7.2.2

Minimum Speed

Description
Specifying a minimum speed allows you to disable a specific range about speed 0
1/min for stationary operation.
Signal Flow Diagram
Setp_after_Lim
r1114
Fig. 7-1
Setting Parameters
p1080
Minimum speed
Setting parameter for the minimum speed. This speed is not undershot during operation.
r1112
Speed setpoint after minimum limit
Display of speed setpoint after the minimum limit.
SINAMICS G150
Operating Manual
Minimum speed
Suppress. speed
Signal flow diagram: Minimum speed
Setpoint Channel and Closed-Loop Control
p1080
y
x
-1
Minimum speed
Setting range: 0.000 ... 19500.000 1/min
Factory setting: 0.000 1/min
Unit: 1/min
nSet_afterSkip
r1112
y
x
7-3