Diagnosis / Faults and Alarms
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
Replace affected component.
Acknowl.:
Immediate
F30832
Power section DRIVE-CLiQ: Telegram failure
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
- Check for break in DRIVE-CLiQ or faulty contacts in connector.
- Check 24 V supply of affected component.
- Replace affected component.
See also: p9916
Acknowl.:
Immediate
F30833
Power section DRIVE-CLiQ: fault in cyclic data transfer
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
- Check firmware states of affected components.
- Replace affected component.
Acknowl.:
Immediate
F30834
Power section DRIVE-CLiQ: Hardware defect
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
Replace affected component.
Acknowl.:
Immediate
F30835
Power section DRIVE-CLiQ: fault in cyclic data transfer
F30836
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
- Check firmware states of affected components.
- Replace affected component.
Acknowl.:
Immediate
F30837
Power section DRIVE-CLiQ: Hardware defect
F30838
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and affected power section defective.
Remedy:
Replace affected component.
Acknowl.:
Immediate
F30860 -
CU DRIVE-CLiQ: Data transfer faulted / Telegram faulted
F30871
Reaction:
OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
Bit 0 - 7: Number of the affected component
(r0949):
Bit 8 - 31: Reserved
Remedy:
- Check cabinet design and cabling for EMC conformity.
- Replace affected component.
Acknowl.:
Immediate
F30872
CU DRIVE-CLiQ: fault in cyclic data transfer
F30873
Reaction:
OFF2
Cause:
Reserved for later use.
Remedy:
Reserved for later use.
Acknowl.:
Immediate