****
If the UPS will not be used for one week or more, proceed to step ⑤.
⑤ Set MAIN MCCB
The LCD panel and
all LEDs turn off.
Notes
If
MAIN MCCB
power outage occurred. Be aware that when the input supply is restored, the full capacity of the
backup function will not be available until the batteries have had time to recharge.
Recharge the UPS periodically when you store the UPS for a long period after shutting down
the UPS using the procedure above. For details on charging, see ④ of §3.3 "Usage
Precautions."
29
S
S
h
u
t
d
o
w
n
S
S
h
u
t
d
o
w
n
.
[Select]=INV OFF
[Back]=Cancel
3
2
Green: Lit Green: Off Red: Off
to "OFF."
is set to "OFF" while the UPS is operating, the batteries are discharged as if a
③ Press
.
INV OFF
Control OK
- STANDBY
****
Green: Off
When shutting down the UPS daily,
do not touch MAIN MCCB . Leave it
set to "ON."
⑤ Set this to "OFF."
The screen changes
after approx. 1 sec.
Green: Lit
Green: Off
Red: Off