Commissioning
5.5.2

Restoring the Saved Configuration

To restore the saved configuration, you have to delete all the files on the
CompactFlash card and transfer the saved copy to the CompactFlash card.
IMPORTANT
When you delete the files on the CompactFlash card, the saved drive parameters
are permanently lost!
When re-importing the saved files, you must ensure that none of the files in the
"User" sub-folder on the CompactFlash card has a write-protection attribute. This
can occur, for example, if the copy of the CompactFlash card was stored
temporarily on a CD.
The CompactFlash card directory must be structured in the same way as before. If
you move individual files to sub-folders, you may not be able to use the
CompactFlash card.
5.6

Resetting Parameters to the Factory Settings

The factory settings represent the defined original status of the cabinet unit on
delivery.
Resetting the parameters to the factory settings means that all the parameter
settings made since the system was delivered are reset.
"Extended" access level
p0009 = 30
p0976 =
Press OK
POWER ON
Fig. 5-8
Procedure for resetting parameters to the factory settings
5-10
Setting the "Extended" access level on the operator panel
Set <key pushbutton> - <access level> - <"Extended">
Setting the parameter filter to "Parameter reset"
<MENU> <device commissioning> <select>
Set p0009 = 30 in the following dialog screen
Resetting all the parameters to the factory settings
All the cabinet unit parameters are reset the SINAMICS G150
factory settings
- 380 V - 480 V, 110 kW - 250 kW: p0976 = 20
- 380 V - 480 V, 315 kW - 560 kW: p0976 = 21
- 660 V - 690 V, 75 kW - 800 kW: p0976 = 22
Saving the parameters
When you press F5 (OK), all the parameter settings are set to
the factory setting and saved to the CompactFlash Card.
The system has finished saving the data when the text "busy ..."
in the status bar is no longer displayed.
POWER ON
To activate the parameter reset to factory setting, switch the
power supply off and then on again.
11/03
SINAMICS G150